Quantcast

Zinc Plated Metal Half Saddle 20mm

Zinc Plated Metal Half Saddle 20mm

Zinc Plated Metal Half Saddle 20mm

Item Number: 180/20

Retail
$0.58
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Product brand

Clipsal

Surface treatment

zinc plated

Physical

Length

50 mm

Width

19 mm

Height

22 mm

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Material

Material

steel

Others

Diameter

20 mm

Package 1 Weight

13 g

Package 1 Height

23 mm

Package 1 width

25 mm

Package 1 Length

54 mm
Show all specifications

Frequently Asked Questions

hide show

Are the Clipsal Conduit Clips available in Electric Orange?

No, they are only available in grey.

This applies to the 280/16 (16mm), 280/20 (20mm), 280/25 (25mm), 280/32 (32mm), 280/40 (40mm) and 280/50 (50mm).

Can I order the 220/20 in white?

Yes, you can order the 220/20 in white but it needs to be done as a special.
For more information, please refer to the link:https://www.clipsal.com/Trade/Products/ProductDetail?catno=220/20

What would be the part number for an Earth Clip, 16/20 mm.

203M.
Pressed Metal Conduit Fittings, Earth Clips, Water pipe adjustable earth clip 15 - 20mm or 1/2 - 3/4 inch.
Please see following link under the documentation tab for full catalogue.
https://www.clipsal.com/Trade/Products/ProductDetail?catno=203M

Trace SW4024 shows error under/over speed as yes, what does that mean?

TRACE SW4024 shows Generator under/over speed error



 The Trace SW4024 120/60hz has a preset AC2 allowable frequency range from (53-67 hz)
If there is a frequency out of that range you will get a generator under/over frequency.
Solution: Service generator, replace bushings if applicable, and try to reduce max charge rate to see if the remedies the generator input. 
 

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

Conext SW - Installation/ Wiring issue.

Issue:

Customer is installing the Conext SW and wants to confirm the wiring of the AC and DC cabling. 

Environment:

Conext SW 2524 120/240 Split-phase (865-2524)
 
Conext SW 4024 120/240 Split-phase (865-4024)


Resolution:
 

See the attached wiring diagrams for the Conext SW and Conext SW-NA.
Do not mix AC and DC wiring in the same conduit or panel. Consult the applicable installation code for details.
There are two dual 3/4" /1" trade-size knockouts on the side panel and another two on the bottom panel for AC wiring. Use the same trade size of strain relief as the trade size of the knockout(s) you are using.

 