surround 2000 ser 2 gang horiz

Flush SurRound, 2 Gang, Horizontal Mount, Curved Sided, Standard Pattern

Catalogue Number: 2000H2
surround 2000 ser 2 gang horiz
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • Cream 1 PCE
  • Dark Blue 1 PCE
  • Red 1 PCE
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Series 2000
Product brand
Clipsal
Mounting position
horizontal
Device mounting
flush
Material
plastic
Type of installation
indoor
Surface finish
brilliant
Depth
13 mm
Length
232 mm
Width
76 mm
Sustainable offer status
Green Premium product
REACh Regulation
Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP120506EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Product Environmental

  • Operating Manuals

  • Specifications

  • Certificates (MSDS)

Frequently Asked Questions

hide show

What are the dimension for the 2000H2?

The dimension for the 2000H2 are - H232mm x W 76mm x D13mm

For further information , visit link below:-
https://www.clipsal.com/Trade/search-results?q=2000H2
User-added image

Can you get a plate larger than 6 gang in the 2000 series?

Not directly, but using the 2000/2 or 2000h2 series you can fit 2 plates under one surround.

What is the mounting frame for the 4025H2

 Part code is 4000H2

What is the plaster bracket to suit the 2000/2?

The part number for the plaster bracket to suit the 2000/2 is 2155PRM/2.

Is there a wall box for a 2025H2?

The wall box for the 2025H2 is the 2157H2.

Some of the key features are:
  • 2 gang
  • 84 mm (2 sets)
  • With sliding nuts for accurate alignment of accessory
  • Precision stamped from 0.9 mm strip bright electrogalvanised, for 2000H2 series

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2157H2

 

What is the part number of Mounting bracket for a 2000/2?

The part number for a for a mounting bracket for a 2000/2 is 2154/2.

Some of the key features are:
  • Mounting brackets
  • 2 gang
  • For plaster board or hardboard mounting for wall boards up to 12 mm thick

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2154/2
 

Is Silver color on part 2000/2 same as Brushed Aluminium?

The Silver color is shinier than Brushed Aluminium and is distinctly different

for information on this part please refer to https://www.clipsal.com/Trade/Products/ProductDetail?catno=2000/2

User-added image

Is there a 4 gang GPO in the Medilec range?

No there isn't but you can put 2 x doubles in a double surround - 2000H2, making 4 GPO's in total.

What is the dissipated power watts for the GV2ME...... manual starter?

It is 2.5 watts per pole


CTA-ID : 2050062

What is the frequency of the internal buzzer used in the Magelis XBTGT 2000 to 7000 series HMI terminals?


The buzzer frequency is between 2000Hz and 2600 Hz. (2300Hz typical)


Legacy KB System (APS) Data: RESL192877 V1.0, Originally authored by MiMe on 10/01/2008, Last Edited by MiMe on 10/01/2008
Related ranges: Magelis XBT G

Do you have a 2000MF round mounting block with a diameter of 800?

Yes the part number is 2000MF800.

Can you get a 2000/2 in chrome.

This part  only comes in standard 'bakelite' colours. Please visit the below link to our website for more information and colour options.
Today, the 2000 series is clipsal’s most popular product range and its surrounds are available in a wide choice from single gang standard size versions to multigang surrounds for situations where you want to house up to four gridplates in a single surround. 2000 series flush surrounds feature a design that neatly conceals all mounting holes, a durable high gloss finish for easy cleaning and a clever clip on/clip off design that enables surrounds to be easily removed when redecorating to conceal overpainting or untidy cut marks when wallpapering.
Please see following link for more details and colour choices of multi gang range.
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2000/2

Are there any plaster clips or other accessories for 2000/3 ?

We only make wall boxes for this 2000/3
The Part number is 2157/3  or 2157/3SB1 or 2157/3SB2

Will the 2000pp fit the C2000 series?

No, unfortunately you will need to use a C2000PP paint protector.

For further information please visit www.clipsal.com/Trade/Products/ProductDetail?catno=C2000PP

What is the Cut-Out, Dimensions and/ or Template for a 4000VH2 quad surround?

Please see the below image for the Dimensions and/ or Template for a 4025H2 quad outlet.

Is there any bracket available for a 2000/4?

There is no stud bracket, you could use the 2154/4 mounting clip.

For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2154/4

What is the part number for standard din rail?

The part number for standard din rail is NSYSDR200B. It is 7.5mm deep by 2000mm long.

What is the part number for wall plate for 2000/2?

The part number for metal wall plate 2000/2  will be  2155PRM2.

 

Can the 155H2 be used with the 2025H2 series ?

No, the 155H2 mounting bracket can not be used with the 2025H2 as the mounting holes do not line up. You can use a wall clip part number 2154/4.

For further information please visit https://updates.clipsal.com/ClipsalOnline/Files/Brochures

 

What is the audible sound level (dB) of the XVAC921 and can it be adjusted? NOTE: This product is obsolete.

Issue:
What is the audible sound level  (dB) of the XVAC921 and can it be adjusted?

Product Line:
Harmony Signalling

Environment:
All products

Cause:
Product Features

Resolution:
It is 90 dB and not adjustable. NOTE:  This product is obsolete.


CTA-ID : 2004022

My meter is measuring 0A and 0kW but correctly reads the Voltage, what is the issue?

Product Line
ION Meters

Environment
Installation/Setup

Resolution
If the meter is being provided a very small current (0.005A/5mA or less) on the secondary side, the meter will read 0 for the phase current.
Since kW is dependent on the current reading this value will also be zero.

To find out what the minimum Primary starting current is you can calculate as follows:
Primary_Min_Current = 0.005 * CT_Ratio
Where CT_Ratio = CT_Primary/CT_Secondary

Example:
CT Ratio = 2000:5 (Primary:Secondary)
Starting Current = 0.005A (Secondary)

CT_Ratio = 2000/5 = 400
Primary_Min_Current > 0.005 * 400 = 2A (primary side load).

 

Is there a decorative surround for the 4025H2 quad outlet?

Yes the part number for a decorative surround for the 4025H2 quad outlet is a 4000H2.

What is the part number for a mounting block to suit 2025H2?

There is no mounting block available for the 2025H2

When using Concept, what may cause a 4000h Stop Code on my Momentum I/O Bus CPU?

The 4000h stop code may be generated by a bad I/O map, extended memory error or missing loadable. This error will also occur when a Momentum I/OBus network has a third party Interbus device on the network but undefined. The Concept ModConnect tool must be used to generate a MDC file that will define the module and allow the Concept database to insert this definition in the I/O map configuration. A common symptom of this problem is the program will download and start with no problems with an older computer that has the MDC definitions installed. When the project is moved to another computer without the modules MDC file, the project will report a 4000h error after download/ start. To eliminate this error generate a new MDC file using the Concept Modconnect tool.


How to manually set the clock in a Modicon PLC using Concept software?

Goals and Symptoms

The Time of Day clock in a Modicon PLC consist of 8 registers. The steps below explains how to manually set the clock on the Modicon PLC should you want to synchronize the PLC clock with a HMI or SCADA.

Causes and Fixes


Hardware:
Modicon 984
Quantum
Momentum
Compact

Software:
Modsoft
Proworx PLUS/NXT/32
Concept
 

1)From the Control Register 4x

  • Enter 0000h. This will stop the clock from being updated

 

2) Set the TOD registers 4x + 1 to 4x + 7 to the correct time.

 

3) From the Control Register 4x, enter 8000h (This sets bit 1, Clock value are being set).
If successful, the control Register should display 2000h,

4) From the Control Register 4x

  • Enter 4000h (This sets bit 2, Clock values are being read)
    If successful, the control Register should display 2000h

Is it Possible to Upgrade a 1600A NW16 Breaker to a 2000A NW20 by Changing the Sensor Plug.

No. It is not possible. As per the attached document the NW16 have sensor rating only from 800 - 1600A, So a 2000A Sensor Plug is not suitable for NW16 Breaker. So it can not be changed. 

Is there a have a mounting bracket for the 2000H2 avaliable?

Yes, there is a mounting bracket for the 2000H2 avaliable. The part number is 2154H2.
Some of its key features are:
  • Mounting brackets
  • 2 gang
  • For plaster board or hardboard mounting
For more information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=2154H2


 

What is the Cell switch kit for an NW breaker?

Issue:
What is the Cell switch kit for NW breaker?

Product Line:
Circuit Breakers

Environment:
Masterpact NW

Resolution:
The cell switch is number S33170. It consists of one switch, which can be used for connected, test or disconnected position.

Can I change the input power plug on my 120Vac Smart-UPS?

Issue:
Changing input plugs on Smart-UPS 2000VA or larger

Product Line:
Smart-UPS 

Environment:
Smart-UPS 2000VA or larger

Cause:
All Smart-UPS 2000VA or larger have an input plug that is not a standard 5-15 household style plug.

Resolution:
The higher capacity of these UPS models require an input plug that is either 20amp or 30 amp (depending on model) rather than the traditional 15 amp household plug you may be more familiar with. The UL listing of the UPS assumes that the UPS is using the input plug for which it was designed. Modifying the input plug may affect the UL or other regulatory compliance. Schneider Electric does not recommend modifying the input plug of your Smart-UPS UPS or attached Smart-UPS Accesories (IE: Stepdown Transformers, PDU strips, ETC) 

Note: If you decide to go against this recommendation and change the input plug of your UPS, please be aware that the functional capacity of the UPS will be limited by the input circuit.
(I E: An SMT3000 being supplied 15 amps is effectively a 1500VA UPS rather than the 3000VA that it is rated for.)

What is the part number for a surround /cover for the 2025H2?

The part number for a surround /cover for the 2025H2 is - 2000H2

 

Is there a double GPO where the outlets are a little further apart?

What is the effect of altitude on ATV312?

Product Line:
All ATV312 and ATV31

Environment:
High altitude, more than 1000m

Cause:
What is the effect of the high altitude on the drive.

Resolution:
For all ATV312, less than 1000m, no derating.
For single-phase supplie and corner grounded distribution networks, up to 2000m, derateing 1% per 100m.
For three-phase supplies, up to 3000m, derating 1% per 100m.




 

How do I setup 3-wire control with ATV28?

Issue: 
 How do I setup 3-wire control with ATV28?
 
Product Line:  
ATV28
   
Environment:  
All
 
Cause:  
N/A
 
Resolution:   
In the I-O menu, set the tCC parameter for 3C.  Then, LI1 will be set to stop. LI2 will be set to forward, and LI3 will be set to reverse.  It is possible to change the setting for LI3 if desired.

 

Is R2 relay programmable on the ATV28?

Issue:  
Is R2 relay programmable on the ATV28?
 
Product Line: 
ATV28
 
Environment:  
All
 
Cause:
 N/A
 
Resolution:  
Yes. Go to Menu 3 ( I/O) and scroll down to R2 and assign to the desired function.


 

Why is my Conext CL showing an alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 31 (AC Curr Snsr Flt Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC current sensor doesn’t measure the grid current accurately
Grid connection
Detection circuit malfunction

Resolution: 
Check AC connection on inverter

Is it possible to mount a weathershield power point on a pole ?

Weather shield enclosure will line up with the 2000MF range, screw mountings will go on an angle to the pole, opposing the enclosure and may be tricky.
Available standard as white. If diameter surface is less than 300mm you may be able to use a 56PMK.
2000MFV range has a large amount of variable for different sized diameter surfaces.
Please see following link for complete range of sizes
https://www.clipsal.com/Trade/search-results?q=2000mf
 

What would be the part number for a mounting block for a 2025H2-WE.

There is no mounting block for this part.
Suggestion would be to mount 2 449-we close together.
This is mainly designed for flush mounting on a gyproc wall hence there is no mounting block.
Please see attached link for complete gang buster range.
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2025H2

What is the part number for an LED flood light that has 20000 Lumens output?

The part number for an LED flood light that has 20000 Lumens output is - FLH200LED

For further information , visit link below:-
User-added image
https://www.clipsal.com/Trade/search-results?q=FLH200LED
 

What is the part number and function of the remote racking devices for Masterpact NT and NW?

Product Line:
Circuit Breakers
Masterpact NT and NW
Remote Racking

Environment:
Electrical Distribution Equipment

Resolution:
The Masterpact NTMPRRT and NWMPRRT Remote Racking Devices are
intended to allow remote insertion and removal of a Masterpact NT or NW
circuit breaker from its chassis, and racking between the disconnected
position and the connected position. Operation can be performed from
outside the arc flash zone as described by NFPA 70E/CSA Z462.


 

Sepam EcoFit offer

Schneider Electric offers a retrofit solution for converting Sepam 2000's to the new Sepam 1000+ relays.
ECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT S2000 Leaflet - SERED111087EN.pdfECOFIT SEPAM 2000 Customer Presentation Rev1a.pptECOFIT SEPAM 2000 Customer Presentation Rev1a.ppt

VijeoLook V2.6 : during the installation, error "1603" and then another error "Missing MSDN 2000". How to solve it ?

Goals and Symptoms

VijeoLook V2.6 : during the installation, error "1603" and then another error "Missing MSDN 2000". How to solve it ?

Causes and Fixes

During the installation of VijeoLook, if you have a problem with MSDN 2000 (error 1603), then you have to check the Status and the Startup type of those 2 Services "Server" and "Computer Browser" (Control Panel \Administrative Tools \ Services).
They must be started in automatic :
---------------------------------------------------------------------------------------
// Name // Status // Startup Type //
---------------------------------------------------------------------------------------
// Computer Browser // Started // Automatic //
// Server // Started // Automatic //


Legacy KB System (APS) Data: RESL177610 V1.0, Originally authored by on , Last Edited by on
Related ranges: Vijeo Look

Video: Enabling Sell Mode on the Xantrex XW Hybrid Solar Inverter/Charger

1) Enable Grid support in XW basic setup menu
2) Set Grid Support Voltage to 64V (32V for XW4024) and enable SELL in XW Advanced - Grid Support menu (only if firmware on the XW inverter/charger is 1.07)
3) Verify XW CHARGE CYCLE is '2Stg/NoFloat' in XW Advanced - Charger Settings - Charge Cycle (factory default setting)
4) On MPPT set CHARGE CYCLE to '3 stage' in MPPT Advanced - Charger Settings - Charge Cycle 
5) It is also recommended that the system has a minimum battery capacity of 200Ah. An additional 100Ah for every 1kW of solar power is preferable.

What is the maximum altitude an ATV61 or ATV71 series drive can be used at?

Issue:
What is the maximum altitude an ATV61 or ATV71 series drive can be used at?

Product Line:
Altivar 61, Altivar 71 series drives.

Environment:
All models, All serial numbers.

Cause:
Elevation vs current rating

Resolution:
The Altivar  61 and 71 series drives can be used at full rating up to 1000 meters above sea level. They must then be derated by 1% for every additional 100 meters up to a maximum of 3000 meters above sea level.
Note that the ATV61H***S6X and ATV71H***S6X drives must not be used with corner grounded systems at altitudes above 2000m.

What are the replacement contacts and diaphragm part numbers for a 9013FHG/FSG pressure switch?

Issue:
9013F** pressure switch repair kit

Product Line:
Commercial Pressure Switches

Environment:
Type F—Pumptrol™ Water Pump Pressure Switches

Resolution:
For standard (non-special) devices:
  • Types FHG2 thru 19 order 9998 PC241.
  • Types FHG22 thru 39 order 9998 PC242.
  • Types FHG42 thru49 order 9998 PC241.
  • Types FHG52 thru 59 order 9998 PC242.
For all Type FSG devices: 
  • Order 9998 PC241.  

Note: the diaphragm comes with the replacement contacts.

How do I get Modsoft to open up to full screen display while I try to run it under WIN 2000?

The command to get Modsoft to change window size is ALT+<ENTER>; however Modsoft is not supported under WIN 2000. Users may try running the application under it; however successful operation cannot be guaranteed. One of the common problems is Modsoft will not open up to full screen. Regrettably there is no means to resolve this issue other than to reinstall the software under a supported OS, such as WIN 95, WIN 98 or DOS.


Legacy KB System (APS) Data: RESL171500 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modsoft

Why is my Conext CL showing an alarm code:2418 & 2419 (AC UV Slow Err & AC OV Slow Err Service Alarm)

Issue: 
Customer is calling to confirm alarm code:2418 & 2419 (AC UV slow err & AC OV slow err Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
AC voltage is below (Under Voltage) or above (Over Voltage) the set limits
AC Voltages are not according to the set country or custom setting

Resolution: 
Measure the voltage at the inverter AC connections and check if it is within the country or custom setting limits, adjust if necessary in accordance with utility.

Why is my Conext CL showing an alarm code:8000 (AC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code:8000 (AC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
Grid current measured exceeds unit rating
DC bus voltage outside operational parameters
Internal AC bus voltage too high
Phase lock loop failure during inverting

Resolution: 
Reset unit by turn off both AC and DC
If problem persist replace the unit
 
 

Why is my Conext CL showing an alarm code: 9000 (DC Internal Error Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 9000 (DC Internal Error Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting

Cause:
PV current measured exceeds unit rating
Internal DC bus voltage too high
Difference between top or bottom DC bus voltage too high
Dc bus voltage too low
DC voltage sensor measurement failure

Resolution: 
Reset unit by turn off both AC and DC
If problem, persist replace the unit

Why is my Conext CL showing an alarm code: 32 & 33 - AC temp snsr flt & DC temp snsr flt ( AC and DC Temp Sensor Fault Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 32 & 33 ( AC temp snsr flt Service)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext CL 25000E

Environment:  
On site troubleshooting
 
Cause:
Abnormal ambient temp
Cooling problem
Detection circuit malfunction

Resolution: 
Check fans, installation conditions, air inlet and outlet
Check Internal temperature displays in STATUS screen
Turn off and on AC breaker
If failure persists, replace the unit

Why is my Conext CL showing an alarm code: 10 - AC relay flt (AC Relay Fault: Service Alarm)

Issue: 
Customer is calling to confirm alarm code: 10 (AC relay flt: Service Alarm)

Product Line: 
Conext CL 18000NA Conext CL 25000NA Conext CL 20000E Conext cL 25000E

Environment:  
On site troubleshooting

Cause:
AC output relay is either welded or opened  
Abnormal frequent disconnections from the grid that caused premature ageing of the relay

Resolution:  
If the failure persists, replace the inverter