tee conduit pvc insp 20mm

Inspection Tee, 20mm, PVC

Catalogue Number: 246HF20
tee conduit pvc insp 20mm
Colour: Black
Colour: Per UOM Std.
  • Black 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 246
Material
PVC (polyvinyl chloride)
Diameter
inner: 20 mm
Length
  • 55 mm
  • 92 mm
    • EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • Technical Leaflet

      • Installation Instruction

      • Specifications

      • Certificates (MSDS)

      Frequently Asked Questions

      hide show

      What is the part number for a conduit bending spring

      266MD20 - for 20mm medium duty conduit.
      266MD25 - for 25mm medium duty conduit.

      What is the part number for inspection tee to suit 9020HF20-BK?

      246HF20-BK is the part number for inspection tee to suit 9020HF20-BK.

      Do you have a 32mm inspection Tee conduit fitting with out the inspection hole?

      No, unfortunately we only do the 246/32, 32mm, Inspection Tee with the inspection hole.

      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=246/32

      How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

      Issue:
      Implementing a hardwire stepdown transformer in a 208v or 240v environment


      Product Line:

      Smart-UPS / Symmetra

      Environment:

      APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

      Cause:

      Unbalanced UPS outputs require a stepdown transformer to power 120v loads


      Resolution:

      This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

      The wiring block outputs are as follows:


      For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

      The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



       Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.