convert cond adapt 25mm 1in.

SoLid Fittings - PVC, Converting Adaptors, 25mm Screwed to 1 inch Plain

Catalogue Number: 236/25S1
convert cond adapt 25mm 1in.
Colour: Grey
Colour: Per UOM Std.
  • Grey 1 PCE
Added to cart

Specifications

hide show
Product brand
Clipsal
Range of product
Series 236
Material
PVC (polyvinyl chloride)
Connector type
thread connector
Length
40-40 mm
Standards
AS/NZS 2053
Sustainable offer status
Green Premium product
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure
ENVPEP100802EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • Installation Instruction

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Video: What causes an StF fault on an Altistart 22 Soft Starter?

Issue:
Troubleshooting StF Fault on Altistart 22

Product Line:
ATS22 Soft Starter

Environment:
All models

Cause:
The StF fault means the starter has exceeded the maximum start time setting, tLS, in the SEt menu.  

Resolution:
tLS needs to be set higher than the ACC time.  
For example:  If ACC (ramp up time) is 10 seconds, then set the tLS max starting time to 20 seconds.

If ILt current limit is too low, the motor may not reach full speed within tLS limit.
Mechanical problems on the load may prevent the motor from reaching full speed within tLS limit.
See page 51 in the ATS22 User Manual:



The following video is a guide for troubleshooting the StF fault code, indicating a longer than expected start-up time, on the Altistart ATS22 soft starter by adjusting the tLS (maximum start time in seconds) and ACC (ramp up time) parameters under the SET menu. tLS must be set higher then the ACC time value.