Quantcast

Cable Management Fixing Accessories, 32mm Zinc Plated Metal Half Saddle

Cable Management Fixing Accessories, 32mm Zinc Plated Metal Half Saddle

Cable Management Fixing Accessories, 32mm Zinc Plated Metal Half Saddle

Item Number: 180/32

Retail
$1.99
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Surface treatment

zinc plated

Physical

Length

67 mm

Width

24 mm

Height

33 mm

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Material

Material

steel

Others

Diameter

32 mm

Package 1 Weight

25 g

Package 1 Height

29 mm

Package 1 width

35 mm

Package 1 Length

70 mm
Show all specifications

Frequently Asked Questions

hide show

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

What colours are the PDL 680M32 available in?

The PDL 680M32 (switch module, 1 way, 2 terminal, 32A, 240V) is only available in white or black.
https://www.pdl.co.nz/product-details.aspx?rcat=products&catid=0&id=825

What is the alternative replacement for old merlin Gerin code 18073 ?

Code =  A9E18073

Is it possible to reset the PM800 (PM8) Peak Demand via a register write?

Issue
How to write a command to a modbus register within the PowerLogic PM800 series meter to reset the peak demand.

Product Line
PowerLogic PM800 series meter

Environment
Microsoft Windows, Modbus Tester Tool

Cause
A customer may be required to reset the peak demand on his meter.

Resolution
To reset peak demand values, write the value 5210 to register 8000 on the PM800 series meter using the Modbus Tester Tool. 

To read/write registers using the Modbus Tester Tool, please refer to KB: FA 180037 - What is Modbus Tester and how do I use it?

Error When Attempting a Runtime Calibration in PowerChute Business Edition

Issue:
Error When Attempting a Runtime Calibration in PowerChute Business Edition

Product Line:
PowerChute Business Edition

Environment:
All supported OS

Cause:
1) The battery has less than 100% charge:
2) The load on the UPS is 10% or less:

Resolution:
Two conditions need to be met in order to perform a calibration:

1) The battery charge needs to be at 100%,
2) The load on the UPS needs to be greater than 10% of the battery capacity


 

Fuse and circuit breaker rating for LXM32

Issue:
What is the fuse or circuit breaker rating for LXM32 drives?

Product Line:
LXM32

Resolution:
For 115VAC and 230VAC drives, the maximum fuse to be connected upstream is 25 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.
For 400VAC and 480VAC drives, the maximum fuse to be connected upstream is 30/32 Amps, Class CC or J as per UL 248-4, alternatively circuit breakers with B or C characteristic.
Show More