Weatherprotected Boxes and Enclosures, Box Surround for Finished Surround

Grey | Weatherprotected Boxes and Enclosures, Box Surround for Finished Surround

Weatherprotected Boxes and Enclosures, Box Surround for Finished Surround

Item Number: 255Z-GY

Retail
N/A
RRP (Inc. GST)
Colour Grey (GY)
  • Grey 1 PCE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Physical

Depth

6 mm

Length

149 mm

Width

111 mm

EU RoHS Directive

Under investigation

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Material

Material

PVC (polyvinyl chloride)

Others

Package 1 Weight

0.001 kg

Package 1 Height

10 mm

Package 1 width

111 mm

Package 1 Length

149 mm
Show all specifications

Frequently Asked Questions

hide show

What is part number for lid to suit 255?

Part number is actually 255FLAP -TR

What is the IP rating of the 255?

The IP rating of the 255 is IP53.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=255

Weatherprotected Boxes and Enclosures, Weather protective box with clear lid and locking provision.

What is the part number for a replacement flap for the 255?

The part number for a replacement flap for the 255 is - 255FLAP

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=255FLAP

What is the Pot Level of the C-Bus 5753L if the Potentiometer A set to fully clockwise?

It reads 2550 lux, if the Pot A at the fully clockwise position.

Is it possible to scale ATV320 analog input to have precisely 25.0Hz when AI1=5V?

Issue:
Customer needs to scale analog input to have 5V equal 25Hz speed. 

Product line:
Altivar 320, ATV320 Altivar Machine

Environment:
All models

Cause:
n/a

Resolution:
By default, the analog input on the ATV320 follows Low speed to High speed in Inputs/Outputs CFG > Reference Template = Standard

To have the drive follow 25Hz with 5V analog signal, set LSP to 0.0 and HSP to 50Hz. Otherwise 5V cannot refer to 25Hz.
If necessary, adjust AI1 min value, AI1 max value, AI1 range, AI1 Interim points X or Y. 

See the extracted pages from the ATV320 programming manual attached

What are the basic troubleshooting steps for the Smart-UPS SMX1500RM2U ?


Issue:

What are the basic troubleshooting steps for the Smart-UPS SMX1500RM2U ?

Product Line:

Smart-UPS

Environment:

SMX1500RM2U - All Serial Numbers

Cause:

During normal operation, you may find your UPS not functioning as expected. This may be due to a malfunction, configuration issue, or the install environment.
This document will assist you with basic troubleshooting steps.

Resolution:

 
Problem Possible Cause Solution
     
The UPS will not turn on or there is no output The unit has not been turned on. Press the ON button once to turn on the UPS. Please note that the LCD screen may be lit even though the UPS is OFF.
  The UPS is not connected to utility power. Be sure that the power cable is securely connected to the unit and to the utility power supply.
  The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker. 
  The unit shows very low or no input utility voltage Check the utility power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.
  The battery connector plug is not securely connected. Be sure that all battery connections are secure.
  There is an internal UPS fault. Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately
     
The UPS is operating on battery, while connected to utility power The input circuit breaker has tripped. Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.
  There is very high, very low, or distorted input line voltage. Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.
     
UPS is beeping The UPS is in normal operation. None. The UPS is protecting the connected equipment.
     
UPS does not provide expected backup time The UPS battery is weak due to a recent outage or is near the end of its service life. Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.
  The UPS is overloaded.  Check the UPS load display. Unplug unnecessary equipment, such as printers
     
Display interface LEDs flash sequentially The UPS has been shut down remotely through software or an optional accessory card. None. The UPS will restart automatically when utility power is restored.
     
Fault LED illuminates Possible Internal Fault Contact APC Support for further assistance. Take care to note the exact fault message on the LCD Display
     
All LEDs are illuminated and the UPS is plugged into a wall outlet The UPS has shut down and the battery has discharged from an extended outage. None. The UPS will return to normal operation when the power is restored and the battery has a sufficient charge.
     
The Replace Battery LED is illuminated The battery has a weak charge Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the battery
  The replacement battery is not properly connected. Be sure that the battery connector is securely connected.
     
The UPS displays a site wiring fault message Wiring faults detected include missing ground, hot-neutral, polarity reversal, and overloaded neutral circuit. If the UPS indicates a site wiring fault, have a qualified electrician inspect the building wiring. (Applicable for 120 V units only.)