Frequently Asked Questions
hide
show
What causes a bOF fault code on ATV61 and ATV71 drives?
Issue:
BOF trip on ATV61/71.
Product Line:
ATV61, ATV71
Environment:
All serial numbers, all model numbers.
Cause:
N/A
Resolution:
If the DB resistor protection is set to Freewheel (yes), the drive faults on bOF on power up. This is because the drive is looking for a DB resistor connected.
Set parameter brP (DB resistor Protection) to NO or check the resistor that is connected to the PA and PB connections.
What is the adjustment range of the solid state overload relay on an 8940SSD4025?
Issue:
Solid State Overload Relay adjustment range on 8940 Type SS Pump Panels.
Product Line:
Class 8940 Pump Panels
Environment:
North American Products
Resolution:
8940SSC2007 and SSC4010 use 9065SS210 and has an adjustment range of 9A - 27A
8940SSD2015, SS4025 and SSD4030 use 9065SS210 and has an adjustment range of 15A - 45A.
8940SSF2050 and SSF1400 use 9065SS310 and has an adjustment range of 45A - 135A.
Are EasyPact CVS circuit breakers for sale in the USA or Canada?
Product Line:
EasyPact CVS circuit breakers
Cause:
This breaker is popular overseas and there is interest in the US
Resolution:
There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.