cover pvc 1g t/setter surr

Flush Surround, 1 Gang, Horizontal Mount, Standard Pattern Trendsetter

Catalogue Number: 2000T
cover pvc 1g t/setter surr
Retail
$7.15
RRP (Inc. GST)
Colour White Electric (WE)
  • White Electric 1 PCE
  • Cream 1 PCE

Specifications

hide show
Range of product
Series 2000
Product brand
Clipsal
Mounting position
horizontal
Device mounting
flush
Material
PVC (polyvinyl chloride)
Type of installation
indoor
Depth
13 mm
Length
116 mm
Width
76 mm
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
15.1 g
Package 1 Height
14 mm
Package 1 width
120 mm
Package 1 Length
77 mm
Unit Type of Package 2
BB1
Number of Units in Package 2
5
Package 2 Weight
0.25 kg
Package 2 Height
117 mm
Package 2 width
102 mm
Package 2 Length
138 mm
Unit Type of Package 3
CAR
Number of Units in Package 3
100
Package 3 Weight
2.5 kg
Package 3 Height
250 mm
Package 3 width
214 mm
Package 3 Length
338 mm
Sustainable offer status
Green Premium product
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP120506EN

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Product Environmental

Frequently Asked Questions

hide show

Is it Possible to Upgrade a 1600A NW16 Breaker to a 2000A NW20 by Changing the Sensor Plug.

No. It is not possible. As per the attached document the NW16 have sensor rating only from 800 - 1600A, So a 2000A Sensor Plug is not suitable for NW16 Breaker. So it can not be changed. 

What is the part number for an LED flood light that has 20000 Lumens output?

The part number for an LED flood light that has 20000 Lumens output is - FLH200LED

For further information , visit link below:-
User-added image
https://www.clipsal.com/Trade/search-results?q=FLH200LED
 

How do I get Modsoft to open up to full screen display while I try to run it under WIN 2000?

The command to get Modsoft to change window size is ALT+<ENTER>; however Modsoft is not supported under WIN 2000. Users may try running the application under it; however successful operation cannot be guaranteed. One of the common problems is Modsoft will not open up to full screen. Regrettably there is no means to resolve this issue other than to reinstall the software under a supported OS, such as WIN 95, WIN 98 or DOS.


Legacy KB System (APS) Data: RESL171500 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modsoft

Can you get a double power point with 2 USB ports?

No, unfortunately this part is unabaliable. However, there is a single power point with 2 USB ports avaliable. This is avaliable in two diffrent styles, 2000 Series or the Classic 2000 Series. The part numbers are (Classic 2000) C2015USB2C and (2000 Series) 2015USB2C.
Some of there key features are:
  • Twin 30USBCM USB Chargers
  • Surge, over-current and over-temperature protection
  • Cable compensation for optimised charging
  • Meets BC1.2 USB Charging Standard
  • Meets Class V Energy Efficiency in standby
  • Certified to all relevant safety and EMC requirements for Australia

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2015USB2C
                                              Or https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015USB2C

 
 
 

 

Can you get a plate larger than 6 gang in the 2000 series?

Not directly, but using the 2000/2 or 2000h2 series you can fit 2 plates under one surround.

Starting Register number in Modbus Read functions

Goals and Symptoms

When performing Modbus read commands, it is important to apply the right starting register address in the read function. Otherwise, the wrong register will be accessed from the meter, giving unexpected data for the meter parameter being read.


  • Meter is functioning as expected. The front panel values for voltages and currents are within expected ranges for the system being monitored. However, modbus read functions from a master station (e.g. a PLC) give values that do not correspond to the front panel values.

Facts and Changes

Modbus, modbus rtu, function read, modbus map, holding register, staring register, function 03, modbus read packet

Causes and Fixes

Cause
One probable cause would be that, the modbus function read command is not pointing to the right registers. The modbus protocol requires an offset to be introduced in the starting register address when reading the slaves register.

Resolution

When reading the meter parameters, the Master must send the device a Read Holding Registers packet. This packet must specify a start register and the number of registers to read. When the function read is received, the slave responds with a packet containing the registers in the range defined in the read request.

However, consider the 3710 Modbus map, which states that according to the MODBUS protocol, in response to a request for address 4xxxx, the master reads register xxxx-1 from the slave (3710). For example, a request for register 40011 returns register 10 from the slave.

What does the above statement mean? Why is an offset required?

Holding registers, by default, are defined the 4xxxx range, the first holding register staring at 40001. The starting register in the read packet is, on the other hand, numbered from zero. Hence, the start register zero automatically points to holding register 40001, starting register one points to holding register 40002, etc. The fact that the first holding register is 40001 and not 40000 explains the offset that needs to be introduced in the starting register number.

Hence, considering the 3710 Modbus Map statement, if the Master needs to read register 40011, then the corresponding starting register that needs to be put in the read function would be 10 (0A hex) since register 40011 is the register 10 from the first holding register, 40001:
40001 > Start register 0
40002 > Start register 1
40003 > Start register 2
40004 > Start register 3
40005 > Start register 4
40006 > Start register 5
40007 > Start register 6
40008 > Start register 7
40009 > Start register 8
40010 > Start register 9
40011 > Start register 10

The Modbus Read Request Packet for a master reading 3 registers from a slave with unit ID 100 (64 Hex) and for starting register of 40011 should be:
 

Slave ID
Function
Start Register (40011)
# of Registers
CRC Checksum
64
03
00
0A
00032C3C


To summarize, when looking at a modbus map, the starting register number to be used in the read function:

Start Register = Modbus Register 40001.

 

Original article#12774

Public

All content © 1992-2007 Schneider Electric


Legacy KB System (APS) Data: RESL188799 V1.0, Originally authored by KBAdPM on 11/03/2007, Last Edited by KBAdPM on 11/03/2007
Related ranges: Modbus / JBus

Sepam EcoFit offer

Schneider Electric offers a retrofit solution for converting Sepam 2000's to the new Sepam 1000+ relays.
ECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT SEPAM 2000 Customer Presentation Rev1a.pptECOFIT SEPAM 2000 Customer Presentation Rev1a.ppt

Is Event Notification Solution 6.4 /Active Pager Module 6.4 (ENS 6.4, APM 6.4) compatible with SQL 2000?

ENS 6.4 is only supported with SQL 2005 and SQL 2008 instances.
During the install, SQL 2000 instances can be chosen, but the install will not complete if a SQL 2000 instance is selected.


Legacy KB System (APS) Data: RESL206608 V1.0, Originally authored by MaTh on 11/09/2011, Last Edited by MaTh on 11/09/2011
Related ranges: Paging Module, SMS Add-on

What is the Pin out detail for the Modbus programming cable 110 XCA 20 3000?

The pin out details of the Modbus programming cable 110 XCA 20300 is as shown in the attached.

 

Is cut out for Modena/Strato same as C2000?

Yes, same dimensions as C2000 series.

What are the placement considerations for the condenser relative to the InRow ACRD10x?

Issue:
What are the placement considerations for the condenser relative to the InRow ACRD10x?

Product line:
ACRD100, ACRD101

Environment:
Data Center Cooling

Cause:

Resolution:
The condenser should always be placed above the InRow ACRD10x unit at a distance not to exceed 200ft equivalent pipe length.

 

What version of SQL Server is used with the different versions of ION Enterprise?

ION Enterprise 3.0 MSDE 1.0 (SQL Server 7.0)
ION Enterprise 4.0 MSDE 1.0 (SQL Server 7.0)

ION Enterprise 4.5 MSDE 1.0 (SQL Server 7.0)

ION Enterprise 5.0 MSDE 2000 (SQL Server 2000)

ION Enterprise 5.5 MSDE 2000 (SQL Server 2000)

NOTE: It is possible to use ION Enterprise 5.5 Service Pack 2 with SQL Server 2005, but some modifications are required. See KB articles 12704, 12708 and 12823 for detailed information.

ION Enterprise 5.6 SQL 2005 Express (SQL Server 2005)
NOTE: ION Enterprise 5.6 will use an existing MSDE 2000 instance, but will install SQL Express on new systems if there is no pre-existing SQL Server instance.
ION Enterprise 6.0 SQL 2005 Express with Reporting Services SP3 (SQL Server 2005 SP3 with Reporting Services)
NOTES: The ION Enterprise 6.0 installer will upgrade an existing MSDE 2000 instance to SQL Server 2005 Express with Reporting Services. ION Enterprise 6.0 does not support SQL Server 2000. It also does not support SQL Server 2008

  • Original article#16492

    Public

    All content © 1992-2009 Schneider Electric


Legacy KB System (APS) Data: RESL188782 V3.0, Originally authored by KBAdPM on 11/02/2007, Last Edited by JaMc on 10/15/2009