INS100 3P 100A
28908
Compact INS160 3P; Switch Disconnector
INS100 3P 100A
28908
Compact INS160 3P; Switch Disconnector

Compact Interpact Switch Disconnector INS100, 3 Poles, 100A

Catalogue Number: 28908
INS100 3P 100A
28908
Compact INS160 3P; Switch Disconnector
INS100 3P 100A
28908
Compact INS160 3P; Switch Disconnector
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Compact
Range of product
INS40...160
Product name
Compact INS
Product or component type
switch disconnector
Device short name
Compact INS100
Switch-disconnector name
Compact INS100
Poles description
3P
Network type
  • AC
  • DC
    • Network frequency
      50/60 Hz
      [Ie] rated operational current
    • AC-22A: 100 A AC 50/60 Hz 220/240 V
    • AC-23A: 63 A AC 50/60 Hz 660/690 V
    • DC-22A: 100 A DC 125 V 2 poles in series
    • DC-23A: 100 A DC 125 V 2 poles in series
    • AC-22A: 100 A AC 50/60 Hz 380/415 V
    • AC-22A: 100 A AC 50/60 Hz 440/480 V
    • AC-22A: 100 A AC 50/60 Hz 500 V
    • AC-22A: 100 A AC 50/60 Hz 660/690 V
    • AC-23A: 100 A AC 50/60 Hz 220/240 V
    • AC-23A: 100 A AC 50/60 Hz 380/415 V
    • AC-23A: 100 A AC 50/60 Hz 440/480 V
    • AC-23A: 100 A AC 50/60 Hz 500 V
      • [Ui] rated insulation voltage
        750 V AC 50/60 Hz
        [Uimp] rated impulse withstand voltage
        8 kV
        [Ith] conventional free air thermal current
        100 A at 60 °C
        [Icm] rated short-circuit making capacity
      • 154 kA with upstream protection circuit breaker 690 V AC at 50/60 Hz
      • 20 kA switch-disconnector alone 690 V AC at 50/60 Hz
        • [Ue] rated operational voltage
        • 125 V DC
        • 690 V AC 50/60 Hz
          • Suitability for isolation
            yes
            Contact position indicator
            yes
            Visible break
            no
            Pollution degree
            3
            Control type
            rotary handle
            Handle colour
            black
            Mounting mode
            fixed
            Mounting support
          • plate
          • DIN rail
            • Upside connection
              front
              Downside connection
              front
              Maximum power
            • AC-23: 22 kW at 220/240 V AC 50/60 Hz
            • AC-23: 45 kW at 380/415 V AC 50/60 Hz
            • AC-23: 55 kW at 440 V AC 50/60 Hz
            • AC-23: 55 kW at 500/525 V AC 50/60 Hz
            • AC-23: 55 kW at 660/690 V AC 50/60 Hz
              • Rated duty
                uninterrupted
                Intermittent duty class
                class 120 - 60 %
                Enclosure dimensions for Ithe
                260 mm x 160 mm x 55 mm
                [Icw] rated short-time withstand current
              • 0.01 kA during 30 s conforming to IEC 60947-3
              • 1.23 kA during 20 s conforming to IEC 60947-3
              • 3.175 kA during 3 s conforming to IEC 60947-3
              • 5.5 kA during 1 s conforming to IEC 60947-3
                • Mechanical durability
                  15000 cycles
                  Electrical durability
                • AC-22A: 1500 cycles 220/240 V AC 50/60 Hz
                • DC-23A: 1500 cycles 250 V DC 2 poles in series
                • AC-22A: 1500 cycles 690 V AC 50/60 Hz
                • AC-23A: 1500 cycles 690 V AC 50/60 Hz
                • AC-22A: 1500 cycles 380/415 V AC 50/60 Hz
                • AC-22A: 1500 cycles 440 V AC 50/60 Hz
                • AC-22A: 1500 cycles 500 V AC 50/60 Hz
                • AC-23A: 1500 cycles 220/240 V AC 50/60 Hz
                • AC-23A: 1500 cycles 380/415 V AC 50/60 Hz
                • AC-23A: 1500 cycles 440 V AC 50/60 Hz
                • AC-23A: 1500 cycles 500 V AC 50/60 Hz
                • DC-22A: 1500 cycles 250 V DC 2 poles in series
                  • Connection pitch
                    30 mm
                    Height
                    100 mm
                    Width
                    135 mm
                    Depth
                    62.5 mm
                    Net weight
                    0.8 kg
                    Compatibility code
                    INS100
                    Standards
                  • IEC 60947-3
                  • IEC 60947-1
                    • Product certifications
                    • CCC
                    • KEMA-KEUR
                      • IP degree of protection
                        IP40 conforming to IEC 60529
                        IK degree of protection
                        IK07 conforming to EN 50102
                        Ambient air temperature for operation
                        -25-70 °C
                        Ambient air temperature for storage
                        -50-85 °C
                        Sustainable offer status
                        Green Premium product
                        REACh Regulation
                        Free of Substances of Very High Concern above the threshold
                        REACh free of SVHC
                        Yes
                        EU RoHS Directive
                        Compliant
                        Toxic heavy metal free
                        Yes
                        Mercury free
                        Yes
                        RoHS exemption information
                        Yes
                        China RoHS Regulation
                        X
                        Environmental Disclosure
                        ENVPEP1304024
                        Circularity Profile
                        N/A
                        WEEE
                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                        California proposition 65
                        WARNING: This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
                        Warranty
                        18 months

                        Documents & downloads

                        hide show
                        Filter items
                        • All

                        • CAD Files and Packs

                        • Technical Data Catalogues

                        • Catalog Page

                        • Product Environmental

                        • Installation Instruction

                        • End of Life Manual

                        • Operating Manuals

                        • Specification for Tender

                        • Declaration of Conformity

                        Frequently Asked Questions

                        hide show

                        What is the load break switch 63Amp 3P dinrail mounted with extended rotary handle

                        You can use a 28902 load break switch with a LV428941 extended rotary handle

                        Is there a replacement handle for the INS63 / 28902?

                        Yes - The 28962 suits the INS40 - INS60 load break switches

                        What is the replacement for RM4JA01F?

                        The replacement is RM22JA21MR, but if not in stock, can offer the RM35JA31MW 
                        see data sheets for more information.....https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM35JA31MW
                        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM22JA21MR
                        User-added image

                        What is the replacement for the RM4JA32F?

                        Replacement for the RM4JA32F is the RM35JA32MW
                        For more information, see data sheet.....https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RM35JA32MW
                        User-added image

                        Does a UV trip or UVR undervoltage release sense phase loss?

                        Issue:
                        Does a UV trip or UVR undervoltage release sense phase loss?

                        Product Line:
                        Circuit Breakers

                        Environment:
                        Circuit breakers that have a UVR undervoltage trip

                        Resolution:
                        The UVR will sense phase loss only on the phase(s) its control power is taken from. The UVR should not be used in place of a phase-failure. See the latest Digest for phase-failure relay information.

                        Replacement for a 28945

                        The equivalent part number in Australia is 28943.


                         

                        What is the part code for a CDS load shedding contactor

                         The part code is 15908

                        What is the IP rating of the 28943 extended rotary handle ?

                        The IP rating of the 28943 rotory handle is IP55

                        What is the alternative part number for the 28941 INS extended handle?

                        The alternative part number is
                        LV428941
                         

                        What is the part code for IN160T options

                        The part code is a 28912

                        Netbotz 500, 420, or 320 loses configuration when it is rebooted.

                        Issue:

                        Netbotz 500, 420, or 320 loses configuration when it is rebooted

                        Product Line:

                        NetBotz

                        Environment:

                        Version 2 NetBotz

                        Cause:

                        Due to a change on the Netbotz devices, some 500s, 420s, and 320s made in mid 2007 began losing some configuration when the system was rebooted. Prior to rebooting the device, the unit would function normally.

                        Resolution:

                        Version 2.6.2 of Botzware has fixed this issue.

                        Extended front rotary handle for the 28910 INS 125A Load Break Switch ?

                        Code = LV428941

                        What is the code for the Acti9 MX shunt trip equivalent to the Merlin Gerin 26948 12-24vAC?

                        A9A26948
                         

                        Is the 28941 the shaft for the extended handle on the INS160

                         Yes it is the correct part code

                        What is the part code for a din rail mounted isolator, 3P 150A

                         You can use a 28912

                        What is the replacement for a 5 Series Load Breaker 5LBC4125CD?

                        The replacement for 5 Series load breaker 5LBC4125CD is a schnieder 31335.

                        For further information please visit the link below.

                        https://www.schneider-electric.com.au/5ser31335

                        https://www.elteh.eu/wp-content/uploads/schneider/H619250_web.jpg

                        What is the part number for the black handle only to suit extended rotary handle 28943?

                        The part number for the black handle only to suit extended rotary handle 28943 is - 28962

                        For further information visit the link below:-
                        https://www.schneider-electric.com.au/en/search/28962
                        User-added image

                        Sun Java Updates for Multiple Vulnerabilities – InfraStruXure Manager 4.7

                        "Sun has released alerts to address multiple vulnerabilities affecting the Sun Java Runtime Environment. The most severe of these vulnerabilities could allow a remote attacker to execute arbitrary code. The InfraStruXure Manager installer relies on the JRE installed on the client machine.

                        Sun Java Runtime Environment versions affected:
                        • JDK and JRE 6 Update 6 and earlier
                        • JDK and JRE 5.0 Update 15 and earlier
                        • SDK and JRE 1.4.2_17 and earlier
                        • SDK and JRE 1.3.1_22 and earlier


                        Alert Information
                        • 238628 Security Vulnerabilities in the Java Runtime Environment related to the processing of XML Data
                        • 238666 A Security Vulnerability with the processing of fonts in the Java Runtime Environment may allow Elevation of Privileges
                        • 238687 Security Vulnerabilities in the Java Runtime Environment Scripting Language Support
                        • 238905 Multiple Security Vulnerabilities in Java Web Start may allow Privileges to be Elevated
                        • 238965 Security Vulnerability in Java Management Extensions (JMX)
                        • 238966 Security Vulnerability in JDK/JRE Secure Static Versioning
                        • 238967 Security Vulnerability in the Java Runtime Environment Virtual Machine may allow an untrusted Application or Applet to Elevate Privileges
                        • 238968 Security Vulnerabilities in the Java Runtime Environment may allow Same Origin Policy to be Bypassed

                        Severity Risk
                        Critical for a vulnerable system installed JRE

                        Recommendations and workarounds:

                        1. Update all vulnerable system installed JREs to a patched version according to Sun’s recommendations [1].
                        2. Uninstall InfraStruXure Manager client
                        3. Reinstall InfraStruXure Manager client.

                        Exploitation and Public Announcements
                        APC is not aware of any malicious use of the vulnerabilities described in this advisory.


                        THIS IS AN ACTIVE ADVISORY. ALTHOUGH APC CANNOT GUARANTEE THE ACCURACY OF ALL STATEMENTS IN THIS NOTICE, ALL OF THE FACTS HAVE BEEN CHECKED TO THE BEST OF OUR ABILITY. APC DOES NOT ANTICIPATE ISSUING UPDATED VERSIONS OF THIS ADVISORY UNLESS THERE IS SOME MATERIAL CHANGE IN THE FACTS. SHOULD THERE BE A SIGNIFICANT CHANGE IN THE FACTS, APC MAY UPDATE THIS ADVISORY. A STAND-ALONE COPY OR PARAPHRASE OF THE TEXT OF THIS SECURITY ADVISORY THAT OMITS THE DISTRIBUTION URL IN THE FOLLOWING SECTION IS AN UNCONTROLLED COPY, AND MAY LACK IMPORTANT INFORMATION OR CONTAIN FACTUAL ERRORS.

                        IN NO EVENT SHALL EITHER APC, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES, BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING, BUT NO LIMITED TO, LOSS OF PROFITS ARISING OUT OF THE USE OR IMPLEMENTATION OF THE INFORMATION CONTAINED HEREIN HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN AN ACTION FOR CONTRACT, STRICT LIABILITY OR TORT (INCLUDING NEGLIGENCE) OR OTHERWISE, WHETHER OR NOT APC HAS BEEN ADVISED OR THE POSSIBILITY OF SUCH DAMAGE AND NOTWITHSTANDING THE FAILURE OF ESSENTIAL PURPOSE OF ANY REMEDY.


                        References
                        [1] https://sunsolve.sun.com/search/document.do?assetkey=1-66-238628-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238666-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238687-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238905-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238965-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238966-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238967-1
                        https://sunsolve.sun.com/search/document.do?assetkey=1-66-238968-1
                        https://www.us-cert.gov/cas/techalerts/TA08-193A.html


                        Copyright
                        This notice is Copyright 2008 by American Power Conversion Corporation. This notice may be redistributed freely after the release date given at the top of the text, provided that redistributed copies are complete and unmodified, and include all date and version information. 

                        Please note that InfraStruxure Manager is no longer updated and Schneider Electric urges customers to move to the more recent monitoring offerings such as StruxureWare Data Center Expert.

                        What is the reference of Type A or Type B thermostat in Prisma Plus switchboard?

                        Type C thermostat is available in Prisma Plus, the part reference of which is 08998. The Type C thermostat Reference 08998 can be used as Type A or Type B by carrying out the modification in the settings and cabling.
                         
                        For making the thermostat Type A or Type B, connect load on the terminal 2 instead of terminal 3 and the supply at L and N. See figures attached for details.






                         

                        Are EasyPact MVS circuit breakers for sale in the USA or Canada?

                        Issue:
                        Where can I buy a EasyPact MVS breaker?

                        Product Line:
                        EasyPact MVS circuit breakers

                        Resolution:
                        There are no plans for a general release of the EasyPact MVS circuit breaker line in the US.
                         

                        What ethernet ports are used by System Manager Software (SMS)?

                         

                        text
                        The user must be an Administrator or PowerUser on the server (for installation the user has to be an Administrator)

                        > Port 80 has to be open for HTTP access via IIS (access by remote browser)

                        > Port 8888 has to be open for PowerLogic Network Server (local server only)

                        > Port 8889 has to be open for Alarm Event Server access (local server only)

                        > Port 1433 has to be open for the SMS database (local server only)

                        > Port 1240 has to be open for the Browser Connection Manager (local PC only)

                        >Port 20978 has to be open for the Alarm Web Service

                        >Port 502 has to be open for Modbus TCP

                        >Port 21 has to be open for FTP

                        >Port 102 has to be open if using TCP/MMS (EGW drivers) 

                        text text
                        text text
                        text text
                        Original article#1630
                        Internal PMO/PMC
                        © Schneider Electric 2005

                        Legacy KB System (APS) Data: RESL184565 V2.0, Originally authored by DaMi on 06/16/2007, Last Edited by MaTh on 02/26/2010
                        Related ranges: System Manager 3.3, System Manager 4.0

                        How to View and Clear DNP3 Events in a SCADAPack E

                        Only the configured master can collect events generated in a SCADAPack E. Sometimes it is necessary to check to see how many events you may have in the SCADAPack E, or you may want to use the event count in logic applications for control purposes. There are two main methods used to check the amount of events in a SCADAPack E. These are through the command line interface or by looking at system points.

                        Command Line Interface

                        You can access the command line interface through different methods. This includes Telnet, a serial port configured as “command line” or by using the Virtual Command Line (Virtual Terminal) in E Series Configurator. The example below will use the Virtual Terminal method.
                        If you have a valid DNP3 connection to a SCADAPack E, the Virtual Command line can be opened by the drop down menu “Transfer -> Remote Command Line” or by clicking on the icon in the tool bar as shown below.



                        At the command prompt, type “Status Events”. You will get the current uptime, IEC-61131-3 resource activity, general status information and a list of the events for each DNP3 object type as seen in the image below.



                        If at any time you would like the clear all of the events in the SCADAPack (DNP3 protocol only, does not clear IEC 60870-5 events), you can type “Clear Events” at the command line prompt. Typically, you will reserve this command for testing purposes only. DNP3 historical events are used for reporting purposes. If events are cleared without a master station confirmation, then unexpected data loss will be expected.

                        System Points

                        You can also view the events for each DNP3 data type in a SCADAPack E by looking at the read-only system points. There are system points for each configured master station. This example will only review Master station 1 DNP3 events. The values in the system points will be 16-bit Integer values. Since they are read only, you cannot configure these to be points in the SCADAPack E Database. In other words, they cannot be placed in a class to be polled from a Master station.

                        Below is a list of the system points for DNP3 object type events for Master station 1. The complete list can be found in the technical help manuals installed with SCADAPack E Configurator.

                        58000 Binary Input Event Count
                        58001 Counter Input Event Count
                        58002 Analog Input Event Count
                        58003 Float Input Event Count
                        58004 Binary Output Event Count
                        58005 Analog Output Event Count
                        58006 Float Output Event Count
                        58007 Binary Output Command Event Count
                        58008 Analog Output Command Event Count
                        58009 Float Output Command Event Count

                        You can view these points by looking at them in the point browser. Put the point number for the corresponding DNP3 datatype as in the image below. You will select the point to be “Analog Input” in the point browser. Once you click  the read button, you will be able to see the event counts.



                        If you would like to use these points in a IEC-61131-3 SCADAPack Workbench logic application, you can use GETPNTSS function blocks in SCADAPack Workbench to read the system points. The result of the function block will show the events for that particular DNP3 data type. See example below.



                        More information can be found in the SCADAPack E Technical Help manuals installed with E Series Utilities.



                         

                        PowerSCADA Expert 8.2 Update 5 - Release Notes

                        Issue
                        What is new in PSE8.2 and a detailed listing of resolved problems and minor enhancements.

                        Product Line
                        PowerSCADA Expert 8.2 (PSE8.2)

                        Environment
                        Installer
                         
                        Cause
                        A new PSE8.2 cumulative update release.

                        Resolution
                        PowerSCADA Expert 8.2 Update 5 - Release Notes
                        Release Notification (Updated 25 April 2018)

                        This is a detailed listing of resolved issues and minor enhancements in this release.

                         


                         

                        Prerequisite

                        You must have PowerSCADA 8.2 installed prior to installing this update. No previous updates are required.

                        Cybersecurity Announcement

                        Floating License Manager v2.1 addresses vulnerabilities in the Flexera FlexNet Publisher component detailed in CVE-2016-10395, CVE-2017-5571 and CVE-2016-2177. Uninstall the current version of the Floating License Manager, and then install version 2.1.
                        NOTE: The Floating License Manager v2.1 installer is included with this hotfix release but is not a part of the hotfix installer. Unzip "Floating License Manager v2.1.zip" and run "setup.exe".

                        Important Notice: There is a known issue with the Floating License Manager v2.1.0.0 installer. When installing with a logged-in Windows User name containing a space, the install will not succeed. The workaround is to install the Floating License Manager with a user that does not include a space character in their name.

                        Bug Fixes and Enhancements

                        TFS 21482 - AlarmEvents with a state of normal returned in GetAlarmEvents response for EWS

                        GetAlarmEvents was changed to not return alarms in the normal state.

                        TFS 21483 - Incorrect timestamp information provided for AlarmEvents not in the Active state

                        Alarm timestamps are now updated to reflect the true timestamp of occurrence for all state changes (active, drop out, acknowledge).

                        TFS 21484 - Unable to filter AlarmEvents by Type using EWS

                        Alarms are now filtered based on type. 

                        TFS 21485 - Unable to successfully acknowledge alarms using EWS

                        In some situations, EWS would not acknowledge alarms correctly.  This behavior has been fixed.

                        TFS 21486 - Unable to filter alarms using the PriorityTo and PriorityFrom fields

                        EWS did not observe the priority field correctly. This has been addressed and the minimum allowable priority has been set to 1 (to exclude non-alarm objects in the PowerSCADA alarm database).

                        TFS 21557 - PowerSCADA projects - including the starter project, PLS_Include, and PLS_Example - need to be upgraded to support the new DBF schemas

                        PowerSCADA projects have been upgraded to the latest DBF schemas.  If there are existing projects created from the starter project, set [CtEdit] Upgrade = 1 in the Citect.ini file using the Setup Editor, and then restart PowerSCADA Studio.

                        TFS 21564 - Alarm Proxy does not show the analog alarm states

                        Alarm Proxy now reports the analog alarm states (HIGH HIGH, HIGH, LOW, LOW LOW) instead of ON / OFF.

                        TFS 21566 - If a CSV file that does not exist is selected in the I/O Device Manager, the application throws a runtime exception

                         

                        A message is displayed indicating that the file does not exist.

                         

                        TFS 21569 - On large systems with 200k configured alarms, the GetAlarmDefinitions call in Alarm Proxy is slow and causes ENM to timeout

                        Performance issue in alarm proxy has been resolved.

                        TFS 21649 - When CoreServiceHost adds and removes devices, it may lose the original IDs

                        CoreServiceHost now keeps a device chronicle.  When the device is removed and then later added, the ID will remain the same.

                        TFS 21913 - If the equipment name is changed in the system, but the I/O Device name is unchanged, CoreServiceHost will not refresh the equipment name

                        CoreServiceHost now properly updates the equipment on name change.

                        TFS 21935 - Logs that are too large for the Windows Event Log do not get logged properly

                        Large logs are now broken down into smaller log entries.

                        TFS 21970 - Profile Wizard and Automation does not support IPv6

                        Profile Wizard and Automation now supports IPv6 for TCP/IP Board level drivers.  This requires the TCP/IP Driver version 4.0.0.0 or later.

                        TFS 21975 - Open and Close buttons are disabled at runtime on equipment popup when separate digital tags are used for commands

                        The form now enables the command buttons if the Pos_On or Pos_Off tags are defined.

                        TFS 21979 - Alarm Proxy cannot return alarms that transition to inactive

                        This setting is now configurable in the Application Configuration Utility.

                        TFS 22043 - Single sign-on calls from a remote thick client do not work

                        Single sign-on now detects remote clients.

                        TFS 22060 - The I/O Device Manager cannot bulk import devices with device names greater than 16 characters

                        The I/O Device Manager now reads the device name length from the equipment.profiles file for proper validation.

                        TFS 22066 - Wonderware ArchestrA Logger Security Patch

                        Wonderware ArchestrA Logger Patch 2017.517.2328.1 is applied.

                        TFS 22150 - Alarm filters do not work on some resolutions

                        Alarm filter AN numbers are fixed for all alarm page resolutions.

                        TFS 22155 - Alarm filters perform exact matching

                        The alarm filter screen allows the user to select the filtering mode. The default setting is read from the INI file [Alarm] FilterMode.  0 (default) = Exact Match, 1 = Starts With, 2 = Ends With, 3 = Contains.

                        TFS 22306 - The equipment tree used on alarm pages is slow to render over the web client

                        Any page using the equipment tree should set the default library and symbol on the equipment tree genie, or set 'Hide Symbol Icons' to 'TRUE' if a default icon is not available.

                        TFS 22401 - Alarm filter and equipment tree filter operate independently

                        The alarm filter and equipment tree filter operate together to filter the alarm tables.

                        TFS 22896 - Core service host logs two warnings during shutdown - exception thrown during disposal.

                         

                        Cleanup methods were reworked to prevent the exception.

                         

                        TFS 22898 - EWS cannot obtain tag updates at a 5 second rate

                        EWS and core services were updated to obtain data at a 5 second poll rate.

                        TFS 23262 - Equipment popup alarm table does not acknowledge or disable alarms

                        Alarms can now be acknowledged or disabled in the equipment page.

                        TFS 23274 - Equipment.profiles cannot be imported into the Profile Editor in cases where the original Device Types and Device Profiles were lost

                        The Profile Editor can import the equipment.profiles file to generate device types, device profiles, and tags.

                        TFS 23437 - Citect 2016 Updates

                         

                        Citect 2016 Update (April 10, 2018) is included with this update.

                        Project ID management was removed from Citect 2016.  Project IDs are now located in the ProjectInfo.xml file. 

                        MinUnitNumber and MaxUnitNumber (previously stored in UnitNumberRange.xml) have also been migrated to ProjectInfo.xml.

                         

                        TFS 23637 - The Alarm Summary page does not display state information

                        The Alarm Summary page now displays the state that caused the alarm.

                        TFS 23650 - 8.2 install does not enable ASP feature within IIS

                        The installer now enables the ASP feature under IIS. This server role feature is required to run the Citect web control client. (Previously the View-Only web client was the only option for web deployment.)

                        TFS 24205 - When Core Services receives a timeout from the Client, alarm processing may halt until the service is restarted

                        Core Services properly recovers from a ctApi deadlock condition.

                        Files Modified

                        Applications\AppServices\bin\Framework.dll
                        Applications\AppServices\bin\Framework.ServiceHost.exe
                        Applications\AppServices\bin\Modules.CoreServices.dll
                        Applications\AppServices\bin\PowerLogic.Cipher.dll
                        Applications\AppServices\bin\Modules.ProviderBase.dll
                        Applications\AppServices\bin\Modules.ProviderEngine.TestHarness.exe
                        Applications\AppServices\bin\ObjectFactoryTools.exe
                        Applications\AppServices\bin\ProviderGatewayProviders.dll
                        Applications\AppServices\bin\PowerSCADA.Common.dll
                        Applications\AppServices\bin\Modules.Platform.Citect.dll
                        Applications\EWS\bin\Framework.dll
                        Applications\EWS\bin\EWS.dll
                        Applications\EWS\Web.config
                        Applications\EWS\DataExchange.svc
                        bin\de\ProfileEngine.resources.dll
                        bin\de\ProfileWizard.resources.dll
                        bin\de\WizardLibrary.resources.dll
                        bin\es\ProfileEngine.resources.dll
                        bin\es\ProfileWizard.resources.dll
                        bin\es\WizardLibrary.resources.dll
                        bin\fr\ProfileEngine.resources.dll
                        bin\fr\ProfileWizard.resources.dll
                        bin\fr\WizardLibrary.resources.dll
                        bin\it\ProfileEngine.resources.dll
                        bin\it\ProfileWizard.resources.dll
                        bin\it\WizardLibrary.resources.dll
                        bin\ja\ProfileEngine.resources.dll
                        bin\ja\ProfileWizard.resources.dll
                        bin\ja\WizardLibrary.resources.dll
                        bin\ko\ProfileEngine.resources.dll
                        bin\ko\ProfileWizard.resources.dll
                        bin\ko\WizardLibrary.resources.dll
                        bin\ru\ProfileEngine.resources.dll
                        bin\ru\ProfileWizard.resources.dll
                        bin\ru\WizardLibrary.resources.dll
                        bin\zh-chs\ProfileEngine.resources.dll
                        bin\zh-chs\ProfileWizard.resources.dll
                        bin\zh-chs\WizardLibrary.resources.dll
                        bin\zh-cht\ProfileEngine.resources.dll
                        bin\zh-cht\ProfileWizard.resources.dll
                        bin\zh-cht\WizardLibrary.resources.dll
                        bin\ProfileAutomation.dll
                        bin\ProfileEngine.dll
                        bin\ProfileWizard.exe
                        bin\WizardLibrary.dll
                        bin\ProfileAutomationUtility.exe
                        bin\CommsMethodProperties.xml
                        bin\DeviceManagementUserControlLibrary.dll
                        Applications\Profile Editor\Tags.xml
                        Applications\Profile Editor\ProfileEditor.Business.dll
                        Applications\Profile Editor\ProfileEditor.exe
                        Applications\Profile Editor\ProfileEditor.UserControls.dll
                        Applications\Profile Editor\Resources\ProfileEditor.UserControls.resources
                        User\PLS_Include\*
                        User\PLS_Example\*
                        Starter\Default_Starter.ctz

                        Installation

                        Unzip "PowerSCADA Expert 8.2 Update 5.zip" and run "PowerSCADA Expert 8.2 Update 5.exe".

                        Where can I get support for APC and MGE Products?

                        For support on APC and MGE products please visit:  https://www.apc.com/support/

                        AC Power
                        Additional Management Cards and Options
                        Air Cooled Chillers
                        Air Distribution Accessories
                        Airflow Management
                        AIS 3000
                        AIS 5000
                        AIS Accessories
                        AIS Battery Systems
                        APC CS
                        APC Enterprise Manager
                        APC ES
                        APC RS
                        Application Shutdown Utilities
                        Assessment Services
                        Auto and Air Inverters
                        AV Accessories
                        AV Power Conditioners & Battery Backups
                        AV Power Filters
                        AV Pro Interconnects
                        AV Surge Protectors
                        Backpacks and Messenger Bags
                        Back-UPS
                        Back-UPS Accessories
                        Back-UPS BI
                        Back-UPS CS
                        Back-UPS ES
                        Back-UPS HI
                        Back-UPS HT
                        Back-UPS LS
                        Back-UPS Office
                        Back-UPS Pro
                        Back-UPS RS
                        Back-UPS XS
                        Basic Rack PDU
                        Battery Management
                        Battery Replacement Services
                        Biometric Security
                        Bulk Cable
                        Cabinet Power Distribution
                        Cable Management
                        Charge-UPS EX
                        Commercial/Industrial Surge Suppression
                        Condensers
                        Configurable Power Accessories
                        Configurable Power Distribution
                        Console Port Servers
                        CyberFort
                        Data Center Facility Cooling - Andover Continuum or TAC Vista
                        Data Center Facility Power - PowerLogic ION Enterprise
                        Data Center Software Integration Kits
                        Data Center University
                        Data Distribution Cable
                        DC Battery
                        DC Components
                        DC Distribution Components
                        DC600
                        Desktop KVM
                        Desktop Notebook Stands
                        EcoBreeze Air Economizers
                        Environmental Management System
                        Environmental Monitoring Unit
                        Ethernet Switches
                        Extended Warranties
                        Fiber Optics
                        Firmware Upgrades
                        FLM Series
                        Fluid Coolers
                        FRP/Ferroresonant Power Supply
                        Game Console Surge Protection
                        Gender Changers
                        Global Deployment
                        Hardwire Surge Suppression Accessories
                        High-Density Cooling Enclosures
                        IDE Cables
                        IEEE1394
                        Industrial
                        InfraStruxure for Large Data Centers
                        InfraStruxure for Medium Data Centers
                        InfraStruxure for Server Rooms
                        InfraStruxure for Small Data Centers
                        InfraStruxure for Wiring Closets
                        InfraStruxure Manager
                        InfraStruxure Type A
                        InRoom Direct Expansion
                        InRow Chilled Water
                        InRow Direct Expansion
                        InRow Pumped Refrigerant
                        Installation Services
                        Interface Cables
                        International Plug Adapters
                        Keyboard
                        KVM Switches
                        Laptop Power Adapters
                        Line-R
                        Magnum VS
                        Magnum XS
                        Magnum XS Rectifier
                        Maintenance Bypass Panels
                        Management Platform Integration
                        Matrix Battery Systems
                        Matrix-UPS
                        Matrix-UPS Accessories
                        Metered Rack PDU
                        Metered-by-Outlet Rack PDU
                        MGE Accessories
                        MGE Alpes
                        MGE Battery Systems
                        MGE Comet
                        MGE EPS
                        MGE EPS 6000
                        MGE EPS 7000
                        MGE EPS 8000
                        MGE Galaxy
                        MGE Galaxy 300
                        MGE Galaxy 3000
                        MGE Galaxy 3500
                        MGE Galaxy 4000
                        MGE Galaxy 5000
                        MGE Galaxy 5500
                        MGE Galaxy 6000
                        MGE Galaxy 7000
                        MGE Galaxy 9000
                        MGE Galaxy PW
                        MGE Legacy
                        MGE Service Bypass
                        MGE Sinewave
                        MGE Static Transfer Switches
                        MGE UPS 4000
                        Microsol Estabilizadores
                        Microsol Modules Isoladores
                        Mobile Notebook Stands
                        Modular Components
                        Modular Power Accessories
                        Modular Power Distribution
                        Monitor
                        Mounting Hardware
                        Mouse
                        MRC1800
                        MRE2400
                        Multimedia
                        MWF1700
                        NetBotz 200
                        NetBotz 300
                        NetBotz 400
                        NetBotz 500
                        NetBotz Access Control
                        NetBotz Accessories and Cables
                        NetBotz Central
                        NetBotz Rack Access
                        NetBotz Sensors
                        NetShelter CX
                        NetShelter EP Enclosures
                        NetShelter ES Enclosures
                        NetShelter Open Frame Rack Accessories
                        NetShelter SX
                        NetShelter VL
                        NetShelter VS Enclosures
                        NetShelter VX Enclosures
                        Network Integration Services
                        Network Patch Cables
                        NetworkAIR Accessories
                        NetworkAIR AFX
                        NetworkAIR CM
                        NetworkAIR CW
                        NetworkAIR FM
                        NetworkAIR IR
                        NetworkAIR TC
                        Notebook Security
                        On Site Service
                        Open Frame Racks
                        Operations Capacity
                        Operations Change
                        Operations Energy Cost
                        Operations Energy Efficiency
                        Operations Insight
                        Operations Mobile
                        Operations VIZOR
                        Outdoor Enclosures
                        Panelmount Environmental Monitoring
                        Parallel
                        Patch Panels
                        PC1200
                        Planning Tools and Publications
                        Portable Cooling
                        Power Cords
                        Power Distribution Units
                        Power Generation Systems
                        Power Ready Notebook Cases
                        PowerChute Business Edition
                        PowerChute Inventory Manager
                        PowerChute Network Shutdown
                        PowerChute Personal Edition
                        PowerChute plus
                        PowerManager
                        PowerShield
                        Preventive Maintenance
                        Project Management Services
                        ProtectNet
                        Rack Air Distribution
                        Rack Components
                        Rack LCD Consoles
                        Rack PDU Accessories
                        Rack-mount Transfer Switches
                        Refrigerant Distribution
                        Remote Monitoring Services
                        Replacement Batteries
                        Replacement Notebook Batteries
                        Residential Hardwire Surge Suppression
                        Retail
                        Retractable Cables
                        Room Air Distribution
                        Room Cooling Accessories
                        Router Cables
                        Row Cooling Accessories
                        SCSI
                        Security Cameras
                        Sensors
                        Serial
                        Service Bypass Panel
                        Service Plans
                        Silcon
                        Silcon Accessories
                        Silcon Battery Systems
                        SLM/FLM Series
                        SmartSlot Expansion Chassis
                        Smart-UPS
                        Smart-UPS Accessories
                        Smart-UPS Battery Systems
                        Smart-UPS DP
                        Smart-UPS On-Line
                        Smart-UPS RT
                        Smart-UPS VT
                        Software Configuration
                        Software Education
                        Software for NetBotz Appliances
                        Software Installation
                        Software Integration
                        Spare Part Kits
                        Specialty Enclosures
                        Start-Up Service
                        Stationary Power Distribution Units
                        Step-Down Transformer
                        StruxureWare Central
                        StruxureWare Operations Suite
                        SurgeArrest Essential
                        SurgeArrest Home/Office
                        SurgeArrest Notebook
                        SurgeArrest Performance
                        Switch Boxes
                        Switched Rack PDU
                        Symmetra
                        Symmetra Accessories
                        Symmetra Battery Systems
                        Symmetra MW
                        Symmetra MW Accessories
                        Symmetra Power Module
                        Symmetra PX
                        Symmetra PX Accessories
                        Sync and Charge Cables
                        Thermal Containment
                        Thick and Thin Ethernet
                        Token Ring
                        Toploading Cases
                        Traditional Cases
                        Training Services
                        Transceivers
                        Transportation
                        Travel Mice
                        TSP Accessories
                        TSP Battery
                        TSP/Generator
                        TSP/Total System Power
                        Tune-UPS for Symmetra
                        Uniflair Chilled Water
                        Universal Mobile Device Batteries
                        Universal Notebook Batteries
                        Universal Notebook Power Adapter
                        Universal Power Accessories
                        Universal Power Adapters
                        UPS Network Hub Card
                        UPS Network Management Cards
                        USB Adapters & Converters
                        USB Cables
                        USB Charging Cables
                        USB Hubs
                        Wall-mount Transfer Switches
                        Wheeled Cases
                        Wireless
                        Wizards and Configurators
                        WS200