coupl b/mouth rigid pvc 63mm

Conduit Coupling, Bell Mouth, Rigid, PVC, 63mm

Catalogue Number: 288/63C
coupl b/mouth rigid pvc 63mm
Colour: Electric Orange
Colour: Per UOM Std.
  • Electric Orange 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 288
Material
PVC (polyvinyl chloride)
Product destination
diameter: 63-63 mm tube
Standards
AS/NZS 2053
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What is the plate to cover the hole from a 149 flush box

Use PDL 683/683C + 2 x PDL 650VH

What is the length of the bell mouth 288/150


 The length is 290mm long.
please see following website for catalogue information as well as Technical specifications
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/150

What is the length of conduit bell mouth 288/50?

The length of conduit bell mouth 288/50 is 100mm.
For further information please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/50
User-added image

What is the part number for a lock nut to match 263/63?

The part number for a lock nut to match is a 260/63

For more information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=260/63

User-added image

What are some major differences between M-flex, E-flex, S-Flex and Field Drives?

Issue:
What are some major differences between M-flex, E-flex, S-Flex and Field Drives?

Product Line:
EFlex, MFlex and Field Irrigation

Environment:
All models

Cause:
None

Resolution:
E-Flex AC drives are packaged, adjustable speed drive solutions for commercial and industrial pump and fan applications.  It offers a full range of E-Flex drives to meet specific indoor and outdoor applications
Type 1 enclosure for indoor, non-dusty environments
Type 12K enclosure for indoor, dusty/wet environments
Type 3R enclosure for outdoor, rain or shine environments
Available Ratings
1 - 100 HP variable torque 460 VAC, three-phase input
1 - 50 HP variable torque 208/230 VAC, three-phase input (10° to 50°C ambient temperatures)
 
The S-Flex 212 enclosed drive provides the right features for HVAC pump fan applications.
Available in a NEMA Type 1 enclosure only.
Available Ratings
460 Vac Three Phase / 1 - 100 HP
208/230 Vac Three Phase / 1 - 40 HP
 
The M-Flex™ enclosed drive featuring either the Altivar® 61 or Altivar 71 drives within a Type 1 general purpose or Type 12/12K drip/dust proof enclosure in integrated or barriered designs.  M-Flex enclosed drive controllers are low voltage products available in the following ratings:
Altivar® 71 power converter
1 to 450 hp, 460 V
1 to 40 hp, 208/230 V
Variable torque (Light duty, 110% current limit)
Altivar 61 power converter
1 to 500 hp, 460 V
1 to 50 hp, 208/230 V
 
The Field Drive package is a sealed Type 3R enclosure package that completely isolates all the critical internal electronic components from the outdoor elements. 
Applications
Oil & Gas
Plumbing
Irrigation
Constant torque (Heavy duty, 150% current limit)
Altivar® 71 power converter
1 to 600 hp, 460 V
1 to 100 hp, 230 V
Variable torque (Standard duty, 110% current limit)
Altivar 61 power converter
1 to 700 hp, 460 V
1 to 125 hp, 230 V Available Ratings
1 to 600 hp, 460 V 
 
 

Can the Altivar ATV312 drives do single phase 110 VAC input?

Issue:
Can the Altivar ATV312 drives do single phase 110 VAC input?

Product Line:
ATV312 Drives

Environment:
All serial numbers for ATV312 Drives

Cause:
N/A

Resolution:
No it cannot. The drive can only do 208/230 VAC single-phase on the single phase input rated drives that have the M2 suffix..

S765RDPS (ION7650 Remote Display) 24 Volt Power Supply Documentation

Issue: 
User would like documentation, including drawings, of the 24VDC (PN: STEP-PS/ 1AC/24DC/0.75 - 2868635) power supply that is included with the M765RDPS

Product Line:
ION 7650 Remote Display 

Environment:
DC Power Supplies

Cause:
The 24VDC power supply included with the S765RDPS is a third party device that is manufactured by Phoenix Contact. 

Resolution:
Please see the attached file for documentation on the TEP-PS/ 1AC/24DC/0.75 - 2868635 24VDC power supply. The Document is a user guide that includes specifications as well as drawings of the device. 



 

I need a wiring diagram for the outdoor receiver heaters.

Issue:
Wiring diagram for the outdoor receiver heaters.
Product line:
Condensers
Environment:
Data Center Cooling
Cause:
 
Resolution:

The heater per the unit submittal package is field wired.  A junction box is typically placed at the receiver and the heater whip is pulled into this box where a small terminal bock is placed.  From the junction box a conduit whip can be connected to carry the wire to its final termination.  If the unit is 208/230 the incoming power can be split and the heater can be wired direct with fuses to protect the condenser if the heater should ever short out.  If the condenser voltage is 460/480v, a transformer is required (field supplied) this can be mounted externally under the control box and wired accordingly.

Are line reactors required for ATV61/ ATV71 series drives?

Issue:
Are line reactors required for ATV61/ATV71 series drives?

Product Line:
Altivar 61 , Altivar 71

Environment:
All models, All serial numbers.

Cause:
Product characteristics unclear.

Resolution:

Our 208/230 and 400/480V rated Altivar 61/71 drives do not require line reactors.  However, depending on the voltage and power quality of the incoming power, a line reactor or other power conditioning device may be necessary in a given installation.  Line reactors are used to filter and clean noisy power being fed into the drive.  They also can lower the incoming voltage a few percentage points if your incoming voltage is running a little high so they are used on a case by case basis, as needed.

The ATV61/71 drives 100HP and below have an internal DC choke which handles a lot of the filtering and power conditioning.  Drives rated 125HP and above have an external DC choke that ships separately and must be field installed.  There is an option to use a 5% line reactor instead of this DC choke so in this case, a 5% line reactor would be mandatory on those drives 125HP and above if the customer decided to not use the DC choke. Either the DC choke or the 5% line reactor must be used, but not both.

Altivar 61/71 drives rated at 575/690V 125HP and above require a 5% line reactor also, it must be used on these drives.