Halogen content performance
Halogen free plastic parts product
Product specific application
arc fault detection
Number of protected poles
1
Breaking capacity
6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Earth-leakage sensitivity
30 mA
Earth-leakage protection time delay
instantaneous
Earth-leakage protection class
class A
Suitability for isolation
yes
Residual current tripping technology
voltage dependent
Trip unit technology
thermal-magnetic
Earth-leakage protection
integrated
Device location in system
outgoer
Magnetic tripping limit
5...10 x In
[Ics] rated service breaking capacity
6000 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Rated breaking and making capacity
500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1
Limitation class
3 conforming to AS/NZS 61009.1
[Ui] rated insulation voltage
250 V AC 50 Hz between phase and neutral400 V AC 50 Hz between phases
Threshold tripping voltage
275 V +/- 5 V
[Uimp] rated impulse withstand voltage
4 kV conforming to AS/NZS 61009.1
Contact position indicator
yes
Locking options description
padlocking device (A9A26970)
Tightening torque
2-2 N.m
Comb busbar and distribution block compatibility
YES
Heat dissipation
3.50-3.50 W at 230 V - 16 A
Pollution degree
2 conforming to AS/NZS 61009.12 conforming to IEC 62606
Tropicalisation
severity B conforming to IEC 60068-2-30 for 28 d
Operating altitude
2000 m