screw 125 bugle jar 8x50mm

General Accessories Screws, Bugle Head, Self Drilling Point, 8 X 50mm, Jar 125

Catalogue Number: 357/50J
screw 125 bugle jar 8x50mm
Retail
$27.36
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal
Material
steel
Surface treatment
zinc plated
Screw gauge
8g
Length
50 mm
Shape of screw head
  • pozidriv No 2
  • bugle head
    • Screwdriver shape
      Philips
      Screw type
      self drilling
      Size of screw head
      9 mm
      Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      529 g
      Package 1 Height
      65 mm
      Package 1 width
      65 mm
      Package 1 Length
      113 mm
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP060307EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Specifications

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What is the part number for the bitsa box?

      The part number for the bitsa box is 357TB.
      Some of the key features are:
      • Tool boxes
      • 12 compartment transparent box with assorted screws, screws and quantities included
      • Includes: 357WF30 (100), 357/20 (150), 357WH12 (350), 357P30 (200), 357P20 (300), 357WH25 (100), 357PH50 (50), 357/63 (50), 357WHP32 (100), 357PH45 (100), 357/35 (100), 357/40 (100)
      For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=357TB


       

      What is the material of construction of 357P20, pan head screws?

      357P20 is made of Zinc plated steel. 

      For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=357P20


       

      What is the part number for Moduline ducting 35x150?

      Part number is PL35150D available in White,Black,Natural Anodised & Oyster Grey and it is 2400mm long.

      Symmetra PX 250/500 Battery to Power Module Ratio

      Issue:
      Symmetra PX 250/500 Battery to Power Module Ratio

      Product line:
      Symmetra PX 250/500

      Environment:
      All Product models, all serial numbers

      Cause:
      Required battery to power module ratio for a Symmetra PX 250/500

      Resolution:

      Ratio between numbers of battery shelves and power modules (PM)

      Maximum recommended discharge level on the batteries used for Symmetra PX 250/500 is 3CA, where CA means the current (Amps) by which the battery is charged or discharged divided by its Amp-hour (Ah) rating.  The 250kW runtime ratio is 10 PMs to 16 battery shelves resulting in a ratio of 1.6 battery shelf per 1 PM. Need to always round up the number of shelves

      Results if ratio is not maintained

      In some situations, the Power Modules will attempt to draw power from the batteries and if the ratio is not observed, you will potentially clear fuses in the battery modules and (less likely, but it happened before) burn traces on the battery backplane boards due to the DC inrush current.

       

       

      Symmetra PX 250/500: What happens when EPO is activated?

      Issue:
      Symmetra PX 250/500; What does the EPO (Emergency Power Off) trip
       
      Product line:
      Symmetra PX 250/500
       
      Environment:
      All serial numbers
       
      Cause:
      What occurs when the EPO on a Symmetra PX 250/500 button is engaged?
       
      Resolution:
      When the EPO is activated, UPS output breaker Q2 and the battery breakers are tripped. The Power Modules (inverter) and if in Static Bypass operation will the UPS turn off

      Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

      Issue:
      Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

      Product line:
      Symmetra PX 250/500

      Environment:
      All Product models, all serial numbers

      Cause:
      Time not updating on UPS when changed on NMC

      Resolution:
      Making changes on the NMC web interface will also make changes on the ups, but the NMC must first be configured for Read/Write in the user configuration settings on the UPS.  Once this is configured making changes on the NMC will update the display on UPS.

      When changing NMC configuration to update Time using NTP, you need to pay attention to the update Interval.  It can be set from 1 to 8760 hours(1 year).  Make sure this is configured as needed.  If time is not immediately updating, click the UPDATE Now box and click apply.  You may need to refresh screen on UPS a couple times to see the change.


       

      How do I change User Password settings on Symmetra PX 250/500

      Issue:
      How to edit User Password settings via system display

      Product line:
      Symmetra PX 250-500

      Environment:
      All Product models, all serial numbers

      Cause:
      How do I change User Password settings on Symmetra PX 250-500

      Resolution:
      Begin at the home screen of the UPS



      Press the wrench key at the lower left of the screen
      Select Configuration, then select User configuration



      Enter the User password (apc by default)



      Select Password settings
      Change the password and select apply



      The following video demonstrates how the manage user password settings on the Symmetra PX 250/500 Data Center 3 Phase UPS.

      Video: How to Start your Symmetra PX 250/500 UPS

      Issue:
      How to Start your Symmetra PX 250/500 UPS
       
      Product line:
      Symmetra PX 250/500
       
      Environment:
      All Product models, all serial numbers

      Resolution:
      Begin by applying power to the UPS by Closing the Q1 Breaker (Located in System I/O Cabinet)



      Once the display is completely powered up and the Home screen is displayed, press the wrench icon in the lower left of the screen



      Then select the operation button
      Select System Startup



      Follow the on screen prompts for starting up the UPS.  As each option is performed it will highlight the next step.


      Some options are automated and will be done for you.

      The following video demonstrates this procedure:
       

      Network Management Card Compatibility with the Symmetra PX 250/500kVA UPS

      Issue:

      Network Management Card Compatibility with the Symmetra PX 250/500kVA UPS
       

      Product Line:
      • Facility & Data Center 3 Phase UPS
        • Symmetra PX 250/500
       
      • UPS Network Management Card 2
        • AP9635/35CH

      Environment:
      • All installation scenarios

      Cause:

      The AP9635/AP9635CH Network Management Card 2 (NMC2) is restricted for use with the Symmetra PX 250/500 UPS and other select UPS models. Additionally, before upgrading the firmware for the Management Card when installed in a, you must make sure that the firmware upgrade is compatible with the firmware level that is running on the UPS system (its MIM, PM, etc) . For example, as described in the chart below, a Management Card running v5.0.0 firmware cannot support a UPS with system firmware 4.1.x.x unless the Management Card is upgraded to the SYPX APP v5.0.1 firmware. To obtain the firmware upgrade files for the Management Card, you must contact Technical Support.


      Alternatively, the UPS System firmware can be updated to support a Management Card with newer firmware.

      Note: The UPS system firmware upgrade can only be performed by a Field Service Engineer.


      Resolution:

      Review the chart below to make sure the Management Card is running firmware that is compatible with the UPS. To view the UPS System firmware and NMC APP firmware versions from the UPS touchscreen display, press the Firmware Overview button in the System Information menu. The APP firmware version of the Management Card is also displayed in its Web interface, under the Administration->General->About menu.

       

      Compatible Symmetra PX 250/500 UPS and Network Management Card firmware releases
       

      UPS Release

      Network Management Card Firmware APP/Version

       3.x.2

      SYPX/5.0.0

      4.0.4

      SYPX/5.0.1 

      4.11.5 

      SYPX/5.0.2 or 5.1.0 

      4.21.6

      SYPX/5.1.2 or 5.1.3

      4.24.8

      SYPX/5.1.5

      4.25.9 SYPX/5.1.6
      4.27.10 SYPX/5.1.6 or 6.0.8
      4.29.11 SYPX/5.1.6 or 6.0.8
      4.36.12 SYPX/6.4.6
      4.37.12 SYPX/6.5.0

       

      Material Safety Data Sheets (MSDS) for Symmetra PX2 and PX 250-500kw UPS

      Issue:
      MSDS information for various battery manufacturers utilized in Symmetra PX2 and PX 250/500 UPS systems

      Product:
      Symmetra PX2, Symmetra 250-500

      Environment:
      All models/ All serial numbers


      Resolution:
      The rules regarding MSDSs changed in 2016 and it’s no longer sufficient just to post a link to the battery MSDS that we use.  When the rules changed, we began authoring Safety Data Sheets (new name for MSDSs) that would meet the new regulations.  These newly authored Safety Data Sheets (SDS) are located at the following web page.  

      https://www.apc.com/us/en/who-we-are/sustainability/battery-safety/battery-compliance.jsp

      You’ll note changes –
      Safety Data Sheets are region specific.  There is a NAM format and an EU format.  

      The intent is to direct all customers to this location when they have SDS or MSDS questions.

       

      Video: How do I Change Language & Regional settings on my Symmetra PX 250-500 UPS?

      Issue:
      How to Change Language, date format & temperature unit settings on the APC Symmetra™ PX 250/500 UPS.
       
      Product line:
      Symmetra PX 250-500
       
      Environment:
      All Product models, all serial numbers
       
      Cause:
      The display may be accidentally changed to an unwanted language.

      Resolution:

       

      Begin at the home screen of the UPS.  



      Press the wrench key at the lower left of the screen.
      Select Language settings



      The following screen will have the available list of languages. Select you desired language.



      Press the Finish to lock in change.

      How do I configure network settings on my Symmetra PX 250/500 UPS?

      Issue:
      Video: How to Configure network settings

      Product line:
      Symmetra PX 250-500

      Environment:
      All Product models, all serial numbers

      Cause:
      How do I Configure network settings  on my Symmetra PX 250-500 UPS

      Resolution:
      Begin at the home screen of the UPS
      Press the wrench key at the lower left of the screen
      Select Configuration then User configuration
      Enter the user password (apc by default)
      Select NMC settings
      Select Configure NMC Settings on the card you would like to configure.
      Ensure the ‘UPS configuration access’ is set to read or read/write for the card
      Make desired changes and Select Apply to save changes.

      See the following video tutorial: