coupl b/mouth rigid pvc 50mm

Conduit Coupling, Bell Mouth, Rigid, PVC, 50mm

Catalogue Number: 288/50C
coupl b/mouth rigid pvc 50mm
Retail
N/A
RRP (Inc. GST)
Colour Electric Orange (EO)
  • Electric Orange 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Series 288
Material
PVC (polyvinyl chloride)
Product destination
diameter: 50-50 mm tube
Standards
AS/NZS 2053
Package 1 Weight
0.001 kg
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

What is the length of conduit bell mouth 288/50?

The length of conduit bell mouth 288/50 is 100mm.
For further information please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/50
User-added image

What is the length of the bell mouth 288/150


 The length is 290mm long.
please see following website for catalogue information as well as Technical specifications
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/150

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

What is the part number for a 50mm female and 50mm male bush?

The part number for a 50mm female and 50mm male bush is - 281/50 & 281F50
For further information , visit link below:-
www.clipsal.com/Trade/search-results?q=281/50
https://www.clipsal.com/Trade/search-results?q=281F50
User-added image

 

Symmetra PX 250/500 Battery to Power Module Ratio

Issue:
Symmetra PX 250/500 Battery to Power Module Ratio

Product line:
Symmetra PX 250/500

Environment:
All Product models, all serial numbers

Cause:
Required battery to power module ratio for a Symmetra PX 250/500

Resolution:

Ratio between numbers of battery shelves and power modules (PM)

Maximum recommended discharge level on the batteries used for Symmetra PX 250/500 is 3CA, where CA means the current (Amps) by which the battery is charged or discharged divided by its Amp-hour (Ah) rating.  The 250kW runtime ratio is 10 PMs to 16 battery shelves resulting in a ratio of 1.6 battery shelf per 1 PM. Need to always round up the number of shelves

Results if ratio is not maintained

In some situations, the Power Modules will attempt to draw power from the batteries and if the ratio is not observed, you will potentially clear fuses in the battery modules and (less likely, but it happened before) burn traces on the battery backplane boards due to the DC inrush current.

 

 

Symmetra PX 250/500: What happens when EPO is activated?

Issue:
Symmetra PX 250/500; What does the EPO (Emergency Power Off) trip
 
Product line:
Symmetra PX 250/500
 
Environment:
All serial numbers
 
Cause:
What occurs when the EPO on a Symmetra PX 250/500 button is engaged?
 
Resolution:
When the EPO is activated, UPS output breaker Q2 and the battery breakers are tripped. The Power Modules (inverter) and if in Static Bypass operation will the UPS turn off

Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

Issue:
Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

Product line:
Symmetra PX 250/500

Environment:
All Product models, all serial numbers

Cause:
Time not updating on UPS when changed on NMC

Resolution:
Making changes on the NMC web interface will also make changes on the ups, but the NMC must first be configured for Read/Write in the user configuration settings on the UPS.  Once this is configured making changes on the NMC will update the display on UPS.

When changing NMC configuration to update Time using NTP, you need to pay attention to the update Interval.  It can be set from 1 to 8760 hours(1 year).  Make sure this is configured as needed.  If time is not immediately updating, click the UPDATE Now box and click apply.  You may need to refresh screen on UPS a couple times to see the change.


 

How do I change User Password settings on Symmetra PX 250/500

Issue:
How to edit User Password settings via system display

Product line:
Symmetra PX 250-500

Environment:
All Product models, all serial numbers

Cause:
How do I change User Password settings on Symmetra PX 250-500

Resolution:
Begin at the home screen of the UPS



Press the wrench key at the lower left of the screen
Select Configuration, then select User configuration



Enter the User password (apc by default)



Select Password settings
Change the password and select apply



The following video demonstrates how the manage user password settings on the Symmetra PX 250/500 Data Center 3 Phase UPS.

Video: How to Start your Symmetra PX 250/500 UPS

Issue:
How to Start your Symmetra PX 250/500 UPS
 
Product line:
Symmetra PX 250/500
 
Environment:
All Product models, all serial numbers

Resolution:
Begin by applying power to the UPS by Closing the Q1 Breaker (Located in System I/O Cabinet)



Once the display is completely powered up and the Home screen is displayed, press the wrench icon in the lower left of the screen



Then select the operation button
Select System Startup



Follow the on screen prompts for starting up the UPS.  As each option is performed it will highlight the next step.


Some options are automated and will be done for you.

The following video demonstrates this procedure:
 

Network Management Card Compatibility with the Symmetra PX 250/500kVA UPS

Issue:

Network Management Card Compatibility with the Symmetra PX 250/500kVA UPS
 

Product Line:
  • Facility & Data Center 3 Phase UPS
    • Symmetra PX 250/500
 
  • UPS Network Management Card 2
    • AP9635/35CH

Environment:
  • All installation scenarios

Cause:

The AP9635/AP9635CH Network Management Card 2 (NMC2) is restricted for use with the Symmetra PX 250/500 UPS and other select UPS models. Additionally, before upgrading the firmware for the Management Card when installed in a, you must make sure that the firmware upgrade is compatible with the firmware level that is running on the UPS system (its MIM, PM, etc) . For example, as described in the chart below, a Management Card running v5.0.0 firmware cannot support a UPS with system firmware 4.1.x.x unless the Management Card is upgraded to the SYPX APP v5.0.1 firmware. To obtain the firmware upgrade files for the Management Card, you must contact Technical Support.


Alternatively, the UPS System firmware can be updated to support a Management Card with newer firmware.

Note: The UPS system firmware upgrade can only be performed by a Field Service Engineer.


Resolution:

Review the chart below to make sure the Management Card is running firmware that is compatible with the UPS. To view the UPS System firmware and NMC APP firmware versions from the UPS touchscreen display, press the Firmware Overview button in the System Information menu. The APP firmware version of the Management Card is also displayed in its Web interface, under the Administration->General->About menu.

 

Compatible Symmetra PX 250/500 UPS and Network Management Card firmware releases
 

UPS Release

Network Management Card Firmware APP/Version

 3.x.2

SYPX/5.0.0

4.0.4

SYPX/5.0.1 

4.11.5 

SYPX/5.0.2 or 5.1.0 

4.21.6

SYPX/5.1.2 or 5.1.3

4.24.8

SYPX/5.1.5

4.25.9 SYPX/5.1.6
4.27.10 SYPX/5.1.6 or 6.0.8
4.29.11 SYPX/5.1.6 or 6.0.8
4.36.12 SYPX/6.4.6
4.37.12 SYPX/6.5.0

 

Material Safety Data Sheets (MSDS) for Symmetra PX2 and PX 250-500kw UPS

Issue:
MSDS information for various battery manufacturers utilized in Symmetra PX2 and PX 250/500 UPS systems

Product:
Symmetra PX2, Symmetra 250-500

Environment:
All models/ All serial numbers


Resolution:
The rules regarding MSDSs changed in 2016 and it’s no longer sufficient just to post a link to the battery MSDS that we use.  When the rules changed, we began authoring Safety Data Sheets (new name for MSDSs) that would meet the new regulations.  These newly authored Safety Data Sheets (SDS) are located at the following web page.  

https://www.apc.com/us/en/who-we-are/sustainability/battery-safety/battery-compliance.jsp

You’ll note changes –
Safety Data Sheets are region specific.  There is a NAM format and an EU format.  

The intent is to direct all customers to this location when they have SDS or MSDS questions.

 

Video: How do I Change Language & Regional settings on my Symmetra PX 250-500 UPS?

Issue:
How to Change Language, date format & temperature unit settings on the APC Symmetra™ PX 250/500 UPS.
 
Product line:
Symmetra PX 250-500
 
Environment:
All Product models, all serial numbers
 
Cause:
The display may be accidentally changed to an unwanted language.

Resolution:

 

Begin at the home screen of the UPS.  



Press the wrench key at the lower left of the screen.
Select Language settings



The following screen will have the available list of languages. Select you desired language.



Press the Finish to lock in change.