elbow cond pvc solid 16mm

SoLid Fittings - PVC, SoLid Elbows, 16mm

Catalogue Number: 245/16
elbow cond pvc solid 16mm
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 245
Material
PVC (polyvinyl chloride)
Diameter
16 mm
Operating angle
90 °
Length
50 mm
Inner radius
18 mm
Standards
AS/NZS 2053
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

How many 261/16 Clipsal saddles are there in a carton?

There are 50 16mm saddles in a carton.

Note: This information can be found in your Clipsal pocketbook right next to the part code.

Is there an extension ring to suit the 343?

Yes, there is the 93ER and also the 249/12 or 249/25.

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

Are the 265 series insulated boxes (suitable for numerous junctions and terminations) IP rated?

The 265 series is a range of IP56 rated insulated boxes suitable for numerous junctions and terminations. Each box is supplied with a 3mm sealing gasket.

This applies to the 265/1, 265/3, 265/4, 265/5, 265/7 and 265/7D.

What is the part code for a RCBO 4P 32Amp C-curve

 Combine a mccb 25016 32Amp C-curve with a 23382 rccb = RCBO

Is the junction box 265/1 UV rated?

No it doesn't have a rating as such, however it is UV resistant.

What screws would suit a 265/1-GY.

The part number for the screws would be 265SCREW.

Does the 252/32/2A come in orange?

No, the 252/32/2A only comes in grey.

Do you do the 265/1 in a orange colour?

Yes, we can offer the 265/1 in electric orange. The part number is 265/1-EO.
Some of the key features are:
  • Surface mount
  • Dimension: 77 mm Length x 77 mm Width x 54 mm Height
  • 63.5 mm screw centres C, 63.5 mm screw centres D
  • Weatherproof, full cover plate
For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=265/1


 

What is the replacement for the 24541?

Part number "24541" was a 3 Poles 20 Amps D Curve 6 KA C60N Circuit Breaker which has been discontinued.

In the new series we have D curve Circuit Breakers available in 10 KA i.e. iC60H series.

The part number for the iC60H 3 Poles 20 Amps D Curve 10 KA Circuit Breaker is "A9F55320"

https://www.schneider-electric.com.au/en/search/A9F55320



 

NetBotz History Export date is seen as a Linux Time Stamp

Issue:

NetBotz History Export date is seen as a Linux Time Stamp.

Product Line:

NetBotz

Environment:

NetBotz History Export.

Cause:

NetBotz is based on the Linux operating system and as such much of it's data uses a Linux Time Stamp The Exported data may look something like this:
"Sensor Pod (integrated)";"Temperature";"1465097276057";"30.00"

Resolution:

It is unlikely this will be changed in a future revision so if it is necessary to view this as a date, the information can always be imported into a spread sheet application such as Microsoft Excel.

I can translate 1465097276057 on the epochtime.com page but in Microsoft Excel, the number does not translate easily. I must delete the last 3 digits just to be able to use the suggested Excel formulae:
=(((C2/60)/60)/24)+DATE(1970,1,1)<br />
or
=C2/(60*60*24)+"1/1/1970"

You can also cut off the rest of the numbers by using a formula like this:
=(((LEFT(C2,10)/60)/60)/24)+DATE(1970,1,1)
When formatted properly using a time format, the result should look like this:
6/5/16 3:27 AM
 

Where can I find the characteristics of the LC1D contactors?

You will find all the characteristics of LC1Dxx contactors on the Tesys web page:
 
The section Downloads has documents ( Catalogues, Brochures, Catalogue pages, Tech publications, Certificates, etc...) that you can download free

See the following documents in the online catalogue: 24505; 24506 and 24533
(Use the search bar on the top right hand side of the web site to search for these particular documents)

Wire recommendation to use with EM4200 series meters

Issue
Wire recommendation to use with EM4200 series meters

Product Line
EM4200 series meters
EM4235
EM4236

Environment
Meter wiring 

Resolution
The EM4200's recommended wire size for I/O, Communications, and CT is 24-16 AWG (0.2 to 1.5 mm2) shielded wire, solid or stranded.

Can the ATV28 drive accept 4-20 mA analog input?

Issue:   Can the ATV28 drive accept 4-20 mA analog input?
 
Product Line:   ATV28
 
Environment:  All
 
Cause:   N/A
 
Resolution:   Yes. It can be used as a summed reference, speed reference or PI regulator feedback. It can also be configured as a 0-20mA current loop. The input is located at terminal AIC.


 

Where are I/O modules installed on a PM8000 meter

Issue:
User wants to know where to install I/O modules on a PM8000 meter.
 
Product Line:
PM8000 meters
METSEPM89M2600 (Digital I/O module)
METSEPM89M0024 (Analog I/O module)

Environment:
I/O modules installation

Resolution:
*Warning:  Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.

There are 2 methods to install I/O modules on a PM8000 meter. The method to choose will depend on your PM8000 model number

If meter is PM8240 (Panel mount meter with integrated display)
I/O module to be installed on the back of the meter. 
1) remove connector's cover on back of the meter
2) Make sure that connectors on meter and I/O module align with each other. Attach I/O module to the back of the meter.
3) secure the I/O module in its location by a 5mm (5/16 in) screw
4) reattach connector's cover that was removed in step 1 to the back of I/O module
See illustration below:


If meter is either PM8243 or PM8244 (DIN rail mount meter)
I/O module to be installed on the side of the meter:
1) remove connector's cover from side of the meter
2) Hang the I/O module on your DIN rail
3) Secure I/O module to the DIN rail using Mounting clip.
4) Move I/O module using the DIN rail and attach it to the PM8000 meter> You should hear a click.
5) Secure the I/O module to the meter using a 5mm (5/16 in) screw.
6) reattach connector's cover that was removed in step 1 to the back of I/O module
See illustration below:



 

What are the pinouts for current inputs on the AMI0810 when using the FTW308 cable with pigtail leads ?

 

 

 
  : Here are the pin assignments for current inputs I0 - I7 when using the FTW308 cable and the BMXAMI0810 .
 
      
    Current input 0  +                   pins 1/3 blue/white & white/blue are jumped together
    Current input 0  common        pin 2 white/orange
 
    Current input 1  +                   pins 4/6  green/ white & white/green are jumped together
    Current input 1  common        pin 5 orange/white
 
    Current input 2  +                   pins 7/9 white/brown  & brown/white are jumped together
    Current input 2  common        pin 8   white/gray 
 
    Current input 3  +                   pins 10/12 blue/red & red/blue are jumped together
    Current input 3  common        pin 11 gray/white
 
    Current input 4  +                   pins 15 /17 red/ orange & orange/ red are jumped together
    Current input 4  common        pin 16 red/green
 
    Current input 5  +                   pins 18/20 brown/red & red/brown are jumped together
    Current input 5  common        pin 19 green/red  
 
   Current input 6  +                 pins 21/23 red/gray & gray/ red are jumped together
   Current input 6  common        pin 22 black/blue
 
   Current input 7  +                   pins 24/26 black/orange & orange/ black are jumped together
   Current input 7  common        pin 25 blue/black 


R-6-30-17

Legacy KB System (APS) Data: RESL211859 V1.0, Originally authored by DaSo on 06/21/2013, Last Edited by DaSo on 06/21/2013
Related ranges: Modicon M340