Quantcast

Standard Series, Flush Switch, 2 Gang, 250VAC, 10A, Architrave

White Electric | Standard Series, Flush Switch, 2 Gang, 250VAC, 10A, Architrave

Standard Series, Flush Switch, 2 Gang, 250VAC, 10A, Architrave

Item Number: 32A-WE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Standard Series

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

Device presentation

basic element with full cover plate and grid

Switch function

1-pole

Number of rocker

2

Number of poles

1

Device mounting

flush

Fixing mode

by screws

Local signalling

without

[Ue] rated operational voltage

250 V AC

Rated current

10 A

Marking

without marking

Actuator

rocker

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information

Yes

Environmental Disclosure

ENVPEP120506EN

Others

Package 1 Bare Product Quantity

1

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

2.9 cm

Package 1 Width

3.28 cm

Package 1 Length

8.62 cm

Package 1 Weight

0.044 kg

Unit Type of Package 2

BB1

Number of Units in Package 2

10

Package 2 Height

8.6 cm

Package 2 Width

7.1 cm

Package 2 Length

16.7 cm

Package 2 Weight

0.5 kg

Unit Type of Package 3

CAR

Number of Units in Package 3

250

Package 3 Height

23.8 cm

Package 3 Width

34.2 cm

Package 3 Length

39 cm

Package 3 Weight

12.75 kg
Show all specifications

Frequently Asked Questions

hide show

Can A9N61512 iC60H DC breaker be fed from top

No, the breaker is Polarized and can only be Fed from Bottom
image.pngimage.png
It will be the same for all iC0H DC single pole breakers:
C60H-DC Rating (In) Reference C curve 1P
1A A9N61501
2A A9N61502
4A A9N61504
6A A9N61506
10A A9N61508  
16A A9N61511
20A A9N61512
25A A9N61513
32A A9N61515
40A A9N61517
50A A9N61518
63A A9N61519

 

Why is 22kW EV charger only charging the vehicle at 7kW ?

The whole charging system is determined by the lowest value in the charging network. The network consists of the EVC, cable & vehicle.
If the EVC & cable are rated to 32A but the Car is only at 8A, the charging station will only deliver 8A.

Note : If a single phase vehicle is connected to a 22kW 3phase charger (with all three phases connected), it will only charge at 7kW. This is because all single phase vehicles will only charge with L1 & N.
EVlink commissioning guide : https://www.se.com/au/en/download/document/DOCA0060EN/

EV derated charging current
 

What is the B10 or B10d of TeSys Ultra Series motor starters?

Issue

What is the B10 or B10d of TeSys Ultra Series motor starters?

 

Product Line

TeSys Ultra Series

 

Resolution

The B10D value of TeSys Ultra is available on LUB** power base web datasheet:

LUB12 - Power base, TeSys Ultra, 3P, 12A/690V | Schneider Electric Global

LUB32 - Power base, TeSys Ultra, 3P, 32A/690V | Schneider Electric Global

What is the replacement for the High HP ATS01N softstarters?

Issue:
Part number for the replacement of the ATS01N High HP Soft Starters.

Product line:
ATS01, Altistart 01, High HP

Environment:
All models

Cause:
The launch of the ATS22 in 2011 caused the High HP units to become redundant.

Resolution:

The ATS01 High HP units were replaced with the ATS22 units.  These are functional replacements only.  The ATS01 had no overload protection, an internal power supply and simple dial adjustments.  The ATS22 will require external 120V or 230V power.  There are no dials to adjust, but the unit will need to be programmed.  See the ATS22 User Manual, document BBV51330 to review the wiring, dimensions and programming.  See the attached file.

ATS01N230LY - 32A rated.  Replaced by ATS22D32S6U
ATS01N244LY - 44A rated.  Replaced by ATS22D47S6U
ATS01N272LY - 72A rated.  Replaced by ATS22D75S6U
ATS01N285LY - 85A rated.  Replaced by ATS22D88S6U

 

What are the replacement part numbers for a Square D RCBOs example QOE120B03?

Please see attached document for the charcateristics of the new RCBos and below table shows the replacemnet part#s
RCBO   
MaterialAlternative MaterialDescriptionComment
QOE110BO3QO110B10RCBO30FQOE RCBO 1P+N 10A B 30mA 10kADirect Replacement
QOE116BO3QO116B10RCBO30FQOE RCBO 1P+N 16A B 30mA 10kADirect Replacement
QOE120BO3QO120B10RCBO30FQOE RCBO 1P+N 20A B 30mA 10kADirect Replacement
QOE132BO3QO132B10RCBO30FQOE RCBO 1P+N 32A B 30mA 10kADirect Replacement
QOE140BO3QO140B10RCBO30FQOE RCBO 1P+N 40A B 30mA 10kADirect Replacement
    


 

Are replacement contacts available for a CAD32 relay?

Issue:
Contacts need to be replaced in a CAD32** relay.

Product Line:
TeSys D IEC style relays

Environment:
CAD relays

Resolution:
The TeSys D IEC style relays do not offer replacement contacts.