flange pvc mntg 167x115mm

Mounting Flange, 3 Gang

Catalogue Number: 31/3F
flange pvc mntg 167x115mm
Colour: White Electric
Colour: Per UOM Std.
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Standard Series
Product brand
Clipsal
Product or component type
flange mounting kit
Fixing center
92 mm
Depth
11 mm
Length
164 mm
Width
116 mm
Material
PVC (polyvinyl chloride)
Number of gangs
3 gangs
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Specifications

  • Case Studies

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Does the 3 gang mounting flange, 31/3F, still exist?

Yes the 31/3F-WE does still exist.

What is the adapter that goes from a 31/3 to a standard plate size?

The adapter is a 31/3F-WE.

Is there a 32/32 version of the 56E1 available?

No. There is only a 56E1/20/20 or 56E1/25/25 available.

Is there a replacement for 5 Series load breaker 5LBC4125CD?

The replacement for 5 Series load breaker 5LBC4125CD is a schnieder 31335.

For further information please visit the link below.

https://www.schneider-electric.com.au/5ser31335


https://www.elteh.eu/wp-content/uploads/schneider/H619250_web.jpg

What is the mounting block to suit part number 31BMF?

No mounting block available as part can be direct mounted.

78mm mounting centres

Fuse and circuit breaker rating for LXM32

Issue:
What is the fuse or circuit breaker rating for LXM32 drives?

Product Line:
LXM32

Resolution:
For 115VAC and 230VAC drives, the maximum fuse to be connected upstream is 25 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.
For 400VAC and 480VAC drives, the maximum fuse to be connected upstream is 30/32 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.

How to set up plus + and minus - speeds on the Altivar 312 (and Altivar 31) drives

Issue:
How to set up plus and minus speeds on the Altivar 31/312 drives

Product Line:
ATV31 and ATV312

Environment:
All serial numbers for ATV31 and ATV312

Cause:
If using a momentary push button to increase/decrease speed

Resolution:
Set up the drive as follows:
Wire one side of the switch to the +24v terminal and the other side of the minus switch to a logic input (example LI5)
Wire one side of the switch to the +24v terminal and  the other side of the plus switch to a logic input (example LI6) 
Then program the drive as follows:
CTL menu
LAC set to 2 or 3
RFC Ref 2 switching set to Ch2 active
FR2 Ref 2 channel set to UPdt + and - speed control.
FUn menu
UPd + /- speeds
USP= + speed input for LI5 or you can choose your logic input assignment.
dSP= - speed input for LI6 or you can choose your logic input assignment.

Note: Conflicting functions need to be de-activated.  Set PS2 = PS4 = JOG = SA2 =  nO

What Product Line Replaces the Altivar 312 and Altivar 32 drives?

Issue:
What Product Line Replaces the Altivar 312 and Altivar 32 drives?

Product Line:
Altivar 312, Altivar 32 and Altivar 320 Machine Drive (ATV312, ATV32, ATV320)

Environment:
All serial numbers for Altivar 312 and Altivar 320 Machine Drive

Cause:
N/A

Resolution:
The Altivar 312 and 32 drives are both smaller Constant Torque machine drives with mid-functionality features. These drives are currently still available but will be phased out soon. The most current replacement would be the Altivar 320 Product line.  See attachments.

Altivar 312/32 to Altivar 320 Product Line 

ATV320...C (IP20) replaces the ATV312 open style
ATV320...B (IP20) replaces the ATV32 open style

Altivar 312/32 vs Altivar 320 Product Line 
The ATV320 has similar functionalities to the ATV312 and ATV32 but a few minor differences to taken in account when replacing. 

Similarities and Differences

Size:
The ATV320...B (Book Shelve) is very similar in build and size to the ATV32 meanwhile the compact drives, ATV320...C, are built similar in size to the ATV312

List of Other Differences
  • Programming layout is similar to that of the Altivar 32
  • All Altivar 320 drives have the Function Block capability
    • If drive shows "RDY" and will not start-up even if DI1 is on, then there maybe a function block turned on
  • There are no LOCAL CONTROLS on the Altivar 320 drive.
    • No red STOP or green RUN buttons
  • New Safety Functions
  • Altivar 320 support numerous Communication Protocols such as Ethernet IP, DeviceNet, Modbus...
    • ATV320...C (Compact ONLY) requires the Communication Module (VW3A3600) when using a communication module


 

There is an application with Altivar 38 with pump switching card where the auxiliary pump is driven by an Altistart 48.There is also Modbus connection...

Goals and Symptoms

There is an application with Altivar 38 with pump switching card where the auxiliary pump is driven by an Altistart 48.There is also Modbus connection where the master is a Twido PLC and the slaves are the ATV38 and the ATS 48. The problem is that en error ERR 7 (erreur LS) is appeared at the ATV38 display.What kind of error is that and what can we do about it?

Facts and Changes

ATV38 with Modbus connection

Causes and Fixes

Product trips transiently to "Err3" or "Err7" fault. Both faults type are generated by the display module.
This one communicates with the microprocessor of control card .
When incorrect messages occur during the communication and after some repetition of exchanges , the display module shows to "ErrX".
This is a very difficult fault to reproduce because depending of environment ( lenght of wire between display module and control board , motor running, disrupted site ) and the combination between display module and control board.

Origin of problem :

Insufficient immunity of communication facing the various disturbances.
The communication frames managing is made by integrated components called "drivers". One is located on control board, the same is inside display module. This fault is the result of wrong interpretation of display module of logic level between two communication frames.
This technical conceived problem is appeared from August 2000.

Corrective action:

This failure has been resolved by a modification of two values of resistors inside the display module.
The revision levels become:
· A20, B20 for the ATV58 display modules.
· A02 for the ATV58Fdisplay modules.

This evolution is applied from the week 47/2000 on all manufactured PRODUCTS and all VW3A58101 spare parts.


Information for internal use:

We have noticed that anyway neither control board nor display module have never been directly to the fault origin . Fault "Err X" is always due to the association of two items.

On no account this failure cannot to disrupted the motor running but she can to disturb only the programming of product.

If during the programming, a customer encounters to " Err3 " or " Err7 " with a product manufactured from the week 31/00 to 46/00 , it is advised to exchange only the VW3A58101 display module.

This problem can also appear if the baudrate of internal communication was modified ( subD 9 pins ) and there is a difference between the keypad and internal modbus.

A solution is to reset the inverter with the 50/60 Hz switch to return the baudrate in factory setting, don't forget to accord the Twido PLC.


Legacy KB System (APS) Data: RESL156317 V3.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 38