Clipsal Iconic Shallow Mounting Block 1 Gang, 32 mm

Clipsal Iconic Shallow Mounting Block, 1 Gang, 32 mm

Clipsal Iconic Shallow Mounting Block 1 Gang, 32 mm

Item Number: 3000SM-VW

Retail
$11.10
RRP (Inc. GST)
Colour Vivid White (VW)
  • Vivid White 1 PCE

Product Dimensions

Width icon

Width140 mm

Height icon

Height91 mm

Depth icon

Depth32 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Clipsal Iconic

Product brand

Clipsal

Product or component type

mounting box

Physical

Number of gangs

1 gang

Length

140 mm

Height

91 mm

Width

140 mm

Depth

32 mm

Depth

32 mm

EU RoHS Directive

Under investigation

Material

Material

plastic

Others

Shape

rectangular

Package 1 Weight

0.076 kg

Package 1 Height

32 mm

Package 1 width

91 mm

Package 1 Length

140 mm
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Does PowerLogic SCADA support waveform data of ION meters?

No, Powerlogic SCADA (PLS) currently does not support the waveform data from ION meters; valid through PLS v7.10 SR3.
Waveforms from the following devices are currently supported as of v7.10 SR3: Circuit Monitor 3000s, Circuit Monitor 4000s, Power Meter 800s, and Sepam 20s, 40s, and 80s.


Legacy KB System (APS) Data: RESL200266 V2.0, Originally authored by KBAdPM on 10/16/2009, Last Edited by MaTh on 12/01/2010
Related ranges: PowerLogic SCADA 7.1

Would a 755SMA be able to replace a 3000SSA directly?

No, the two have different bases.

What is the part number for standard din rail?

The part number for standard din rail is NSYSDR200B. It is 7.5mm deep by 2000mm long.

Do you have a 45RU data cabinet 800mm Wide X 1000mm Deep?

Yes, the part number is 3106N45C810-BK.

What is the part number for a 45RU data cabinet , 800mm wide and 1000mm deep?

The part number for a 45Ru data cabinet that has dimensions of W800m x D1000mm is - 3106N45C810

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=3106N45C810

What is the Pin out detail for the Modbus programming cable 110 XCA 20 3000?

The pin out details of the Modbus programming cable 110 XCA 20300 is as shown in the attached.

 

What is the altitude derating for a TeSys D-Line contactor?

Issue:​
What is the altitude derating for a TeSys D-Line contactor?

Product Line:
Digest 177 Section 18 : Contactors and Starters, IEC

Environment:
North American Products

Resolution:
The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

Voltage
3500m x 0.90
4000m x 0.80
4500m x 0.70
5000m x 0.60

Current
3500m x 0.92
4000m x 0.90
4500m x 0.88
5000m x 0.86

For example, an LC1D80 at 5000 meters:
- The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
- The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



 

What is the MTBF (Mean Time Between Failure) for Lexium 32?

The MTBF (Mean Time Between Failure) for the Lexium 32 product range equals 300000 hours.

Will the 30RSM mechanism fit into a Saturn plate?

No, unfortunately this mechanism does'nt fit the Saturn series. However, this mechanism will fit into the coms Saturn series comunication plate 4031VH.

Is the 600SM available in red

No, it only comes with White and Black covers.

What parts are required to make a Saturn permanent connection unit (PCU)?

4032VH + 30USM + 38TB

What is the effect of altitude on ATV312?

Product Line:
All ATV312 and ATV31

Environment:
High altitude, more than 1000m

Cause:
What is the effect of the high altitude on the drive.

Resolution:
For all ATV312, less than 1000m, no derating.
For single-phase supplie and corner grounded distribution networks, up to 2000m, derateing 1% per 100m.
For three-phase supplies, up to 3000m, derating 1% per 100m.




 

Show More