Switch Arch 2G 1/2way 10AX 250V LED VW

Clipsal Iconic - Flush Switch, 2 Gang, 1-Way/2-Way, Architrave 250V, 10AX, LED

Catalogue Number: 3042AL
Switch Arch 2G 1/2way 10AX 250V LED VW
Colour: Vivid White
Colour: Per UOM Std.
  • Vivid White 1 PCE

Specifications

hide show
Range
Clipsal Iconic
Product or component type
switch
Device application
lighting
Colour tint
vivid white
Quantity per set
set of 20
Device presentation
complete product
Control type
rocker
Device mounting
flush
Installation direction
vertical
Switch function
1-pole 1/2-way
Number of rocker
2
Local signalling
LED indicator
Rated current
10 A
[Ue] rated operational voltage
250 V
Material
plastic
Height
120 mm
Width
38 mm
Depth
39 mm
Net weight
0.05 kg
Sustainable offer status
Green Premium product
EU RoHS Directive
Compliant
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What are the dimensions of a 4061AL or 4062AL plate ?

The plate dimensions are the same for 1 gang and 2 gang saturn architrave
97mm Hx 38mm W

What is the part number for a 2 gang Iconic switch plate and switch mech and dimmer?

The part number for a 2 gang Iconic switch plate and switch mech and dimmer is - 3042HA , 40M & 41E300PBUD2SM

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3042HA
https://www.clipsal.com/Trade/search-results?q=40M
https://www.clipsal.com/Trade/search-results?q=41E300PBUD2SM
User-added image

What can cause an USF (undervoltage fault) on an ATV12 drive?

Issue: 
What can cause an USF (undervoltage fault) on an ATV12 drive?

Product Line:
Altivar 12

Environment:
All

Cause:
Fault condition

Resolution:
For N4, 480V drives at factory setting of 480VAC, the threshold is 430VDC on the DC bus or 304VAC on the line terminals. 
For M3, 240V drives at factory setting of 260VAC, the threshold is 230VDC on the DC bus or 163VAC on the line terminals.

Recommendations:
- Measure the the incoming line to line voltages
- Compare the line voltage to the Mains Voltage as shown under monitoring MON.
- If the standard line voltage is low, you can adjust the Mains voltage setting
- Adjust the Undervoltage time out to compensate for line contactors, or add time delay before a fault would occur. 
- Check to issues where line potential is dropping due to supply issues that may be caused by load pulling too much current.

What are the causes of an USF fault on ATV61 drives?

Issue:
What are the causes of an USF fault on ATV61 drives?

Product line:
ATV61, ATV71, Altivar 61, Altuvar 71

Environment:
All models

Cause:
Undervoltage supply.

Resolution:
The USF fault occurs when the DC bus voltage level drops below the threshold set in 1.8 Fault Management > Undervoltage Management > Undervoltage level. 

For N4, 480V drives at factory setting of 480VAC, the threshold is 430VDC on the DC bus or 304VAC on the line terminals. 
For M3, 240V drives at factory setting of 260VAC, the threshold is 230VDC on the DC bus or 163VAC on the line terminals.
For Y, 575V drives at factory setting of 690VAC, the threshold is 571VAC on the DC bus, or 404VAC on the line terminals.

Recommendations:
- Measure the the incoming line to line voltages
- Compare the line voltage to the Mains Voltage as shown under Menu 1.2 Monitoring, and also the measurement of the DC bus voltage.
- If the standard line voltage is low, you can adjust the Mains voltage setting.
- Adjust the Undervoltage time out to compensate for line contactors, or add time delay before a fault would occur.