MASTER YOUR CASTLE with your new build or reno project
Enter competition
plate only 1g arch switch

31

Flush Plates - Standard Range, Architrave Size, Switch Plate 1 Gang (75 x 32mm)

plate only 1g arch switch
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • Cream 1 PCE
  • White Electric 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
  • Architrave flush switch
  • Flush mount
  • For termination of unused or looped cables, mounting of custom equipment or simply blanking off unused openings in wall/wall cladding
Range of product
Standard Series
Product brand
Clipsal
Number of gangs
1 gang
Product destination
switch
Fixing mode
by screws
Material
plastic
Marking
without marking
Mounting position
horizontal and vertical
Fixing center
55 mm
Width
32 mm
Height
72 mm
Depth
11 mm

Frequently Asked Questions

hide show

What are the dimensions of the detachable Keypad (VW3A31101)of the Altivar 31 Drive.

Refer the attachment for the dimensions of the detachable Keypad (VW3A31101) of the Altivar 31 Drive.

 

What is the Earth Leakage current value for an Altivar 31 Drive?

Refer attachment for the Earth Leakage current values for Altivar 31 Drive.

Note:
The earth leakage current strongly depends on how well the input voltages are balanced and the quality of the wiring.

What is the overvoltage fault threshold of Altivar 31.

The over voltage fault threshold of Altivar 31 is as attached.

What do I do if I am getting flickering or load distortion

Confirm you are using compatible load type and then there is an option to fit a 31 Cap.  Please refer to Installation Instructions.

What is the cable pinout to connect an M340 to an Altivar 31 drive via CANopen?

The CANopen cable pinout to connect a M340 to a Altivar 31 drive is:


Legacy KB System (APS) Data: RESL190316 V1.0, Originally authored by MiMe on 12/11/2007, Last Edited by MiMe on 12/11/2007
Related ranges: Modicon M340

Where can I find the manual for Altivar 31 drives?

Issue:
Needs the manual for Altivar 31 drives

Product Line:
Altivar 31, ATV31

Environment:
All

Cause:
N/A

Resolution:
Please see attachment below for a copy of the manual.

What is the Bus Cycle Time for the Twido AS-Interface module?

This is the cycle time between slave(s) and the master module. The AS-Interface system always transmits information, which is the same length to each slave on the
bus. The AS-Interface cycle time depends on the number of active slaves connected to the bus. The scan time t represents the exchange time between a
master and n active slaves (a maximum of 31 on /A or /B).So, for:
  • up to 19 active slaves, t = 3ms
  • 20 to 31 active slaves, t = (1+n) * 0.156ms

When two slaves A and B have the same address, each slave in the pair is scanned every two cycles. This means that for 31 extended address setting slaves
configured in /A, + 31 extended address setting slaves configured in /B. the scan time will be 10 ms.
Maximum cycle time:
  • maximum 5 ms for 31 standard or extended address setting slaves,
  • maximum 10 ms for 62 extended address setting slaves.

ATV 31 modbus comms with LUFP1.I need application examples and short cuts and configuration for the drive.

Goals and Symptoms

ATV 31 modbus comms with LUFP1.I need application examples & short cuts & configuration for the drive.

Facts and Changes

ATV 31 with LUFP1 to premium plc

Causes and Fixes

There is nothing for the drive, only the baudrate and address, example in attachments.

Attachments

(Removed File URL: 162238_542E/Appli_ATV.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/870f29ca3457766285256ea90047269b/fl_block_5/0.612?OpenElement&FieldElemFormat=gif)(Removed File URL: 162238_542E/App_LUFP1_ATV.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/870f29ca3457766285256ea90047269b/fl_block_5/0.113C?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL162238 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 31

What is the pinout to connect TWIDO CANopen Master module (TWDNC01M) to an Altivar drive 31 ?

The pinout to connect the DB9 connector on the TWIDO CANopen module (TWDNC01M) to a ATV 31 drive is given below:
TWDNC01M (DB9) ------------------------------------------>>> ATV 31 (RJ 45 )

CAN_H ( 7 ) ------------------------------------------>>> CAN_H ( 1 )

CAN_L ( 2 ) ------------------------------------------>>> CAN_L ( 2 )

GND ( 3 ) ------------------------------------------>>> GND ( 3 )


Legacy KB System (APS) Data: RESL182258 V1.0, Originally authored by TVe on 02/21/2007, Last Edited by TVe on 02/21/2007
Related ranges: Twido

Why is my Conext CL showing an alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC current sensor doesn’t measure the grid current accurately
Grid connection
Detection circuit malfunction

Resolution: 
Check AC connection on inverter

What are the watts loss for the ATV31H075N4?

Issue:   What are the watts loss for the ATV31H075N4?
 
Product Line:   ATV31
 
Environment:  ATV31H075N4
 
Cause:   N/A
 
Resolution:   Total dissipated power at rated load is 41 watts.

 

What is the part number for the GSM/GPRS TSXETW330G1 module antenna cable extension?

The part number for the 5m antenna cable extension is TSXETW3GANT1

Why is Slimline being withdrawn?

With the introduction of Iconic, the Slimline range will be withdrawn – this means the Slimline range will not be available commercially after 31 December 2016. We will continue to honour warranty periods and outstanding contracts.

Where can I find the ATV31 programming manual?

Issue:
Where can I find the ATV31 programming manual?

Product Line:
Altivar 31

Environment:
All

Cause:
N/A

Resolution:
See attached.

Connect MV and LV on Trihal with IP 31 enclosure on site


Trihal IP 31- connect MV and LV

How do you unlock the access of all Drive Parameters in an Altivar 31 Drive?

In order to gain access to all the Altivar 31 Drive parameters one of the two conditions will apply:

 
1. Parameter Access Via Standard Keypad (Integrated LED Display):
 

Enter the Customer password in parameter Terminal Locking Code (Cod) in Monitoring Menu (Sup).

 
2. Parameter Access Via Remote Keypad:
 
a. Enter the Customer password in parameter Terminal Locking Code (Cod) in Monitoring Menu (Sup).
 
AND
 
b. Set the Dip Switch called ‘Access Locking Switch’ at the rear portion of the Remote Keypad to ‘Unlock’ position. Refer to the attachment.
 
Note:
Customer password protection has priority over the switch setting.
 
 
Note:
In case the Customer set password is forgotten use the Master password ‘6969’ which resets the customer password and opens access to all parameters.

What can cause the InF fault in the Altivar 31 and Altivar 312 drives?

Issue:
What can cause the InF fault in the Altivar 31 and ATV312 drives?

Product Line:
Altivar 31 and ATV312 drives

Environment:
All 

Cause:
Internal fault 

Resolution:
InF indicates an internal fault.  
It can occur if there are loose connections inside the drive or if the drive is subjected to electromagnetic interference.  Check the line voltage to the drive.
Also, check the voltages on the control terminals, +10 to COM and 24V to COM.  It has been observed that improper wiring of the inputs or external potentiometer can overload the internal power supplies of the drive. This may result in InF fault.
Incorrect connections on the RJ45 ModBus/CANopen port can also cause this.  Verify wiring, particularly to pin 7 (10VDC supply for external keypad).



 

Is it possible to do remote reset function with ASI module ASILUF05 of TeSys U.

ASILUFC5 unit works on the ASI bus which is a basic bus and handles only 31 or 62 slaves. This unit cannot support the remote reset function alone.

The ASILUFC5 unit supports the remote reset function when used with other communication protocols like Modbus, Profibus, DeviceNet etc. and LULC communication module in TeSys U unit.

What is the mounting hole diameter of a 30mm pushbutton?

Issue:
What size is the mounting hole for a 9001KX  30mm pushbutton?

Product Line:
Pushbuttons and Operator Interface

Environment:
9001K, 9001SK and 900KX 

Cause:
Product Features

Resolution:
31 mm or 1.22 inches.

What is the character limit for a device name on the EGX300?

Product Line  
EGX300

Environment  
Editing Web page

Resolution
The character limit for a device name on the EGX300 is 31 characters. The device name cannot contain special characters other than spaces and underscores.

 

With a UA cintroller is it possible to start the Generator of the ATS system only without Switching to the Reserve Supply?

The contacts 29 - 31 (Startup Order) of the UA controller should be externally connected with a switch to give an external signal to start the Generator. There is no internal connection or program to acheive this in UA controller. 


 

What is the wire size and torque specs for C60 Multi 9 circuit breakers with lugs?

Issue:
Wire size for Multi 9

Product Line:
Circuit breakers

Environment:
Multi 9 MCB

Cause:
Torque and wire size is marked on the breaker, but users often want this information before they receive the product.

Resolution:
Wire size and torque are as noted below.  Always confirm with markings on the circuit breaker. Only one wire can be installed per terminal. There are no replacement lug kits available for the Multi 9 breakers. The wire strip length is 14mm.

UL 1077 Supplementary Protectors
0.5 to 25 A: #18 to #4 AWG (1 to 25 mm^2) cables; torque 22 lb-in (2.49 Nm)
30 to 63 A: #18 to #2 AWG (1 to 35 mm^2) cables; torque 31 lb-in (3.50 Nm)

UL 489 240 Vac
0.5–25 A: 14–4 AWG (2–25 mm2) Cables:  Torque to 22 lb-in. (2.48 N•m)
30–35 A: 14–2 AWG (1–35 mm2) Cables:  Torque to 31 lb-in. (3.52 N•m)

UL 489 Listed 480 Vac
18–16 AWG (1–1.5 mm2), Cu Only Stranded Wire:  Torque to 7 lb-in (0.68 N•m)
14–10 AWG (2–5 mm2), Cu Only Solid or Stranded Wire:  Torque to 14 lb-in (1.6 N•m)

IEC Rated C60 C60N/H/L Except C60L-MA
0.5–25 A, 18–4 AWG (1–25 mm2) Cu Only Cables:  Torque to 22 lb-in (2.5 N•m)
30–63 A, 18–2 AWG (1–35 mm2) Cu Only Cables:  Torque to 31 lb-in (3.5 N•m)

What is the ATV28 replacement kit part number for the size 9 ATV31HD11M3X, ATV31HD15M3X, ATV31HD11N4, ATV31HD15N4, ATV31HD11S6X, ATV31D15S6X units?

Issue:   What is the ATV28 replacement kit part number for the size 9 ATV31HD11M3X, ATV31HD15M3X, ATV31HD11N4, ATV31HD15N4, ATV31HD11S6X, ATV31D15S6X units?
 
Product Line:   ATV31
 
Environment:  ATV31HD11M3X, ATV31HD15M3X, ATV31HD11N4, ATV31HD15N4, ATV31HD11S6X, ATV31D15S6X
 
Cause:   ATV28 to 31 conversion kit
 
Resolution:   
VW3A31825.


 

Can Class T fuses be used with Altivar 31 drives? The manual only references Class CC or J.

The ATV31 units were tested with the Class J fuses however the 600V version of the Class T fuses have equivalent ratings. So can use the 600V Class T fuses but not the 300V Class T fuses.

Can the ATV31 drive be repaired?

Issue:   
Can the ATV31 drive be repaired?
 
Product Line:   
ATV31
 
Environment:
All serial numbers
 
Cause:  
Customer wanted to send ATV31 for repaired. 
 
Resolution:   
There are no replacement parts available for the ATV31 drives. 



 

What is the bandwidth of the skip frequency, JPF on the ATV12 drive?

Issue:
Bandwidth of the skip frequency, JPF on the ATV12 drive.

Product Line:
Altivar ATV12

Environment:
All serial numbers

Cause:
N/A

Resolution:
The bandwidth is +/- 1 Hz around the JPF setting.  Example, JPF = 30, the drive will not run at speeds between 29 Hz and 31 Hz..


CTA-ID : 2062188

Video: How do you wire and program an ATV31 or ATV312 to follow an external 0-10vdc speed pot on AI1 and use the logic inputs for starting and stopping?

Issue:
Wiring and configuring 2-wire terminal start/stop run control on Logic Input 1 (LI1 + 24vdc) and 0-10vdc speed control via Analog Input 1 (AI1) on Altivar 31 & 312 (ATV31/ATV312) Variable Frequency Drives (VFD). A potentiometer is commonly used as the 0-10vdc analog speed reference.

Product Line:
Altivar 31 and 312

Environment:
All models in range.

Cause:
Pot for speed control or 0-10v logic input for speed control.

Resolution:
Wiring:
Wire your external pot to AI1 com and +10vdc. (wiper wire on AI1)
Wire your Start forward command between LI1 and +24vdc.

Programming:
Step 1: Go into the CTL menu enter
Step 2: Set Fr1 to AI1

 

Where do I check for a last fault code on an ATV31 and ATV312 drives?

Issue: 
No fault code displayed, after drive reset.

Product Line:
ATV31 and ATV312

Environment:
 All

Cause:  
Would like to know the last drive fault .

Resolution: 
Go to SUP (monitoring menu) and select parameter "LFT" to display the last drive fault.

What is the maximum bus length for the Quantum 140EIA92100 AS-i module?

 

        • Max length of the bus": 100m.
          Possibility to extend the bus through repeaters (+supplies): 2 repeaters max between the master and a slave (300m).
          Scan Time: 5ms with 31 stations / 10ms with 62 stations with extended profile.
           

Setting Address of SY/NET Devices such as PowerLogic Network Interface Modules (PNIM) etc.

The number of a Sy/Net device address on a SY/NET network cannot exceed the network size specified on the Sylink card. i.e. if the network size is set to 31 a PNIM cannot be addressed with the number 40.
© Schneider Electric 2005
Original article#3742
Public


Legacy KB System (APS) Data: RESL183936 V1.0, Originally authored by DaMi on 05/03/2007, Last Edited by DaMi on 05/03/2007
Related ranges: third party devices (modems, converters...)

What replaces the ATV31 drives series?

Issue:
What replaces the ATV31 drives series?

Product Line:
All  ATV31 Except ATV31W......

Environment:
All

Cause:
Obsolete

Resolution:
The ATV31 series was replaced by the  ATV312 series, which has been replaced by the ATV320 series. The ATV320 is now available.

ETSNZ How many charging records can the EVLink webserver hold?

You are able to view the last 30CDR (Charge Detail Record) regardless of the date. It will also store the last 31 days of load. It will write of the last record when it is full.
The export button in the Charge Data Record tab is used to export all the charging sessions (up to 3000) in the station via a .csv file.

 

Is there a parameter change history on an Altivar 31?

Issue:
Can we csee what parameters were changed and what were not on an Altivar 31?

Product Line:
Altivar 31, ATV31

Environment:
All

Cause:
NA

Resolution:
No, there is no change history available on the drive.  If you connect using Somove, you can see the Modified parameters.

What causes an Err 7 fault code in an ATV31 drive?

Issue:
What causes an Err 7 fault code in an ATV31 drive?

Product Line:
ATV31  , All models , All  serial numbers

Environment:
All

Resolution:
Possible cause of Err7 on the ATV31 remote display :
1).  Baud rate not equal to 19.2 kb/sec   - Set to 19.2  in the COn Menu parameter tbr
2).  Format is not equal to 8bits even parity 1 stop bit (8E1) - Set to 8E1  in the COn Menu parameter tFO
3).  Defective cabling or connection between the VFD and keypad - change the cabling
4).  Defective keypad - replace the keypad
5).  Shorted pins on the comport of the VFD - If no physical short on the pins in the comport then the issue is internal to VFD, replace VFD

How do I add a password on an ATV312?

Issue:
How do I add a password on an ATV312?

Product Line:
ATV312, Altivar 312

Environment:
All

Cause:
Prevent program changes

Resolution:
You can add a password by setting parameter COd (PIN code 1).  This parameter is under the SUP menu (Monitoring).  Change from Off to to On and then change the display to a 4 digit code and push the Enter button.

To unlock the drive, go under the COd parameter again and enter the pin code saved. 

To reactivate the same pin code, change COd back to On and push the enter button. 

To change the pin code, once unlocked, change the pin code to another 4 digit code and pus enter to save. 

To disable the pin code, change the display to Off and then push Enter to save.

Can an ATV31 file be converted to an ATV312 file using SoMove software?

Issue:
Can an ATV31 file be converted to an ATV312 file using SoMove software?

Product line:
ATV31, ATV312

Environment:
All models, all serial numbers

Cause:
Need to connect to Blue Hose

Resolution:
It is not possible to transfer a configuration from ATV31 to ATV312 with SoMove software.  You will have to use the multiloader or the old ATV31 keypad to copy an 31 file into the ATV312 drive if you configure the ArE parameter to 31A or 31 E.
The better solution is to generate the configuration file in Off-line Project for ATV312 then upload to Drives.

What is the part number for the remote keypad for the ATV31?

Issue:   What is the part number for the remote keypad for the ATV31?
 
Product Line:   ATV31
 
Environment:  All
 
Cause:   Remote keypad kit
 
Resolution:   The Altivar 31 remote mount keypad kit is VW3A31101.
The kit includes a keypad, mounting hardware and a 3 meter cable.


 

How is the ATV31 setup for AI3 input to be the primary speed reference?

Issue:   How is the ATV31 setup for AI3 input to be the primary speed reference?
 
Product Line:   ATV31
 
Environment:  All
 
Cause:   Speed reference
 
Resolution:   In the CtL menu, set the Fr1 parameter to AI3.

 

Can the ATV31...A model be setup to use the integral speed pot dial for reference adjustment, but use the LI logic input for a run forward command?

Issue:   Can the ATV31...A model be setup to use the integral speed pot dial for reference adjustment, but use the LI logic input for a run forward command?
 
Product Line:   ATV31
 
Environment:  ATV31**A models
 
Cause:   N/A
 
Resolution:   Yes.  In the IO menu, set parameter tCC to 2C.  This assigns LI1 as run forward command.  In the CtL menu, set parameter Fr1 to AIP.

 

What is the part # for a clear plastic bezel for a ZB4BW31, ZB4BW32, ZB4BW33 ZB4BW34, ZB4BW35, ZB4BW36, ZB4BW37 ?

Issue:
What is the part # for a clear plastic bezel for a ZB4 illuminated push buttons (incandescent type)?

Product Line:
Product selection

Environment:
All Products

Cause:
Product selection

Resolution:
Use a W415595280111
 

Does the VW3A8104 Powersuite software kit include the cables?

Issue:
Does the VW3A8104 Powersuite software kit include the cables?

Product Line:
Powersuite

Environment:
All

Cause:
N/A

Resolution:
No. This is the software only. The cable kit is VW3A8106.

What the difference is between these 2 contact blocks - LADN22 and LADN22G?

Issue:
Identifying differences in two part numbers

Product Line:
IEC contactors and starters

Environment:
Products sold and used in the United States

Cause:
Determining which part number to order

Resolution:
They both have 2 normally open (N.O.) and 2 normally closed (N.C.) contacts.
The sequence and numbering are different
LADN22 from left to right read : N.O. 53 and 54; N.C. 61 and 62; N.C. 71 and 72; N.O. 83 AND 84.

LADN22G from left to right read : N.C. 31 and 32; N.C. 41 and 42; N.O. 53 and 54; N.O. 63 and 64.


 

What is the A Suffix mean at the end of an ATV31 drive part number?

Issue:
What is the A Suffix mean at the end of an ATV31 drive part number?
Product Line:
Altivar 31 ATV31

Environment:
All

Cause:
Drive part number omits the A suffix.

Resolution:
The ATV***31A has the start/stop button, run button, and a potentiometer on the front of the drive. The ATV***31 without the "A" at the end of the part number does not have the start/stop, run, and potentiometer on the front of the drive.

Is there another full version of SOMOVE software, besides SOMOVE Lite?

Issue:
Is there another full version of SOMOVE software, besides SOMOVE Lite?

Product Line:
Altivar 71 Altivar 61 Altivar 12 Altivar 32 Altivar 312 LXM 32 Altivar 31 Altistart 22 TeSysU TeSu

Environment:
All models, All series

Cause:
Potential confusion of product naming to indicate SOMOVE Lite may not be a full featured version.

Resolution:
Yes, SoMove 2.0 and higher is a full version. You must install associated DTM files. 
There is also SoMove Mobile.
 

No action on logical input, logical input out of order.

Goals and Symptoms

No action on logical input, logical input out of order.

Facts and Changes

ATV31
Logical Input
LI1, LI2, LI3, LI4

Causes and Fixes

This phenom can occur when the 24V used for the logical input is connected in some coil of relay or of electromagnet and so on.
It's due to the overvoltage generated by Ldi/dt when you cut a continue voltage on a coil (L).
It's possible to reduce the level of this overvoltage, use LA4KC1B or LA4DE2U.

Supplemental Profibus Island Module Health Bit Information for ACS Online Help

Goals and Symptoms

Information in this resolution applies to Structure of the STB NDP 2212 Diagnostic Message, Bytes 16 - 31 located in the Advantys Configuration Software Online Help > Hardware Help > Advantys STB Profibus DP NIM > Fieldbus Communication Support > Diagnostics Service. The purpose is to explain module conditions which are represented by the 0s and 1s in those bytes.

Causes and Fixes

This information may also be found on Pl@net in the Advantys STB Profibus DP Network Interface Applications Guide, p/n 890USE17300.


Legacy KB System (APS) Data: RESL179562 V1.0, Originally authored by WeDa on 09/01/2006, Last Edited by WeDa on 09/01/2006
Related ranges: Advantys STB

How many devices are supported on the RS-485 port (COM3) of the ECC21 card in a CM4000 & CM4000T?

Issue
How many downstream devices can be connected to COM3?

Product Line
CM4 ECC21 Card

Environment
COM3 = RS-485 Serial Port

Resolution
This port supports up to 31 devices (without a repeater), since the device that holds the ECC card counts as a device. The limit is up to 63 devices with a repeater.

What would be the replacement to the older ATV31 S-Flex drive?

Issue:
What would be the replacement to the older ATV31 S-Flex drive?

Product Line:
ATV31 S-Flex

Environment: 

All

Answer To Customer: 
If the application is low torque such as fan or pump then an ATV212 S-Flex would be a good replacement.
If the application is moderate or heavy torque, then please contact your local Product Application Engineer (PAE) or local distributor for enclosed drive selection.

Where can I find dimensions and weights for the Altivar ATV312 drives?

Issue:
Where can I find dimensions and weights for the Altivar ATV312 drives?

Product Line:
Altivar ATV312

Environment:
All

Cause:
Needs a cut sheet dimensions for the ATV312 drives.

Resolution:
You can find the dimensions and weights in the ATV312 installation manual.








 

What are the Publish and Receive Gooses Capacity for Sepam and CET 850 in IEC61850 Protocol?

Issue   
Customer would like to know the capacity for GOOSE messaging. 

Product Line    
IEC 61850
Sepam 80 Series

Environment    
communications

Resolution
For GOOSE publishing there isn't a maximum limit. Only the limit to 100% has to be respected.

For GOOSE receive messages there are a maximum of 40 GOOSE subscriptions for each IED/ ICD file.
For each Sepam there are 31 GOOSE receive messages when using the SFT 2841 to program.