switch cooker d/pole 32a

Electric Range Switches, 415V 32A Double Pole

Catalogue Number: 2031D32
switch cooker d/pole 32a
Colour: White Electric
Colour: Per UOM Std.
  • Cream 1 PCE
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Series 2000
Product brand
Clipsal
Device presentation
basic element with full cover plate
Switch function
2-pole
Actuator
rocker
Number of rocker
1
Number of poles
2
Device mounting
flush
Fixing mode
by screws
Local signalling
without
[Ue] rated operational voltage
415 V AC
Rated current
32 A
Marking
without marking
Standards
AS/NZS 3133
Sustainable offer status
Green Premium product
REACh Regulation
Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Technical Leaflet

  • Installation Instruction

  • Product Environmental

  • Operating Manuals

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Is the C2031D32 available in Slimline?

No, unfortunately the C2031D32 is not available in Slimline.

For further information please visit https://www.clipsal.com/Trade

Is the C2031D32 available in horizontal

 No - only available in vertical only

Are C2031D32 cooker switches available in Chrome shadow ?

No , as you can buy either Stainless Steel or Brushed aluminium covers
For more information regarding the C2031D32 series please visit the Clipsal web site on the link provided https://www.clipsal.com/Trade/search-results?q=c2031d32
 
   
   

What is the part number for a cover plate to suit the C2031D32C ?

The part nuber is C2031/45C-WE

What is part number for cover to suit C2031D32?

The part number for cover to suit is a C2031/45C.
For information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2031/45CUser-added image

Are Saturn cooker switches 4061D32 and 4061/45 marked cooker?

4061D32 and 4061/45 cooker switches are supplied with a spare labeled mechanism cap that is marked COOKER to replace the unmarked cap. Picture attached.
Thus the customer has the choice to use  4061D32 and 4061/45 either marked COOKER or unmarked.


 

ATV61 Lonworks user manual to access the SNVTs for commanding the drive over the network.

Issue:
ATV61 Lonworks user manual to access the SNVTs for commanding the drive over the network.

Product Line:
Altivar 61 with the lonworks card VW3A3312

Environment:
All

Cause:
Needs a copy of the user manual for accessing the SNVT points.

Resolution:
atv61_LONWORKS_EN_V2


CTA-ID : 2039332

What is the mounting height of a PowerPact H Frame 3-pole breaker

Product Line:
Circuit Breakers
PowerPact H
I Line

Environment:
Electrical Distribution Equipment

Resolution:
It takes 4.5`` of mounting height.
 

Do the Saturn 4061/45 and 4061D32 Switches have the word 'Cooker' labelled on the switch?

Yes, Due to a change in the Wiring Regulations these now have to be lablled with 'Cooker' on the switch.
 

Will the 60R32 fit into a 4062VH plate ?

No , The 60R32 series mechs are only designed to go into the 4025XA and 4025XUA plate styles. If Mechs over 32 amp are required for Saturn plates then you will need either 4031VH plate and 30M35 series mechs or the dedicated cooker plates 4061D32 or 4061/45 series

Do you have a 32A switch that fits in a 2 gang Saturn switch plate?

No, unfortunately there isn't a 32A switch that fits in a 2 gang Saturn switch plate.
The only 32A switches in the Saturn series are the 60R32 that fits in the 4025XA and the 4061D32 cooker switch.

For further information please visit https://www.clipsal.com/Trade

Customer wants to know what is the NSYSDR200 is made of?

It is galvanized steel.


CTA-ID : 2061172

Do you make a 2031VHA like the 2032VHA?

Unfortunately, we only make a 2 gang version.

What is the white cover plate for a 2031VCS

The part code is 2000-WE surround cover plate

Does the 2031V66 come in architrave?

No it doesnt

Is there a cover available for part C2031HD32?

The part name is as follows: C2031/45C 

What is the maximum voltage for a 9001BG201?

Issue:
What is the maximum voltage for a 9001BG201?

Product Line:
Harnony Control Stations

Environment:
All products

Cause:
Product Features


Resolution:
600V


CTA-ID : 2035612

What is the difference between a LULC031 Modbus communication module and a LULC033 Modbus communication module.

The LULC031 does not provide and extra input and there are no fault registers for communication failure, both a prevelant with the new LULC033 module


CTA-ID : 2053932

What are the part numbers for early closing and late opening contacts for a 9001K, 9001SK, 9001KX, or 9001T operators?

9001KA5 is a normally closed late opening contact and a 9001KA6 is a normally open early closing contact.  These can be used together to provide overlapping contacts.


CTA-ID : 2061321

Can the Z4061D32 Cooker Switch assembly be mounted Horizontal?

Yes it can, just rotate the legend "cooker" to suit.

What coil codes are available for the U-Line motor starter Control Units?

The coil codes available for the U-Line Motor Starter control units are as follows:
24VDC is BL
24VAC is B
48-72V DC or 48V AC is ES
110-240V AC/DC is FU.
We do not have 480VAC coils available


CTA-ID : 2031577

Do you do the 2031V66 with double pole switches?

No, the 2031V66 does not have double pole mechanisms.

Some of the key features are:
  • Switches have been re-designed to provide mechanisms that can be re-orientated horizontally or vertically
  • 1 gang weatherproof switch

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2031V66

Can the grid for the 2031v66 be purchased without mechs?

No, We do not supply or encourage this as the 2031v66 has a specific gasket set up to ensure weatherproof rating and this may be compromised if tampered with therefore we only sell them assembled.

What is the mech that fits in the 2031V66 switch?

Unfortunately we dont do the mech as a spare part it is essentually a 30 mech with a rubber seal between the contacts ant the dolly and we dont do that mech as a spare part.

What is the temperature range for the SWLUB grease (Dow Corning BG20 grease) ?

Issue:
Application

Product Line:
Safety Switch

Cause:
Application

Resolution:
Temperature range is -50 F to 360 F, but for Safety switches, the normal ambient operating temperature range is -30 degree C (-22 degree F) to +40 degree C (+104 degree F) per NEMA Standards Publication KS-1,``Enclosed and Miscellaneous Distribution Equipment Switches``.


CTA-ID : 2021634

Will the LA4DC1U work with the new CAD32BD relay?

Issue:
Will the LA4DC1U work on the CAd32BD relay

Product Line:
IEC relays and accessories

Environment:
Products sold and used in the United States

Cause:
Identifying product compatibility

Resolution:
The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.


CTA-ID : 2031917

What is the form number to get a 9012 type G preset from the factory?

Issue:
Ordering

Product Line:
Industrial Pressure Switches

Environment:
9012G

Cause:
Preset range and differential settings

Resolution:
Add for Y1 to the catalog number and  include the pressure settings  on the markings section in Quote to Cash in order to process the order. ( ie. 9012GBW2Y1 ( 400 FALL- 435 RISE) )

CTA-ID : 2042032

 

 

Can the 5.2E, 5.3E, 6.2E and 6.3E trip units handle dielectric (hi-pot)testing or should they be removed from the breaker prior to testing. Do wehave any documentation to state the proper procedure as we do with thePower & Harmonic trip units?

Bulletin 48940-313-01 page 85 states that Micrologic trip units can be left connected, even if equipped with voltage measurement (ENVT option).


CTA-ID : 2061833

ATS01: What happens if a new start command is given soon after a stop command when using ramp down function?

If a new start command is given before the motor stops, the motor will start again immediately. It does not wait for the motor to stop.  For the ATS01, any run order is taken into account to start the motor as soon as it is given to the soft starter.



CTA-ID : 2061902

Can an XVBC21 be mounted directly to a panel?

Issue:
Can an XVBC21 be mounted directly to a panel?                 

Product Line:
Harmony Tower Lights

Environment:
All Products

Cause:
Product Features

Resolution:
Yes. You have remove terminal strip and drill or knock out 2 holes in base as indicated in the instructions. These are partly done from factory. This will allow the unit to be direct mounted. Gasket is provided with base unit for this purpose.


CTA-ID : 2001138

Is the ATV28 HU29N4U rated NEMA 1?

Issue:   Is the ATV28 drive rated NEMA 1?
 
Product Line:   ATV28
 
Environment:  All
 
Cause:   N/A
 
Resolution:   No. It is an open style drive that requires an enclosure.


 

Does the ATV28 have Profibus communication capability?

Issue:  Does the ATV28 have Profibus communication capability?
 
Product Line:  ATV28
 
Environment:  All
 
Cause:  N/A
 
Resolution:  No.


 

What is the conduit entrance kit for the ATV31HU11M3X or ATV31HU15M3X?

Issue:   What is the conduit entrance kit for the ATV31HU11M3X or ATV31HU15M3X?
 
Product Line:   ATv31
 
Environment:  ATV31Hu11M3X, ATV31HU15M3X
 
Cause:   N1 conduit kit selection
 
Resolution:   
VW3A31813

 

What is the watts loss for the ATV31HU22M2?

Issue:   What is the watts loss for the ATV31HU22M2?
 
Product Line:   ATV31
 
Environment:  ATV31HU22M2
 
Cause:   Watts dissipated
 
Resolution:   
The total dissipated power at rated load is 123 watts.

 

Are handle ties available for four single pole QO/QOB breakers?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
No, handle tie are not available for (4) single pole breakers.

Does the zelio software SR2SFT01 work with Vista?

Issue:
Needs to know if SR2SFT01 SR2 or SR3 Zelio Software work with Vista.

Product Line: 
Zelio Logic

Environment:
Smart Relays

Resolution:
The SR2, SR3 software will work with Vista.

What is the data bulletin with self-certified DC ratings for the QO at 125Vdc?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The bulletin to reference for self certification and other DC applications is  0601DB0401.

Do you offer a 60 Series Saturn mechanism in double pole?

No unfortunately this part is unavailable. We do have the cooker style plate but that isn't a removable mechanism. The part number is 4061D32.

Can part number 30M35 be used in 2031V66?

No. Unfortunately, part number 30M35 CANNOT be used in 2031V66.

 

How do you activate the ground fault protection feature on a Masterpact or Powerpact breaker with a 6.0 A Trip unit?

Issue:
How do you activate the ground fault protection feature on a Masterpact or Powerpact breaker with a 6.0 A Trip unit?

Product Line:
Micrologic, Powerpact, Masterpact

Environment:
Products sold in North America

Cause:
Need to remove ground fault from breaker with a LSIG trip functions.

Resolution:
The ground fault cannot be deactivated. The trip unit needs to be replaced to an unit without LSIG trip functions like S143A (5.0A).

CTA-ID : 2030439

What are the part numbers of the IGBT's for the ATV66 drives?

Issue:
What are the part numbers of the IGBT's for the ATV66 drives?

Product Line:
All ATV66 drives

Environment:
IGBT's

Cause:
n/a

Resolution:
See the attached attachment

What is the replacement keyed operator for the XB3D cam switch?

Issue:
What is the replacement keyed operator for the XB3D cam switch?

Product Line:
Harmony Pushbuttons

Environment:
Obsolete Products

Cause:
Legacy Replacement

Resolution:
Replacement operators only are not available for the XB3D cam switches.


 

Are there lugs available for Masterpact NW breakers?

Issue:
Lugs for Masterpact NW

Product Line:
Air Circuit Breakers

Environment:
Masterpact Circuit Breakers

Resolution:
There are no lug pads for the NW breaker. Cable cannot be directly attached to the breaker.
 

What is the difference between the GV2MC01 and the GV2MC02 enclosures?

Product Line:
 
GV Manual Motor Starters and Protectors
 
Resolution:
The GV2MC01 has an IP41 rating ( similar to Nema Type 1 ), whereas the GV2MC02 has an IP55 rating (similar to the Nema Type 12 ).

 

How many LUFN auxiliary blocks may be installed on a U-line starter?

Issue:
What is the quantity of LUFN auxiliary blocks, that  may be installed on a U-line starter?

Product Line:
PTCTR - Contactors

Environment:
Tesys U-line

Resolution:
Just one LUFN** or function module per starter.


 

What is the sensor multiplier value of the ARP040 rating plug used on a Micrologic Series B trip unit?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment

Resolution:
The multiplier is 0.40 (40%).
 

what is the part number of cooker mech in Zen?

Will the VW3A8106 cable kit for the Power Suite work on the ATV11 drive?

Issue:   Will the VW3A8106 cable kit for the Power Suite work on the ATV11 drive?
 
Product Line:   ATV11
 
Environment:  All
 
Cause:   VW3A8106 compatibility 
 
Resolution:   
Yes it will. The kits that shipped after December of 2002 include the VW3A11301 adapter. If the kit was shipped before that date then you must order the optional adapter.


 

Can additional contact blocks be stacked on 9001K35H2 joystick?

Issue:
How many contact block can be added on the 9001K35H2 joystick?

Product Line:
Push buttons and operator Interface

Environment:
9001, 9001K35, KA1, Joystick

Cause:
Additional contact blocks are needed for application.

Answer: 
A maximum of 2 more contact blocks can be added. If (2) 9001KA1`s are added, there will be (2) contacts that close in each position (excluding the OFF position).

Are the LC1D115 and LC1D150 contactors din rail mountable?

Issue: 
LC1D115 and D150 mounting

Product Line:
 Tesys D contactors

Environment:
Products sold and used in the United States
 
Cause:
Din rail mounting desired for large D line contactor
 
Resolution:
 
Yes, they use 2-35mm din rails


 