bellmouth rigid pvc 100mm

Conduit Coupling, Bell Mouth, Rigid, PVC, 100mm

Catalogue Number: 288/100
bellmouth rigid pvc 100mm
Retail
$192.54
RRP (Inc. GST)
Colour Electric Orange (EO)
  • Electric Orange 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Series 288
Material
PVC (polyvinyl chloride)
Product destination
diameter: 100-100 mm tube
Standards
AS/NZS 2053
Package 1 Weight
0.001 kg
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

What is the length of the bell mouth 288/150


 The length is 290mm long.
please see following website for catalogue information as well as Technical specifications
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/150

What is the length of conduit bell mouth 288/50?

The length of conduit bell mouth 288/50 is 100mm.
For further information please visit
https://www.clipsal.com/Trade/Products/ProductDetail?catno=288/50
User-added image

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

Are there Certificates of Conformity for the 247P100 and 262P100?

No. Unfortunately, there are not.

What are some major differences between M-flex, E-flex, S-Flex and Field Drives?

Issue:
What are some major differences between M-flex, E-flex, S-Flex and Field Drives?

Product Line:
EFlex, MFlex and Field Irrigation

Environment:
All models

Cause:
None

Resolution:
E-Flex AC drives are packaged, adjustable speed drive solutions for commercial and industrial pump and fan applications.  It offers a full range of E-Flex drives to meet specific indoor and outdoor applications
Type 1 enclosure for indoor, non-dusty environments
Type 12K enclosure for indoor, dusty/wet environments
Type 3R enclosure for outdoor, rain or shine environments
Available Ratings
1 - 100 HP variable torque 460 VAC, three-phase input
1 - 50 HP variable torque 208/230 VAC, three-phase input (10° to 50°C ambient temperatures)
 
The S-Flex 212 enclosed drive provides the right features for HVAC pump fan applications.
Available in a NEMA Type 1 enclosure only.
Available Ratings
460 Vac Three Phase / 1 - 100 HP
208/230 Vac Three Phase / 1 - 40 HP
 
The M-Flex™ enclosed drive featuring either the Altivar® 61 or Altivar 71 drives within a Type 1 general purpose or Type 12/12K drip/dust proof enclosure in integrated or barriered designs.  M-Flex enclosed drive controllers are low voltage products available in the following ratings:
Altivar® 71 power converter
1 to 450 hp, 460 V
1 to 40 hp, 208/230 V
Variable torque (Light duty, 110% current limit)
Altivar 61 power converter
1 to 500 hp, 460 V
1 to 50 hp, 208/230 V
 
The Field Drive package is a sealed Type 3R enclosure package that completely isolates all the critical internal electronic components from the outdoor elements. 
Applications
Oil & Gas
Plumbing
Irrigation
Constant torque (Heavy duty, 150% current limit)
Altivar® 71 power converter
1 to 600 hp, 460 V
1 to 100 hp, 230 V
Variable torque (Standard duty, 110% current limit)
Altivar 61 power converter
1 to 700 hp, 460 V
1 to 125 hp, 230 V Available Ratings
1 to 600 hp, 460 V 
 
 

Can the Altivar ATV312 drives do single phase 110 VAC input?

Issue:
Can the Altivar ATV312 drives do single phase 110 VAC input?

Product Line:
ATV312 Drives

Environment:
All serial numbers for ATV312 Drives

Cause:
N/A

Resolution:
No it cannot. The drive can only do 208/230 VAC single-phase on the single phase input rated drives that have the M2 suffix..

Symmetra PX 250/500 Battery to Power Module Ratio

Issue:
Symmetra PX 250/500 Battery to Power Module Ratio

Product line:
Symmetra PX 250/500

Environment:
All Product models, all serial numbers

Cause:
Required battery to power module ratio for a Symmetra PX 250/500

Resolution:

Ratio between numbers of battery shelves and power modules (PM)

Maximum recommended discharge level on the batteries used for Symmetra PX 250/500 is 3CA, where CA means the current (Amps) by which the battery is charged or discharged divided by its Amp-hour (Ah) rating.  The 250kW runtime ratio is 10 PMs to 16 battery shelves resulting in a ratio of 1.6 battery shelf per 1 PM. Need to always round up the number of shelves

Results if ratio is not maintained

In some situations, the Power Modules will attempt to draw power from the batteries and if the ratio is not observed, you will potentially clear fuses in the battery modules and (less likely, but it happened before) burn traces on the battery backplane boards due to the DC inrush current.

 

 

Symmetra PX 250/500: What happens when EPO is activated?

Issue:
Symmetra PX 250/500; What does the EPO (Emergency Power Off) trip
 
Product line:
Symmetra PX 250/500
 
Environment:
All serial numbers
 
Cause:
What occurs when the EPO on a Symmetra PX 250/500 button is engaged?
 
Resolution:
When the EPO is activated, UPS output breaker Q2 and the battery breakers are tripped. The Power Modules (inverter) and if in Static Bypass operation will the UPS turn off

What's the difference between ATS22..S6U and ATS22...S6 Softstart models?

Issue:
What's the difference between an ATS22..S6U and  ATS22..S6 soft start models?

Product Line:
Altistart 22 ATS22

Environment:
All models, All series

Cause: 
Altistart has difference voltage suffix S6U and S6.  

Resolution:
The ATS22..S6 model requires 220vac control power and has 24vdc logic inputs.





The ATS22..S6U model requires 110vac control power and has 110vac logic inputs.


Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

Issue:
Changing Symmetra PX 250/500 System Time from NMC – Configuring NTP server

Product line:
Symmetra PX 250/500

Environment:
All Product models, all serial numbers

Cause:
Time not updating on UPS when changed on NMC

Resolution:
Making changes on the NMC web interface will also make changes on the ups, but the NMC must first be configured for Read/Write in the user configuration settings on the UPS.  Once this is configured making changes on the NMC will update the display on UPS.

When changing NMC configuration to update Time using NTP, you need to pay attention to the update Interval.  It can be set from 1 to 8760 hours(1 year).  Make sure this is configured as needed.  If time is not immediately updating, click the UPDATE Now box and click apply.  You may need to refresh screen on UPS a couple times to see the change.


 

How do I change User Password settings on Symmetra PX 250/500

Issue:
How to edit User Password settings via system display

Product line:
Symmetra PX 250-500

Environment:
All Product models, all serial numbers

Cause:
How do I change User Password settings on Symmetra PX 250-500

Resolution:
Begin at the home screen of the UPS



Press the wrench key at the lower left of the screen
Select Configuration, then select User configuration



Enter the User password (apc by default)



Select Password settings
Change the password and select apply



The following video demonstrates how the manage user password settings on the Symmetra PX 250/500 Data Center 3 Phase UPS.

Video: How to Start your Symmetra PX 250/500 UPS

Issue:
How to Start your Symmetra PX 250/500 UPS
 
Product line:
Symmetra PX 250/500
 
Environment:
All Product models, all serial numbers

Resolution:
Begin by applying power to the UPS by Closing the Q1 Breaker (Located in System I/O Cabinet)



Once the display is completely powered up and the Home screen is displayed, press the wrench icon in the lower left of the screen



Then select the operation button
Select System Startup



Follow the on screen prompts for starting up the UPS.  As each option is performed it will highlight the next step.


Some options are automated and will be done for you.

The following video demonstrates this procedure:
 
Show More