coupling hft plain/scr 20mm

Coupling, HFT, 20mm, Plain to Screwed

Catalogue Number: 258HF20
coupling hft plain/scr 20mm
Retail
$40.84
RRP (Inc. GST)
Colour Black (BK)
  • Black 1 PCE

Specifications

hide show
Product brand
Clipsal
Connector type
thread connector
Product destination
diameter: 20-20 mm tube
Standards
AS/NZS 2053
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
5 g
Package 1 Height
24 mm
Package 1 width
24 mm
Package 1 Length
34 mm
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Environmental Disclosure
ENVPEP100802EN

Frequently Asked Questions

hide show

What is the VA rating of a 9001KM transformer light module?

Issue:
What is the VA rating of a 9001KM transformer light module?

Product Line:
Harmony Pushbuttons

Environment:
All Products

Cause:
Product Features

Resolution:
9001 KM2 110-120 volt 25-30 hertz      2.2 VA
9001 KM1 110-120 volt 50-60 hertz      2.4 VA
9001 KM3 208-220 volt 50-60 hertz      2.5 VA
9001 KM4 220-240 volt 25-30 hertz      2.2 VA
9001 KM7 220-240 volt 50-60 hertz      2.0 VA
9001 KM8 277 volt 50-60 hertz             2.4 VA
9001 KM5 380-480 volt 50-60 hertz      2.8 VA
9001 KM6 550-600 volt 50-60 hertz      2.5 VA

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.