COMB BUSBAR PH AND N 12POLES
PRODIS COMB BUSBAR 1 P+N
PRODIS COMB BUSBAR 1 P+N
COMB BUSBAR PH AND N 12POLES
PRODIS COMB BUSBAR 1 P+N
PRODIS COMB BUSBAR 1 P+N

Acti 9 Comb Busbar, 1L+N, 9 mm Pitch, 12 Modules, 80A

Catalogue Number: 21501
COMB BUSBAR PH AND N 12POLES
PRODIS COMB BUSBAR 1 P+N
PRODIS COMB BUSBAR 1 P+N
COMB BUSBAR PH AND N 12POLES
PRODIS COMB BUSBAR 1 P+N
PRODIS COMB BUSBAR 1 P+N
Retail
$105.81
RRP (Inc. GST)

Specifications

hide show
Range
Acti 9
Product or component type
comb busbar
Accessory / separate part category
connection accessory
Lines description
1L + N
Total number of 18 mm modules
12
Number of ways
12 ways N + 1 L
Poles configuration for 1 way
  • 1 x 1P + N
  • 1 x 2P
    • Connection pitch
      9 mm
      Connector type
      tooth
      Distance between way
      18 mm
      Marking
      N L
      Insulation
      insulated
      Device presentation
      cuttable
      [Ie] rated operational current
      80 A at 40 °C
      [Ue] rated operational voltage
      230 V AC Ph/N
      [Ui] rated insulation voltage
      440 V AC conforming to IEC 61439-1
      [Uimp] rated impulse withstand voltage
      6 kV
      Mounting mode
      horizontal
      Mounting location
      top on tunnel type terminals
      9 mm pitches
      24
      Width
      216 mm
      Range compatibility
    • Acti 9 iDPN
    • Acti 9 iDPN Vigi
    • Acti 9 IDc
    • Multi 9 N40 Vigi N40 Vigi
    • Multi 9 N40
      • Standards
      • EN/IEC 60439-1
      • IEC 60947-7
        • Fire resistance
          960 °C ( 30 s ) conforming to IEC 60695-2-1
          Pollution degree
          3 conforming to IEC 60947-7
          Unit Type of Package 1
          PCE
          Number of Units in Package 1
          1
          Package 1 Weight
          82 g
          Package 1 Height
          3 cm
          Package 1 width
          3.2 cm
          Package 1 Length
          26.9 cm
          Unit Type of Package 2
          BB1
          Number of Units in Package 2
          12
          Package 2 Weight
          1.036 kg
          Package 2 Height
          16 cm
          Package 2 width
          6 cm
          Package 2 Length
          31 cm
          Unit Type of Package 3
          P12
          Number of Units in Package 3
          1020
          Package 3 Weight
          96.49 kg
          Package 3 Height
          80 cm
          Package 3 width
          80 cm
          Package 3 Length
          120 cm
          REACh free of SVHC
          Yes
          EU RoHS Directive
          Compliant
          Toxic heavy metal free
          Yes
          Mercury free
          Yes
          RoHS exemption information
          Yes
          China RoHS Regulation
           Pro-active China RoHS declaration (out of China RoHS legal scope)
          WEEE
          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
          Warranty
          18 months

          Frequently Asked Questions

          hide show

          What is the part number for the bus bar to suit the 4RCBE216/30S slim line RCBO ?

          The combination Busbars to suit the slim line RCBO's are the  21501 (12 pole) or 21503 (24 pole)
          For more information on this product range please visit the Clipsal web site on the link provided.
          https://www.clipsal.com/Trade/search-results?q=4rcbe210/30s
           

          What would be the replacement part for the 4BB5/26.

           21501 for a 12 module and a 21503 for the 24 module. these are a Schneider part which is equivalent to the 4bb5/26
          Clipsal’s range of busbars are available in 63A - 250A versions and have been specifically designed to make installations quicker and easier.
          Please see following link for further information and complete range.
          https://www.clipsal.com/Trade/Products/ProductDetail?catno=4BB5/26

          What comb busbar can you use with the A9D73620?

          You can use the 21501 Comb Busbar PH and N 12 Poles.

          what are the dimensions for a T100, T100F, T150, T150LF, T150F

           140 x 94 x 81mm ( L x W x D)

          What is the dimensions of a T150, T150LF, T150F

           140 x 94 x 81mm (L x W x D)

          What is the separator for a 15092

           The separator part code is 27001

          Is a C60N 25801 ok to operate on 24V DC

          Yes it is

          Can the 15013 isolators handle a manual operation under load

           Yes they can

          What is the replacement for 25018 MCB?

          The replacement for 25018 MCB is A9F54450
          A9F54450
          Acti9 iC60H 4P 50A C Miniature Circuit breaker
          For more information see:
          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F54450

          Do we meet IEC 61511 with motor starters?

          Then IEC 61511 is safety for process industry and it is above the machine safety. However the IEC 615011-2 shows the guideline how to implement IEC 61508 into process industry.
          Simple motor starters do not meet directly iEC 61508, because there must be additional components and so IEC61508 can be aplicable to whole circuitry.
          FOr example IEC61508 schematic diagrams can be found in Preventa manuals.
          Or ANy safty manual for ATVs shows the levels in reference to IEC61508

          Are the SCADAPack RTU products comply with IEC 61508 standard?

          IEC 61508 is about functional safety of a system, or SIL (safety integrity level) compliance. 
          Our SCADAPack’s are not designed with 61508 and as such do not comply with it. 
          None of SCADAPack's are designated as functional safety equipment.

           

          Why is my Conext CL showing an alarm code: 2102 & 2018 & 2101(DC AC Comm Err / AC Inter-Comm Err / DC Inter-Comm Err Service Alarm)

          Issue:  
          Customer is calling to confirm alarm codes: 2102 & 2018 & 2101 (DC AC Comm Err / AC Inter-Comm Err / DC Inter-Comm Err Service Alarm)

          Product Line: 
          Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

          Environment:  
          On site troubleshooting

          Cause:
          Communication error between processors
          Firmware issue
          Internal circuit issue

          Resolution: 
          Reset by turning off both DC & AC connections
          Upgrade firmware to lastest version
          If problem persist, replace inverter
          Show More