Switch Vert IP44 1G 1/2way 10AX 250V VW

Switch Vertical 1G 1/2 Way 10AX 250V IP44

Catalogue Number: 3041V44
Switch Vert IP44 1G 1/2way 10AX 250V VW
Colour: Vivid White
Colour: Per UOM Std.
  • Vivid White 1 PCE
Added to cart

Specifications

hide show
Range
Clipsal Iconic
Product or component type
switch
Device application
lighting
Colour tint
vivid white
Quantity per set
set of 20
Device presentation
complete product
Control type
rocker
Device mounting
flush
Installation direction
vertical
Switch function
1-pole 1/2-way
Number of rocker
1
Rated current
10 A
[Ue] rated operational voltage
250 V
Material
plastic
Height
124 mm
Width
82 mm
Depth
40 mm
Net weight
0.098 kg
IP degree of protection
IP44
EU RoHS Directive
Under investigation
Environmental Disclosure
ENVPEP120506EN

Documents & downloads

hide show
Filter items
  • All

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Does part number 3044V44 available in Cool Grey?

Part number comes standard as Vivid White, will need Cool Grey cover to suit.
 

What is the part number for the 1 gang Iconic switch , and can the mech be rotated for horizontal or vertical switch plates?

The part number for the 1 gang Iconic switch , and can the mech be rotated for horizontal or vertical switch plates - 3041VA and yes can be mounted Vertical or Horizontal..
For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3041VA
User-added image

Is there a horizontal version of Iconic 3041/45, single pole 250V, 45A cooking appliance isolator?

3041/45, single pole 250V, 45A cooking appliance isolator can be vertical or horizontal mounted. However the mechanism orientation cannot be changed.
For further information, please visit https://www.clipsal.com/Trade/Products/ProductDetail?CatNo=3041/45

Do we have any series ratings with the Masterpact NT and NW breakers?

Issue:
Do we have any series ratings with the Masterpact NT and NW breakers?

Product Line:
Masterpact NW, NT

Environment:
Masterpact breakers in NEMA markets

Resolution:
There are no series ratings for Masterpact NT, NW circuit breakers.
There are none for the obsolete SE or Masterpact MP either.
 

What is the percentage of imbalance that will cause a single phase sensitive D-line overload to trip?

Issue:
Identifying trip point in a single phase sensitive overload relay

Product Line:
NEMA combination starters

Environment:
Products sold and used in the United States

Cause:
Identifying the trip point in a single phase sensitive Tesys D overload relay

Resolution:
The phase loss sensitive overloads are designed to conform to IEC standard 60947-4-1. In that standard is this paragraph:

8.2.1.5.2 Limits of operation of three-pole thermal overload relays
energized on two poles
With reference to table 4:
The overload relay or starter shall be tested in its enclosure if normally fitted. With the relay
energized on three poles, at A times the current setting, tripping shall not occur in less than
2 h, starting from the cold state, at the value of the ambient air temperature stated in table 4.
(Table 4 `A` multiple of current setting states 2 poles at 1.0 times the current setting, the third pole at 0.9)

Moreover, when the value of the current flowing in two poles (in phase loss sensitive relays,
those carrying the higher current) is increased to B times the current setting, and the third
pole de-energized, tripping shall occur in less than 2 h. (Table 4 `B` multiple of current setting is 2 poles
at 1.15 current setting, third pole at 0.0.)

The values shall apply to all combinations of poles.

In the case of thermal overload relays having an adjustable current setting, the characteristics
shall apply both when the relay is carrying the current associated with the maximum setting
and when the relay is carrying the current associated with the minimum setting.