Switch Vert 2G 1/2way 10AX 250V LED VW

Clipsal Iconic - Flush Switch 2 Gang Veritcal Mount 1-Way/2-Way, 250V, 10AX, LED

Catalogue Number: 3042VAL
Switch Vert 2G 1/2way 10AX 250V LED VW
Colour: Vivid White
Colour: Per UOM Std.
  • Vivid White 1 PCE

Specifications

hide show
Range
Clipsal Iconic
Product or component type
switch
Device application
lighting
Colour tint
vivid white
Quantity per set
set of 20
Device presentation
complete product
Control type
rocker
Device mounting
flush
Installation direction
vertical
Switch function
1-pole 1/2-way
Number of rocker
2
Local signalling
LED indicator
Rated current
10 A
[Ue] rated operational voltage
250 V
Material
plastic
Height
120 mm
Width
78 mm
Depth
39 mm
Net weight
0.092 kg
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Environmental

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Does part number 3044V44 available in Cool Grey?

Part number comes standard as Vivid White, will need Cool Grey cover to suit.
 

What is the part number for a 2 gang Iconic switch plate and switch mech and dimmer?

The part number for a 2 gang Iconic switch plate and switch mech and dimmer is - 3042HA , 40M & 41E300PBUD2SM

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3042HA
https://www.clipsal.com/Trade/search-results?q=40M
https://www.clipsal.com/Trade/search-results?q=41E300PBUD2SM
User-added image

What is the part number for the 1 gang Iconic switch , and can the mech be rotated for horizontal or vertical switch plates?

The part number for the 1 gang Iconic switch , and can the mech be rotated for horizontal or vertical switch plates - 3041VA and yes can be mounted Vertical or Horizontal..
For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3041VA
User-added image

What metal wall box suits the 39/2VA?

The wall box that suits the 39/2VA is 157/2.

Some of the key features are:
  • Sliding nut
  • 84 x 46 mm mounting centre
  • Suits universal wall construction
  • Horizontal and vertical mounting
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=157/2



 

What can cause an USF (undervoltage fault) on an ATV12 drive?

Issue: 
What can cause an USF (undervoltage fault) on an ATV12 drive?

Product Line:
Altivar 12

Environment:
All

Cause:
Fault condition

Resolution:
For N4, 480V drives at factory setting of 480VAC, the threshold is 430VDC on the DC bus or 304VAC on the line terminals. 
For M3, 240V drives at factory setting of 260VAC, the threshold is 230VDC on the DC bus or 163VAC on the line terminals.

Recommendations:
- Measure the the incoming line to line voltages
- Compare the line voltage to the Mains Voltage as shown under monitoring MON.
- If the standard line voltage is low, you can adjust the Mains voltage setting
- Adjust the Undervoltage time out to compensate for line contactors, or add time delay before a fault would occur. 
- Check to issues where line potential is dropping due to supply issues that may be caused by load pulling too much current.

Do you do a ICONIC switch 5 gang with LED's?

The ICONIC switch 5 gang is not available with LED's however can be purchased then LED's can be added so a 3045-VA and a 40MLEDW

What is part number for 2 gang Iconic switch?

The part number for 2 gang Iconic switch is a 3042VA

for more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=3042VA

User-added image

What are the causes of an USF fault on ATV61 drives?

Issue:
What are the causes of an USF fault on ATV61 drives?

Product line:
ATV61, ATV71, Altivar 61, Altuvar 71

Environment:
All models

Cause:
Undervoltage supply.

Resolution:
The USF fault occurs when the DC bus voltage level drops below the threshold set in 1.8 Fault Management > Undervoltage Management > Undervoltage level. 

For N4, 480V drives at factory setting of 480VAC, the threshold is 430VDC on the DC bus or 304VAC on the line terminals. 
For M3, 240V drives at factory setting of 260VAC, the threshold is 230VDC on the DC bus or 163VAC on the line terminals.
For Y, 575V drives at factory setting of 690VAC, the threshold is 571VAC on the DC bus, or 404VAC on the line terminals.

Recommendations:
- Measure the the incoming line to line voltages
- Compare the line voltage to the Mains Voltage as shown under Menu 1.2 Monitoring, and also the measurement of the DC bus voltage.
- If the standard line voltage is low, you can adjust the Mains voltage setting.
- Adjust the Undervoltage time out to compensate for line contactors, or add time delay before a fault would occur. 
 

What are the part numbers to make a Bluetooth switch with rotary dimmer in Anthracite?

The Part numbers required to make a Bluetooth dimmer in Anthracite are:

3042G -(Grid)
3042C-AN -(Cover)
40APB-AN -(Push button dolly in Anthricite)
40EDIMKB-AN -(Rotary knob Kit in Anthricite)
41E6PBES3SBM-VW -(Bluetooth Switch Mechanism)
42E350RUD2M-VW -(Rotary Dimmer Mechanism)

For further information please visit www.clipsal.com/iconic