screw 1/2x6 nc rsd csk hd

Catalogue Number: 353

General Accessories Screws, 12Mm X M3.5 X 0.8 Pitch, Plated

screw 1/2x6 nc rsd csk hd
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • 0.8 mm pitch
Product brand
Clipsal
Thread type
M3.5
Length
12 mm
Shape of screw head
  • slotted
  • raised countersunk
    • Sustainable offer status
      Green Premium product
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP060307EN
      Circularity Profile
      N/A

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • CAD Files and Packs

      • Technical Data Catalogues

      • Technical Leaflet

      • Installation Instruction

      • Operating Manuals

      • Specifications

      • Certificates (MSDS)

      • Corporate Marketing

      Frequently Asked Questions

      hide show

      What modules support the 140 XSM00200 16 point discrete simulator module connector?

      The simulator module connector is designed to operate with the 140DAI 540 00 and the 140 DAI 740 00 modules. These modules are 115 and 230 volts AC and field wire in the same manner. If the power source was reduced to 30volts or less AC the module 140DAI 353 00 could also be used for simulating discrete inputs.


      Changing counter value while Hot Standby switchover

      Goals and Symptoms

      This resolution describes a workaround for an effect by a Hot Standby switchover with RIO and a software counter.
      The RIO cable connection to the Primary CRP 931 fails.
      An input from a 140 DDI 353 00 module has value "1" at the same time.
      The Standby system switches to Primary (what is correct).
      But the input bit gets for a short time the value "0", because the CRA is not available while switchover.

      If the binary input is linked to a software counter the counter will change the value. Also affected are program parts, which use this binary input together with Edge detection.

      Facts and Changes

      Problem is known with the following components:
      Concept 2.6 SR2
      140CPU43412A, EXEC 1.25, Kernel 1.01
      140CHS11000, EXEC 1.04, Kernel 1.00
      140CRP93100, EXEC 1.15, Kernel 1.01
      140 DDI 353 00

      It should exist with all Hot Standby systems equiped with 140CRP93100, every discrete Input and a software counter or a Edge detection is linked to the Input module.

      Causes and Fixes

      Use the EN input of the software counter and link it to the healthy bit of the Input module. This avoids to increase the counter during RIO cable interrupt.


      Legacy KB System (APS) Data: RESL167770 V1.0, Originally authored by on , Last Edited by on
      Related ranges: Modicon Quantum