Grid Switch Vert/Horiz 6G

Clipsal Iconic Switch Grid, 6 Gang, Horizontal/Vertical Mount

Catalogue Number: 3046G
Grid Switch Vert/Horiz 6G
Retail
$14.96*
RRP (Inc. GST)

Specifications

hide show
Range
Clipsal Iconic
Product or component type
fixing frame
Aesthetic name
Iconic
Number of gangs
6 gangs
Fixing mode
by screws
Range compatibility
cover plate
Provided equipment
screws
Depth
12 mm
Width
71 mm
Height
115 mm
Net weight
0.044 kg
Type of packing
polybag
EU RoHS Directive
Under investigation
Environmental Disclosure
ENVPEP120506EN

Documents & downloads

hide show
Filter items
  • All

  • Product Environmental

Frequently Asked Questions

hide show

What is the part number for a 6 gang switch for the Iconic range?

The part number for a 6 gang switch for the Iconic range is - 3046G & 3046C

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3046G
https://www.clipsal.com/Trade/search-results?q=3046C
User-added image

User-added image

 

Is Iconic intermediate mechanism available assembled on a switch plate?

Unfortunately, the Iconic intermediate mechanism is not available assembled on a plate. It can put together using below part numbers;
40MIL  - Clipsal Iconic Intermediate Switch Mechanism, 250V, 10A, LED.
+
3041G - Clipsal Iconic - Switch-Grid, Vertical/Horizontal Mount, 1 Gang
+
3041C - Clipsal Iconic - Skin Switch Plate Cover, Vertical/Horizontal Mount, 1 Gang
For further information, please visit the below links:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=40MIL
https://www.clipsal.com/Trade/Products/ProductDetail?catno=3041G
https://www.clipsal.com/Trade/search-results?q=3041C


What are the part numbers to make up a 4 gang switch with LED for the Iconic range?

The part numbers to make up a 4 gang switch with LED for the Iconic range are - 3044G , 40ML & 3044C

For further information visit links below:-
https://www.clipsal.com/Trade/search-results?q=3044G
https://www.clipsal.com/Trade/search-results?q=40ML
https://www.clipsal.com/Trade/search-results?q=3044C
User-added image

What is the part number for Iconic foxtel TV outlet?

The part numbers for Iconic Foxtel TV outlet are 3041G + 3041C-** + 40PFM-TN

3041G Clipsal Iconic - Switch-Grid, Vertical/Horizontal Mount, 1 Gang

3041C-WY Clipsal Iconic - Skin Switch Plate Cover, Vertical/Horizontal Mount, 1 Gang

Clipsal Iconic - TV Antenna Socket, 75 Ohm, F-Type

For further information see:https://www.clipsal.com/Trade/Products/ProductDetail?catno=3041G:https://www.clipsal.com/Trade/Products/ProductDetail?catno=3041C-WYhttps://www.clipsal.com/Trade/search-results?q=40PFM
 

What part numbers are needed to put together an Iconic 1 gang electronic Pushbutton switch plate (Vivid white)?

Below are the part numbers needed to put together an Iconic 1 gang electronic Pushbutton switch plate :

3041G - Clipsal Iconic - Switch Grid, Vertical/Horizontal Mount, 1 Gang
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=3041G

+

3041C-VW -Clipsal Iconic - Skin Switch Plate Cover, Vertical/Horizontal Mount, 1 Gang, Vivid White
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=3041C-VW​

+
41E350PBES2SM-VW -Clipsal Iconic - Electronic Switch Mechanism, Push Button with ControlLink (without bluetooth) 2-wire, 350W
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=41E350PBES2SM

Are EasyPact CVS circuit breakers for sale in the USA or Canada?

Product Line:
EasyPact CVS circuit breakers

Cause:
This breaker is popular overseas and there is interest in the US

Resolution:
There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.

Do we still have the 30/60 PBI?

Yes, the part number is PBI/KIT.
 
 
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=PBI/KIT 

What is the part number for Iconic 3 gang grid and cover assembly (less mechanisms)?

In the Iconic range, switch grid and skin(cover) are sold separately.
Part number of the 3 gang switch grid is 3043G. For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=3043G
Part number of the skin is 3043C. Skins are available in Vivid White(VW), Warm White(WY), Cool Grey(CY) and Anthracite(AN). 
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=3043C-WY


 

How is MTBF (Mean Time Between Failures) Calculated?

Goals and Symptoms:

How is MTBF (Mean Time Between Failures) Calculated?

Causes and Fixes:

How is MTBF (Mean Time Between Failures) Calculated?

1. Computed following RDF2000 Reliability model (UTE C 80-810 standard) - EQUIPMENT ambient temperature at 30deg C (86deg F), 60deg C (140deg F) and 85deg C (185deg F)
  • 2. Continuous operation profile: 100% operation rate per year (365d / year, 24h / day) - 12 power on/off per year (1 per month) - No stocking days
  • 3. Intermittent operation profile: 46% operation rate per year (335d / year 12h /day) - 335 power on/off per year (1 per operating day) 30 stocking days
  • 4. MTBF are given in hours

Powerview displays Rev. N, please wait or does not communicate with the UPS

 

Issue

The Powerview display interface displays "Rev. N, please wait" indefinitely or has some other type of communication issue.


Product Line

Symmetra Power Array
Symmetra RM
Symmetra LX
PowerView Display interface


Environment

All serial ranges


Cause

The PowerView upon booting up and initializing will request the UPS model name from the Symmetra Main Intelligence module. It will wait at the "PowerView Rev. N please wait..." screen until it is informed as to what APC UPS it is connected to.  If there is no response then it will ask again in 5 second intervals.  It is normal for this message to be displayed for a period of 30-60 seconds, however, if there is no response for an extended PowerView hangs up and displays the Rev. screen.  Other communication problems can exist such as missing values or  blank screen.  There are several possible causes for this so it will be necessary to troubleshoot to find the cause.


Resolution


There are several troubleshooting steps that can be taken to identify the cause of the issue.
 
  1. Inspect the LEDs on the front of the main intelligence module (MIM) for any abnormal indicators.  Indicators of a problem could include seeing no LEDs, a solid red LED, or a solid amber LED.  A replacement module may be needed.  If the UPS is a Symmetra LX, a faulty IM can be removed and the system can be retested with the redundant intelligence module.  This is not possible with Symmetra RM or Symmetra Power Array because the RIM is not capable of communication with the accessories.
     
  2. Check the RJ45 connection between the cable and the PowerView for any damage or bent pins.  If any damage is noted, the appropriate part(s) should be replaced.
     
  3. Substitute a known functioning cable in place of the stock cable that connects the PowerView and UPS and observe if communication is re-established.  The proper cable is a common Ethernet cable i.e. a straight through category 5 unshielded twisted pair (UTP) cable terminated with RJ-45 connectors.
     
  4. If the UPS is a Symmetra LX, connect the PowerView to the other intelligence module to test a different pass-through port.
     
  5. Connect the PowerView to the Remote PowerView port located on the Symmetra Communication Card at the rear of the UPS and observe if communication is re-established.
     
  6. Reseat the Symmetra Communication Card to ensure there is a good connection.  Check to see if communication is re-established.
     
  7. Check other attached accessories to identify whether or not they are also having communication issues.  If only the PowerView is experiencing an issue, attach a known functioning PowerView to the system and observe to see if communication can be established.
     
  8. If the UPS is a Symmetra LX, disable the MIM and allow the RIM to assume control of the system.  Now that the accessories are communicating with a different intelligence module, observe if communication is re-established.
     
  9. The Symmetra Communication card can be tested by establishing a hyperterminal session to the MIM using the DB9 serial port on the rear communication card. Use the 940-1524 or 940-0024 cable from the DB9 to your computer. Connect at a baud rate of 2400 , 8 none, 1. Flow control should be XON/XOFF. At the terminal screen enter a <shift> Y. You should receive a SM back if there is communication from the Comm Card to the MIM. You can also send a "Control A" to determine if the MIM is responding with its model name. If you do not receive a SM the SYCC is defective, assuming the HyperTerminal session is properly configured.
     
  10. Replace the display.  The display itself could be faulty.
     
  11. If the problem cannot be isolated to a particular component and replacement of the parts mentioned above do not remedy the situation, there could be an issue with the backplane PCB of the Symmetra.
If assistance is required with these troubleshooting steps, contact APC by Schneider Electric technical support.