Can a 9013FS ``water switch`` be used on an air compressor load ?

Yes ....as long as the switch meets the pressure range requirements . The switches designed for water pressure, as a group, will have a lower range of pressures. Note that a pressure relief valve, which is often desired for compressor loads , is not available with 9013FS products


CTA-ID : 2023020

What is the part number for an inspection elbow to suit 9020HF20-BK?

The part number for an inspection elbow to suit the 9020HF20-BK is 244HF20-BK.
 

What is the part number for inspection tee to suit 9020HF20-BK?

246HF20-BK is the part number for inspection tee to suit 9020HF20-BK.

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.