coupl b/mouth rigid pvc 150mm

Conduit Coupling, Bell Mouth, Rigid, PVC, 150mm

Catalogue Number: 288/150C
coupl b/mouth rigid pvc 150mm
Colour: Electric Orange
Colour: Per UOM Std.
  • Electric Orange 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 288
Material
PVC (polyvinyl chloride)
Product destination
diameter: 150-150 mm tube
Standards
AS/NZS 2053
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What is the length of the bell mouth 288/150


 The length is 290mm long.
please see following website for catalogue information as well as Technical specifications
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/150

What is the length of conduit bell mouth 288/50?

The length of conduit bell mouth 288/50 is 100mm.
For further information please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/50
User-added image

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.