clip earth brass 16mm

Cable Management Pressed Metal Conduit Fittings, Earth Clip BRASS 16mm

Catalogue Number: 206MBS
clip earth brass 16mm
Retail
$12.49
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal
Package 1 Weight
0.024 kg
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

Part number for the 256MB memory card used with SoMachine controllers

Issue:
Part number for the 256MB SD card used with SoMachine controller

Product Line:
M221, M241, M251

Resolution:
The part# for a 256MB SD card is TMASD1. 
We don't offer a bigger one. 
It works for the M221, M241 and M251 controllers.

Where can I find the electrical ratings and certification for the NSYTRR24M?

Issue:
Customer needs to confirm the electrical ratings and certification on the NSYTRR24M for his application.

Product Line:
Linergy TR Screw terminal blocks.

Environment:
Linergy TR NSYTRR24M, NSYTRR24MBL  

Cause:
Customers application was calling for a UL rating for 20Amps @600V

Resolution:
The UL rating for this terminal bloc is 20amps @ 600V, found on page 54 in the LINERGY CATALOG 9080CT1301

What are the dimensions of the 4CC9-WE?

The dimensions of the 4CC9 are 178mm Wide, 206mm High and 104mm Deep.

Customer is requesting the utility interactive current for XWs models

Max Sell Amps

Default - 18Amps (865-1010 XW4024) 36Amps (865-1010-01 XW4024)
                27Amps (865-1000 XW6048) 20Amps (865-1005 XW4548) 48Amps (865-1000-01 XW6048)

Range - 0-18Amps (865-1010 XW4024) 0-36Amps (865-1010-01 XW4024)
                0-27Amps (865-1000 XW6048) 0-20Amps (865-1005 XW4548) 0-48Amps (865-1000-01)

What are the dimensions for part number LC1F330U7?

The dimensions for part number LC1F330U7 are:
206mm (H) x 213mm (W) x 219mm (D)

 

What are the C-BUS Relay part numbers?

You have several options for relays, Catalogue numbers and information below.

L5504RVF, L5504RVFP** - 4 Channel voltage free relay - 10amps per channel
L5508RVF, L5508RVFP** - 8 Channel voltage free relay - 10amps per channel
L5512RVF, L5512RVFP** - 12 Channel voltage free relay - 10amps per channel

L5504RVF20, L5504RVF20P** - 4 Channel voltage free relay - 20amps per channel

L5508RELVP - 8 Channel Extra Low Voltage Relay

5101R - Single and Two Channel 250v AC 10amp relay
5102RVF - Single and Two Channel 250v AC 10amp Voltage Free Relay

** Any part number that has a 'P' after the part number for Din Rail mount units does NOT include a C-Bus 200ma Power Supply.

What is the accuracy of the Premium PLC CPU real time clock.

Real time clock accuracy:

Accuracy of the real time clock is one second (%SW50) +/- 200ms.

Resolution of the real time clock is one second (%SW50) +/- 200ms,because 200ms is the refresh rate of the RTC.
 
Accuracy error:
 
The accuracy error of the quartz oscillator is:
 
1. At 0 and 70°C : -101/20 ppm, error in second/day is -8.7/1.7, in minute/year is -53/11.
 
2. At 25°C: -20/20 ppm, error in second/day is -1.7/1.7, in minute/year is -11/11.

The ACSC100 manual lists an In-Rush current of 56amps for 200ms. How does this not trip the 20amp breaker?

Issue:
The ACSC100 manual lists an In-Rush current of 56amps for 200ms.  How does this not trip the 20amp breaker?
Product line:
ACSC100
Environment:
InRow Cooling
Cause:
 
Resolution:
The reason that the circuit breaker does not trip is expressed in the time/current curve that are unique properties of circuit breakers or fuses. For example a typical Square ""D"" ""NQ"" breaker rated at 20 amps might trip after 300 seconds of a 20 amp load, but will pass considerably more than 56 amps at 200ms of time.

Are the Masterpact NW and NT shunt trip and shunt close coils continuous-duty rated?

Issue:
Does the Masterpact NW shunt trip and shunt close have a coil clearing switch?

Product Line:
Masterpact NT and NW breakers

Resolution:
Yes, the coils themselves are continuous duty rated and do not use a coil clearing switch. However in actual use, a maintained signal should not be used on the shunt close coil (XF). Any opening order will open the breaker so a standing close order is not necessary (see Anti-Pump Feature in the Masterpact catalog 0613CT0001). Instead, use a signal of at least 200ms on the shunt close coil (XF), then remove the signal.

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V suppl...

Goals and Symptoms

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V supply from the ATV. Controller operating sequence is, during initialisation, send a 200mS run signal to the ATV and read the motor encorder for motion. For ATV28 case, there is no run signal at all. Thus the controller detect a encorder feedback error. Could this be due to the ATV28 emit higher level of noise on the 24V supply, thus interfere with the controller operation? Can ATV58 or ATV11 improve the situation? The ATV28 works well when tested independly.

Facts and Changes

Replace ATV16U41M2 by ATV28HU41M2. Spray painting maching,

Causes and Fixes

Try to connect the Ov of ATV28 control terminals to the ground. We are very interesting by your problem, is it possible to make some oscillograms of the noise.

You can also try to use an external 24v supply


Legacy KB System (APS) Data: RESL156482 V3.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 28

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V suppl...

Goals and Symptoms

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V supply from the ATV. Controller operating sequence is, during initialisation, send a 200mS run signal to the ATV and read the motor encorder for motion. For ATV28 case, there is no run signal at all. Thus the controller detect a encorder feedback error. Could this be due to the ATV28 emit higher level of noise on the 24V supply, thus interfere with the controller operation? Can ATV58 or ATV11 improve the situation? The ATV28 works well when tested independly.

Facts and Changes

Replace ATV16U41M2 by ATV28HU41M2. Spray painting maching,

Causes and Fixes

Try to connect the Ov of ATV28 control terminals to the ground. We are very interesting by your problem, is it possible to make some oscillograms of the noise.

You can also try to use an external 24v supply. Try to use a core on the encoder cable.


Legacy KB System (APS) Data: RESL156617 V1.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 28

What are pulse characteristics of the Extended Range Powerlogic Energy Meter?

Issue
Need the pulse characteristics of the Energy Meter (EME) to determine the compatibility of the input device.

Product Line
Powerlogic Energy Meter

Environment
Application requiring submetering device that produce and energy pulse (kWh) 

Resolution
*Warning:  Installation and maintenance of this device should only be performed by qualified, competent personnel that have appropriate training and experience with high voltage and current devices. Failure to follow the instructions / warnings in the Meter Installation Guide can result in permanent damage to the meter, severe injury or death.


The pulse output is a contact closure only - power must be supplied externally in the range of 5-24 V ac/dc, with a maximum load of 100mA.

The pulse output provides a contact closure for 200ms at each pulse time. Be sure the controller will accept this signal as an input. See marked location of the pulse out terminal in figure below.




 
Show More