Cable Management Pressed Metal Conduit Fittings, Earth Clip 25mm

Cable Management Pressed Metal Conduit Fittings, Earth Clip 25mm

Cable Management Pressed Metal Conduit Fittings, Earth Clip 25mm

Item Number: 208MBS

Retail
$15.30
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Sustainable offer status

Green Premium product

Physical

REACh Regulation

Free of Substances of Very High Concern above the threshold

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure

ENVPEP110719EN

Others

Package 1 Weight

0.032 kg
Show all specifications

Frequently Asked Questions

hide show

Customer is requesting the utility interactive current for XWs models

Max Sell Amps

Default - 18Amps (865-1010 XW4024) 36Amps (865-1010-01 XW4024)
                27Amps (865-1000 XW6048) 20Amps (865-1005 XW4548) 48Amps (865-1000-01 XW6048)

Range - 0-18Amps (865-1010 XW4024) 0-36Amps (865-1010-01 XW4024)
                0-27Amps (865-1000 XW6048) 0-20Amps (865-1005 XW4548) 0-48Amps (865-1000-01)

What is the accuracy of the Premium PLC CPU real time clock.

Real time clock accuracy:

Accuracy of the real time clock is one second (%SW50) +/- 200ms.

Resolution of the real time clock is one second (%SW50) +/- 200ms,because 200ms is the refresh rate of the RTC.
 
Accuracy error:
 
The accuracy error of the quartz oscillator is:
 
1. At 0 and 70°C : -101/20 ppm, error in second/day is -8.7/1.7, in minute/year is -53/11.
 
2. At 25°C: -20/20 ppm, error in second/day is -1.7/1.7, in minute/year is -11/11.

The ACSC100 manual lists an In-Rush current of 56amps for 200ms. How does this not trip the 20amp breaker?

Issue:
The ACSC100 manual lists an In-Rush current of 56amps for 200ms.  How does this not trip the 20amp breaker?
Product line:
ACSC100
Environment:
InRow Cooling
Cause:
 
Resolution:
The reason that the circuit breaker does not trip is expressed in the time/current curve that are unique properties of circuit breakers or fuses. For example a typical Square ""D"" ""NQ"" breaker rated at 20 amps might trip after 300 seconds of a 20 amp load, but will pass considerably more than 56 amps at 200ms of time.

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V suppl...

Goals and Symptoms

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V supply from the ATV. Controller operating sequence is, during initialisation, send a 200mS run signal to the ATV and read the motor encorder for motion. For ATV28 case, there is no run signal at all. Thus the controller detect a encorder feedback error. Could this be due to the ATV28 emit higher level of noise on the 24V supply, thus interfere with the controller operation? Can ATV58 or ATV11 improve the situation? The ATV28 works well when tested independly.

Facts and Changes

Replace ATV16U41M2 by ATV28HU41M2. Spray painting maching,

Causes and Fixes

Try to connect the Ov of ATV28 control terminals to the ground. We are very interesting by your problem, is it possible to make some oscillograms of the noise.

You can also try to use an external 24v supply


Legacy KB System (APS) Data: RESL156482 V3.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 28

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V suppl...

Goals and Symptoms

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V supply from the ATV. Controller operating sequence is, during initialisation, send a 200mS run signal to the ATV and read the motor encorder for motion. For ATV28 case, there is no run signal at all. Thus the controller detect a encorder feedback error. Could this be due to the ATV28 emit higher level of noise on the 24V supply, thus interfere with the controller operation? Can ATV58 or ATV11 improve the situation? The ATV28 works well when tested independly.

Facts and Changes

Replace ATV16U41M2 by ATV28HU41M2. Spray painting maching,

Causes and Fixes

Try to connect the Ov of ATV28 control terminals to the ground. We are very interesting by your problem, is it possible to make some oscillograms of the noise.

You can also try to use an external 24v supply. Try to use a core on the encoder cable.


Legacy KB System (APS) Data: RESL156617 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 28

What are pulse characteristics of the Extended Range Powerlogic Energy Meter?

Issue
Need the pulse characteristics of the Energy Meter (EME) to determine the compatibility of the input device.

Product Line
Powerlogic Energy Meter

Environment
Application requiring submetering device that produce and energy pulse (kWh) 

Resolution
*Warning:  Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.


The pulse output is a contact closure only - power must be supplied externally in the range of 5-24 V ac/dc, with a maximum load of 100mA.

The pulse output provides a contact closure for 200ms at each pulse time. Be sure the controller will accept this signal as an input. See marked location of the pulse out terminal in figure below.




 