1ph 18pole ins busbar fork

Max 4 Chassis Assemblies And Insulated Busbars, 1 Phase, 18 Mod Fork, 80A

Catalogue Number: 4BB4/18
1ph 18pole ins busbar fork
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
Network number of phases
1 phase
[In] rated current
80 A
Connector type
fork
Number of poles
18
Sustainable offer status
Green Premium product
REACh Regulation
Free of Substances of Very High Concern above the threshold
REACh free of SVHC
Yes
EU RoHS Directive
Compliant
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
ENVPEP1707001EN

Frequently Asked Questions

hide show

Is there a 2 pole busbar that suits the RCBM combo breakers?

No, unfortunately there isn't a 2 pole busbar that suits the RCBM combo.
However you can use the 4BB4/12 but this only connects the active and the neutral still needs to be wired.

For further information please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures/I0000126.pdf

What is the Busbar to suit an RCBE216/30S?

The busbar to suit use to be 4BB4/12, however that part is no longer available. It has been replaced by the schneider model 21501.
 
Description Ratings
Rated operational current at 40°C (Ie) 80 A
Rated conditional short-circuit current of an assembly (Isc) Compatible with the breaking capacity of Schneider E lectric circuit breakers
Insulation voltage (U i) 440 V
Rated voltage (U e) 230 V (P4 + N) - 400 V (3Ph + N)
Rated impulse withstand voltage (U imp) 6 kV
Degree of protection IP20
F ire resistance to IE C 69 5-2-1 Self-ext inguishing 9 60°C 30 s
Colour RAL 7035
Number of 18 mm modules Comb busbar 1 12

What is the kA rating for the busbar 4BB4/12/3?

The kA rating for the busbar 4BB4/12/3 is - 20kA for 0.1s

What would be the replacement part for the 4BB5/26.

 21501 for a 12 module and a 21503 for the 24 module. these are a Schneider part which is equivalent to the 4bb5/26
Clipsal’s range of busbars are available in 63A - 250A versions and have been specifically designed to make installations quicker and easier.
Please see following link for further information and complete range.
https://www.clipsal.com/Trade/Products/ProductDetail?catno=4BB5/26

Do you do a insulated single phase busbar with Pin Teeth for 12 modules?

Unfortunately we only have a 4BB1/24 which is 24 Poles / Modules.