Junction and Adaptable Boxes PVC, Round Junction Boxes - 16mm Entries, 4 Way

Grey | Junction and Adaptable Boxes PVC, Round Junction Boxes - 16mm Entries, 4 Way

Junction and Adaptable Boxes PVC, Round Junction Boxes - 16mm Entries, 4 Way

Item Number: 240/16/4-GY

Retail
$22.50
RRP (Inc. GST)
Colour Grey (GY)
  • Grey 1 PCE
  • Electric Orange 1 PCE

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Series 240

Product brand

Clipsal

Physical

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Material

Material

PVC (polyvinyl chloride)

Others

Shape

round

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

79 g

Package 1 Height

42 mm

Package 1 width

95 mm

Package 1 Length

95 mm
Show all specifications

Frequently Asked Questions

hide show

What is the rating of transformer in the PDL shaver sockets

Rating are 240/115V 20va

What is the part number for a plug to suit the 240/25?

The part number for a plug to suit the 240/25/3 is a 220/25.
 

Is a 30USM-WE a normal switch rocker mechanism

30USM-WE = Universal switch mechanism 20/16AX - compared to the 10A only 30M-WE
(see attached 30USM Brochure)

What is the temperature range for the SWLUB grease (Dow Corning BG20 grease) ?

Issue:
Application

Product Line:
Safety Switch

Cause:
Application

Resolution:
Temperature range is -50 F to 360 F, but for Safety switches, the normal ambient operating temperature range is -30 degree C (-22 degree F) to +40 degree C (+104 degree F) per NEMA Standards Publication KS-1,``Enclosed and Miscellaneous Distribution Equipment Switches``.


CTA-ID : 2021634

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

How can input phase loss fault be disabled with the Altivar 58 drive?

Issue:
Altivar 58 input phase loss fault disable.

Product Line:
Altivar 58

Environment:
All

Cause:
N/A

Resolution:
Go to menu 6 (FLt - fault menu)
Set the IPL  parameter (Input Phase Loss) to no.
This will allow the drive to continue running without PHF fault if there is a loss of input phase voltage. This does not disable other faults in the drive.
See keypad programming manual for additional details.