Cable Management Pressed Metal Conduit Fittings, Earth Clip 12mm Brass

Cable Management Pressed Metal Conduit Fittings, Earth Clip 12mm Brass

Cable Management Pressed Metal Conduit Fittings, Earth Clip 12mm Brass

Item Number: 205MBS

Retail
$12.20
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Physical

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Others

Package 1 Weight

21 g

Package 1 Height

10 mm

Package 1 width

30 mm

Package 1 Length

50 mm
Show all specifications

Frequently Asked Questions

hide show

What is the cut out diameter of the 5600ICBT65 blue tooth speaker?

The cut out diameter is 205mm

Customer is requesting the utility interactive current for XWs models

Max Sell Amps

Default - 18Amps (865-1010 XW4024) 36Amps (865-1010-01 XW4024)
                27Amps (865-1000 XW6048) 20Amps (865-1005 XW4548) 48Amps (865-1000-01 XW6048)

Range - 0-18Amps (865-1010 XW4024) 0-36Amps (865-1010-01 XW4024)
                0-27Amps (865-1000 XW6048) 0-20Amps (865-1005 XW4548) 0-48Amps (865-1000-01)

What are the dimensions of the INS400 single handle transfer switch 31150?

205mm x 395mm x 155mm (H x W x D) excluding the handle.
Overall depth with standard handle is 213mm.
See attached.

What is the accuracy of the Premium PLC CPU real time clock.

Real time clock accuracy:

Accuracy of the real time clock is one second (%SW50) +/- 200ms.

Resolution of the real time clock is one second (%SW50) +/- 200ms,because 200ms is the refresh rate of the RTC.
 
Accuracy error:
 
The accuracy error of the quartz oscillator is:
 
1. At 0 and 70°C : -101/20 ppm, error in second/day is -8.7/1.7, in minute/year is -53/11.
 
2. At 25°C: -20/20 ppm, error in second/day is -1.7/1.7, in minute/year is -11/11.

The ACSC100 manual lists an In-Rush current of 56amps for 200ms. How does this not trip the 20amp breaker?

Issue:
The ACSC100 manual lists an In-Rush current of 56amps for 200ms.  How does this not trip the 20amp breaker?
Product line:
ACSC100
Environment:
InRow Cooling
Cause:
 
Resolution:
The reason that the circuit breaker does not trip is expressed in the time/current curve that are unique properties of circuit breakers or fuses. For example a typical Square ""D"" ""NQ"" breaker rated at 20 amps might trip after 300 seconds of a 20 amp load, but will pass considerably more than 56 amps at 200ms of time.

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V suppl...

Goals and Symptoms

Machine worked well with ATV16. But when replaced by ATV28, no run signal received from controller. Controller is open collector output with 24V supply from the ATV. Controller operating sequence is, during initialisation, send a 200mS run signal to the ATV and read the motor encorder for motion. For ATV28 case, there is no run signal at all. Thus the controller detect a encorder feedback error. Could this be due to the ATV28 emit higher level of noise on the 24V supply, thus interfere with the controller operation? Can ATV58 or ATV11 improve the situation? The ATV28 works well when tested independly.

Facts and Changes

Replace ATV16U41M2 by ATV28HU41M2. Spray painting maching,

Causes and Fixes

Try to connect the Ov of ATV28 control terminals to the ground. We are very interesting by your problem, is it possible to make some oscillograms of the noise.

You can also try to use an external 24v supply


Legacy KB System (APS) Data: RESL156482 V3.0, Originally authored by on , Last Edited by on
Related ranges: Altivar 28
Show More