switch time delay

Pneumatic Timer Controls, Time Delay Switch 250V 10A

Catalogue Number: 319
switch time delay
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • White Electric 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Series 319
Device presentation
basic element with full cover plate
Device mounting
flush
Material
plastic
Surface finish
glossy
Autonomy
0.0083...0.33 h
[Ue] rated operational voltage
250 V
Network frequency
50/60 Hz
Rated current
10 A
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Specifications

  • Case Studies

  • Certificates (MSDS)

Frequently Asked Questions

hide show

How long does part number 319 run for?

Part number 319 can be run up to 20mins.

What is part number for 319 reverse action?

The part number is  319RA.

Does part number 319 have N/C contact?

Yes it does.

What is the maximum time for a 319 timer?

319 Pneumatic timer can be set from 30 seconds to 20 minutes

please see link below for further information

https://www.clipsal.com/Trade/Products/ProductDetail?catno=319

Can the 319 switches be wired in two way?

Yes, the 319 pneumatic switches can be wired in parallel so that they can switch the same load.

For further information please visit https://www.clipsal.com/Trade/search-results?q=319

What is the part number of the mounting block suitable for 319 pneumatic timer?

238/25 mounting block is suitable for 319 pneumatic timer. 238/25 is a 1 Gang Surface Mounting Box, with 25mm end entries and dimensions of 115mm( length), 74(Width), 42(Depth).
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=238/25
User-added image

Is the time delay switch 319 compatible with two way switching?

No, the time delay switch 319 isn't compatible with two way switching.

For further information on this product please visit https://www.clipsal.com/Trade/search-results?q=319
 

What is the adjustable range of time for the CLipsal 319-WE?

It is adjustable from 30 seconds to 20 minutes.

What time adjustment is possible for a Clipsal 319 Timer?

Can be set between 2 and 10 minutes but will only be approximate.

IMPORTANT NOTES:
• This time delay switch operates on the air bleed principle and therefore it is not
possible to calibrate precisely. The timing will vary slightly with manufacturing
tolerances, air temperatures, relative humidity, and barometric pressure.

Which web browsers can support Conext Insight?

Conext Insight is compatible with IE 10+, Firefox 34+, Chrome 31+ .

What is the overvoltage fault threshold of Altivar 31.

The over voltage fault threshold of Altivar 31 is as attached.

How can you copy a old ATV31 program into a new ATV312 drive?

Issue:
Can you copy an ATV31 drives program into the new ATV312 drive?

Product Line:
Altivar ATV312, ATV31

Environment:
All

Cause:
Needs to use the old file from his ATV31 and put that program into his new ATV312 drive.

Resolution:
Yes, you can copy the old ATV31 file into the new ATV312 drive.
You will need to set up your new ATV312 to act like a old ATV31 by setting the  ArE parameter to 31E or 31A.
The differences are as follows.
31A has the knob on the face of the old ATV31 drive.
31E does not have the knob only the 4 buttons on the face of the drive.
To copy the old program from the ATV31 into the new ATV312 drive you will need the original ATV31 remote keypad, Powersuite software V2.6 or the Multiloader.

See the attached pdf document for notes.

If IEEE 519 is required, who enforces it? Citation concerns?

IEEE 519 is recommended practice standard and not really mandatory; Utility may ask this to be enforced;

Shipping weights of the NetBotz 310 Wall & Rack appliances

Issue:

Product Shipment Weights for the NetBotz 310 Units

Product Line:

NetBotz

Environment:

NetBotz 310

Cause:

Product information

Resolution:

The NetBotz 310 (Wall & Rack have the following shipping weights:

310 Wall: 6 lbs
310 Rack: 6 lbs 

Is there a parameter change history on an Altivar 31?

Issue:
Can we csee what parameters were changed and what were not on an Altivar 31?

Product Line:
Altivar 31, ATV31

Environment:
All

Cause:
NA

Resolution:
No, there is no change history available on the drive.  If you connect using Somove, you can see the Modified parameters.

What is a E19 code on a ATV212 drive? 

Issue: 
What is a E19 code on a ATV212 drive? 

Product Line:
ATV212  

Environment::
All 

Cause:
Will not clear with power cycle

Resolution:
Verify the cable and connectors to the HMI display. Replace the drive.

What is the Steel rating for 173SS?

The 173SS is rated at 316 Grade Steel

Do any Altivar Drives meet IEEE 519 requirements?

Issue:
Do any Altivar Drives meet IEEE 519 requirements?

Product Line:
Altivar 680, ATV680 Active Front End

Environment:
Known Harmonics Issues

Cause:
All

Resolution
ATV680 product line with active front end built in will meet requriements to fall within the  IEEE 519 System Specification.

Why do I get 'error Message 619 - This software is restricted to Compact, Momentum and Micro 984s, in the ProWORX NxT programming software'?

This error will occur when selecting a PLC type other than a Compact , Momentum or Micro PLC with an authorized Lite version of the ProWORX NxT software.
The Lite software will operate like a Full version when in DEMO mode, but once authorized as Lite version it will be limited to these three PLC types.

 

Are the 172SS saddles made from 316 Stainless Steel?

Yes, the 172SS saddles are made from 316 stainless steel.

Some of the key features are:
  • 0.9 mm gauge
  • 135 mm Maximum Slot Width
  • 5 mm diameter Hole
  • 39 mm Centres
  • 50 mm Length x 20 mm Width x 24 mm Height
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=172SS

 

What steel mounting plate can be used with the NSYS3X6625?

The NSYMM66 is the correct steel mounting plate for the NSYS3X6625.

See page F19 of the 2014 A4 Schneider Catalogue for a list of steel mounting plates and their enclosure counterparts.

What is the part number of the lock nut for 355 series screw?

359 is the locknut for 355 series screw.
  • Size: 6 mm x 6 mm
  • fits M3.5 x 0.8 mm pitch screws
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=359

Connect MV and LV on Trihal with IP 31 enclosure on site


Trihal IP 31- connect MV and LV

What is the length of the shaft in the GV3APN02 kit?

 The shaft included in the GV3APN02 kit is a GVAPA1. It has a length of 315 mm.
 

What grade is the stainless steel used in Clipsal BSL cover plates?

304 is the standard grade but we can get 316 as special.
There is no set pricing for 316 grade plates, we need to get a quote from AU
as it is a special and it will depend on the cost of the SS 316 
at the time of manufacturing.

How to set up plus + and minus - speeds on the Altivar 312 (and Altivar 31) drives

Issue:
How to set up plus and minus speeds on the Altivar 31/312 drives

Product Line:
ATV31 and ATV312

Environment:
All serial numbers for ATV31 and ATV312

Cause:
If using a momentary push button to increase/decrease speed

Resolution:
Set up the drive as follows:
Wire one side of the switch to the +24v terminal and the other side of the minus switch to a logic input (example LI5)
Wire one side of the switch to the +24v terminal and  the other side of the plus switch to a logic input (example LI6) 
Then program the drive as follows:
CTL menu
LAC set to 2 or 3
RFC Ref 2 switching set to Ch2 active
FR2 Ref 2 channel set to UPdt + and - speed control.
FUn menu
UPd + /- speeds
USP= + speed input for LI5 or you can choose your logic input assignment.
dSP= - speed input for LI6 or you can choose your logic input assignment.

Note: Conflicting functions need to be de-activated.  Set PS2 = PS4 = JOG = SA2 =  nO

I need a similar switch with key insert on the top of the xcsa512?

The xcsa512 has a black blanking plug on the top , which can be removed and a key can be used on top as well.
The actual head can be rotated as well in any direction for actation.
Please refer to safety catalogue 2008/2009 on page 3/9 and 3/20

Where is information on ATV31C drive ratings?


Issue:
Where is information on ATV31C drive ratings?

Product Line:
ATV31C

Environment:
All serial numbers for ATV31C

Cause:
N/A

Resolution:
The Installation manual, document 1624729, is attached.                
 

What is an "NOF" code in the ATV31 or ATV312 last fault?

Issue:
ATV31 showing nOF in the LFT parameter

Product Line:
ATV31/ATV312

Environment:
All
 
Cause:
Troubleshooting

Resolution:
Last fault code  NOF means "No Fault".
This indicates the drive does not have any recorded faults stored in memory.

What is the difference between an NSYS3X8625 and an NSYS3X8625H?

Issue:
NSY stainless steel enclosure form "H"

Product Line:
Wall-mounting enclosures

Environment:
Spacial S3DC - S3X

Resolution:
NSYS3X8625 is 304 stainless steel and NSYS3X8625H is 316 stainless steel.
Default stainless steel materil is 304. Form H makes it a 316 stainless steel.

What are the dimensions of the SBIP2P pop up power socket?

The front plate is 119 high x 124 wide.
The enclosure is 62mm deep. The minimum depth is 80mm deep from the surface when mounted in 18mm (minimum) panel thickness. The maximum panel thickness is 38mm.
Cutout is 105mm x 105mm


 

Is there information available regarding EIA-310-D, EIA/ECA-310-D and EIA/ECA-310-E?

Issue:
Clarification is needed on the various EIA 310 governing bodies.

Product Line:
NetShelter SX, NetShelter VX, NetShelter WX, NetShelter SV
 
Environment:
All versions and serial ranges.
 
Cause:
The EIA 310 organization has changed specification and owners in the past several years. What is the difference between these governing bodies?
 
Resolution:
See attached file
 

What is the part number for 56 series screws?

The part number for the 56Series cover screws is 56MS.They are 316 Grade Stainless Steel.
Please see link below for more information:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=56MS

Does the 110CPU31103 PLC have a time of day clock?

No. None of the Micro 311 series of PLC's offer a time of day clock. This includes the 110CPU31100, 110CPU31101, 110CPU31102, and 110CPU31103 All other controllers in the Modicon Micro line have a time of day clock.


Legacy KB System (APS) Data: RESL2276 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon Micro

Product ATV38 (Europe) ATV58 (US). Recently discovered that the Vulcain drives, size C19 displays an Ini message. The message cannot be cleared. Ath...

Goals and Symptoms

Product ATV38 (Europe) ATV58 (US). Recently discovered that the Vulcain drives, size C19 displays an Ini message. The message cannot be cleared. Athlab software was utilized to change the NCV code from a value of 25 to a value of 26 or 24 and the Ini message does not occur. It was further discovered if NCV =25 and EC22 was set to a value of of 21843 (US) the fault Ini occurs, If NCV=25 and EC22 is set to a value of 65535 the fault does not occur. Did the size drive C19 not get included in the lookup table for US conversion?

Causes and Fixes

this problem is in the course of investigation and it come from the keypad and we are waiting another version.


Legacy KB System (APS) Data: RESL156440 V3.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 38

Can you get a prestige 4 gang grid and cover ( Plate) less mechanisms?

Yes, you can get a prestige 4 gang grid and cover less mechanisms. The part number is P2034/2VH.

Some of the key features are:
  • Large format size
  • 8 x 31J screws
  • Without mechanism
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=P2034/2VH.
 

What size bolts are needed to floor mount the NetShelter 4-post rack?

Issue: 
A customer needs to know what size bolt will fit through the floor mounting holes in the rack. 

Product Line: 
NetShelter SX

Environment: 
AR203A, AR204A, all serial numbers. 

Cause: 
There is no documentation as to the size of the floor mount holes. 

Resolution: 

A 5/8" diameter bolt (19 mm) will fit through the floor mount holes of the NetShelter 4-post rack. 

I believe someone has hacked my Wiser Link system, what do I do?

If you have any doubt regarding the integrity of your system, contact Schneider Electric Customer Care Center on 1300 369 233

If I face an issue during installation and commissioning whom should I contact?

Contact :partner.supportau@schneider-electric.com
CUSTOMER SERVICE 1300 369 233 (7:30AM TO 7:00PM (MON TO FRI) AEST)
TECHNICAL SUPPORT 1300 202 525 (7:30 AM to 7:00 PM MON TO FRI AEST)

For further information please visit Trade - Clipsal by Schneider Electric

Is there a MSDS for 157FSM?

Yes, the material safety data sheet for the 157FSM Flexible Fire Resistant Sealant is available on request only.
To receive a copy, please call the Clipsal Technical Department on 1300 369 233.

What hardware and software does APC or Schneider Electric offer for NetShelter cabinet security and management?

Issue:
Does APC offer cabinet management and security products?

Product Line:
NetShelter
 
Environment:
All versions and serial ranges.
 
Cause:
Need for management and security
 
Resolution:

Our NetBotz security and environmental product line can be view at the following link: https://www.apc.com/products/category.cfm?id=17.
Our StruxureWare for Data Centers management software suite can be viewed at the following link: https://www.apc.com/products/category.cfm?id=7

What grade of stainless steel are the screws used in 56 series products?

The Anti-Corrosion Enclosure Screws are Stainless Steel Grade 316 for all 56 series products.

56MS Self Drilling Screw:
https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=56MS&c=6&ms=8&s=36&mg=12064&g=120641307&sg=120641407

For further information or support please call the Clipsal Technical Support on 1300 20 25 25


 

If the IEEE 519 PCC (point of common coupling) is on the HV side of the transformer, why are we required to find solutions for harmonics at a motor 4 levels downstream, if there are no real issue?

IEEE519 is a general quide and applies at the PCC (where end user network meets Utility); Why it is applied to loads or secondaries of transformers? - cannot answer this question but many consultants go this route; a misapplication of the standard

Where can I find the manual for Altivar 31 drives?

Issue:
Needs the manual for Altivar 31 drives

Product Line:
Altivar 31, ATV31

Environment:
All

Cause:
N/A

Resolution:
Please see attachment below for a copy of the manual.

End of Support Announcement for WallBotz 300, 300B and RackBotz 300 and 303

Issue:

End of Support Announcement for WallBotz 300, 300B and RackBotz 300 and 303

Product Line:

NetBotz

Environment:

NetBotz version 1 WallBotz 300, 300B and RackBotz 300 and 303

Cause:
End of Life, End of Support

Resolution:

End of Support Announcement for WallBotz 300, 300B and RackBotz 300 and 303

The following NetBotz products will reach the end of their support life on January 31, 2005:
WallBotz 300B
WallBotz 300
RackBotz 303
RackBotz 300

After that date, NetBotz may not take support calls or E-mails regarding these products. NetBotz also may not issue any further software releases or patches for these products after that date. 

Please note that the Rack and wall versions of the 310 and 400 units are also end of support

what are the dimensions of the ATV312HU40N4?

Height 184 mm
Width 142 mm
Depth 152 mm

Why is the drive not responding to the 4-20mA feedback signal when the Pump Switching Card is installed?

Most common issue is Parameter o19 must be set to the maximum pressure of the sensor in Bars.  Parameter o20 is set to the PI setpoint in Bars.

To get the pressure in Bars, divide the pressure in PSI by 14.504.


CTA-ID : 2015151

Safety shuddered outlets will not accept a plug

Issue:

Surge safety shuddered outlet is not accepting my device's electrical plug.

Product Line:

APC Performance Surge Arrest

Environment:

P11VXXX

Cause:

These outlets are designed to be child safe, they open only when equal pressure is applied to both shudders. If you lean more on one side then the shudder will not slide open.

Resolution:

Holding the molded portion of the equipment's plug try to adjust the alignment to equally distribute pressure across both prongs.

Plugs that have cord at a 90 degree angle to their prongs (right-angled plugs) can be more difficult to insert than others."
 

I believe someone has hacked my Wiser Link Energy Monitor system, what do I do?

If you have any doubt regarding the integrity of your system, contact Schneider Electric Customer Care Center.

Contact :partner.supportau@schneider-electric.com
CUSTOMER SERVICE 1300 369 233 (7:30AM TO 7:00PM (MON TO FRI) AEST)
TECHNICAL SUPPORT 1300 202 525 (7:30 AM to 7:00 PM MON TO FRI AEST)
 

How is it possible to determine if an Enercept Meter is the Basic or Enhanced model?

A System ID register located at addresses 30 (Integer) and 315 (Float) exists within the Enercept Meter. Reading that register will yield one of two values:
A value of 15022 will be returned from the Enhanced Enercept model.
A value of 15023 will be returned from the Basic Enercept model.