socket cord ext'n 10a 250v

Extension Socket, 250VAC, 10A, Quick Connect, Transparent

Catalogue Number: 1438
socket cord ext'n 10a 250v
Retail
$26.15
RRP (Inc. GST)
Colour Transparent (TR)
  • Transparent 1 PCE

Specifications

hide show
Range of product
Standard Series
Product brand
Clipsal
Quantity per set
set of 1
Cover type
complete housing
Marking
without marking
Local signalling
without light indicator
[In] rated current
10 A
[Ue] rated operational voltage
250 V AC
Depth
62 mm
Diameter
41 mm
Standards
  • AS/NZS 3112
  • AS 3100
  • AS 3109
  • AS/NZS 3122:approval number S/1
    • Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      48.3 g
      Package 1 Height
      50 mm
      Package 1 width
      70 mm
      Package 1 Length
      100 mm
      Unit Type of Package 2
      BB1
      Number of Units in Package 2
      10
      Package 2 Weight
      0.55 kg
      Package 2 Height
      84 mm
      Package 2 width
      126.5 mm
      Package 2 Length
      170 mm
      Unit Type of Package 3
      CAR
      Number of Units in Package 3
      200
      Package 3 Weight
      11 kg
      Package 3 Height
      254 mm
      Package 3 width
      348 mm
      Package 3 Length
      445 mm
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      Frequently Asked Questions

      hide show

      Does Clipsal have a 1438 in 20 amp?

      No, but we have a 438 in 20 amp or there is the 56 series which could do the job.

      For more information, please refer to the link:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=438/20 

      How to use a port other than 1433 for SQL transactions with PME7.2 / SPM7.0.1

      Issue:
      Use a port other than 1433 for SQL transactions with PME7.2 / SPM7.0.1

      Product Line:
      Power Monitoring Expert 7.2.x
      Struxureware Power Monitoring 7.0.x

      Environment:
      Power Monitoring Expert 7.2.x
      Struxureware Power Monitoring 7.0.x

      Cause:
      When port 1433 is blocked or unavailable

      Resolution:

      Port 1433 is the default port used by SQL for all transactions. If port 1433 is blocked and a different port needs to be used, then perform the following steps after installing SQL, but before installing the StruxureWare:

      1. On the application server, create an alias using the SQL Server Client Network utility (start->run->cliconfg) that comes as part of the Windows OS installation.



      2. Click on the Alias tab and then click the Add button



      3. Select TCP/IP, enter the server name, and uncheck "Dynamically determine port"

      4. Change the Port Number to the new port that is is being used (if the new port is 1436, for example, enter 1436 in this field)



      After these steps are completed, running the StruxureWare installer on the Application Server will now connect to the correct port.

      Do you have a 32A version of a 438 extension socket?

      No, the largest rated version of a 438 extension socket is the 438/20 which is 20A.

      Where to find settings manual for MiCOM x3x Series?

      Issue 
      Need more information on settings on the MiCOM x3x.

      Product Line  
      MiCOM P13x
      MiCOM P23x
      MiCOM P43x
      MiCOM P53x
      MiCOM P63x

      Environment  
      Setting or Troubling settings

      Resolution    
      All the settings, measurements, recordings with option and configuration tables plus IEC - 103 telegram documentation/menu database can all be found in the Data Model Explorer.
      To get the Data Model Explorer needed just type in the MiCOM model need.  For example in Google type in MiCOM P438 for Data Model Explorer.  Click on the Schneider Electric result for the MiCOM P438 Data Model Explorer.
      It will bring up the following Data Model Explorer page https://www.schneider-electric.com/en/download/document/P438_DataModelExplorer_EN/
      On the site download the P438 that is needed. 
       

      What is a K1 rating on a dry type Transformer?

      Issue:
      K rated Transformers

      Product Line:
      LV Transformers

      Environment:
      Applies to Low Voltage Transformers by SquareD/Schneider Electric

      Cause:
      K rated Transformers for application on Non Linear loads

      Resolution:
      The Transformer industry does not typically use a `K1` rating.  Rather it is a non-recognized term that some (consultants, OEMs, contractors) use  to denote a Transformer that will only be feeding Linear loads such as motors, compressors, solenoids, heaters, etc.   In other words, K1 refers to a Transformer that does not have a  `K` rating such as K4, K9, K13, K20.        


      CTA-ID : 14386

      We get response buffer too small: 1038 / 1204 in Unity Loader log file ( ULUMAS log file ), what does this error means?

      The log message "response buffer too smal" means that when we upload  from the CPU not all data blocks were uploaded, because some block sizes in the PLC seem to be too big.

      What size cable does a LAD7B10 accept?

      Issue:
      Need to know the size cable accepted by the LAD7B10 block.

      Product Line:
      IEC Contactors and starters

      Environment:
      Products sold and used in the United States

      Cause:
      Identifying cabling requirements.

      Resolution:
      It takes either a 1 flexible cable without cable end size 14-8 AWG or 1 flex cable with cable end size 16-12AWG or 1 solid cable without cable end size 16-10 AWG.


       

      Does third-party equipment exist to test the AFCI to determine that it is functioning properly?

      Product Line:
      Circuit Breakers
      QO and Homeline
      AFI and AFCI

      Environment:
      Electrical Distribution Equipment

      Resolution:
      No. So-called AFCI ``testers`` are on the market, but they are not UL listed for testing the function of an AFI circuit breaker. UL 1436 refers to them as ``indicators`` rather than testers, and Square D does not endorse them or recommend their use. They are subject to error in the form of giving a false negative result.

      The UL approved method of testing an AFCI circuit breaker is to press the push-to-test button when installed in an energized load center or panel. This test injects a signal into the AFCI sensor that looks like an arc to the AFCI. A properly functioning AFCI will trip when the test button is pushed.

      Paragraph 31.8.1 of the UL 1436 standard requires the AFCI Indicator markings or instructions to effectively state that the test button on the AFCI circuit breaker demonstrates proper operation.
       

      Configuring SeaLevel 450 Relay I/O Device within Netbotz

      Issue:

      Configuring SeaLevel 450 Relay I/O Device within Netbotz

      Product Line:

      NetBotz
      Sealevel

      Environment:

      NetBotz version 2 and 3
      Sealevel 450

      Cause:

      3rd party device configuration.

      Resolution:

      Once the I/O Device is connected to the Appliance, configuration for the Seal/O device can be done by the following:

      1. Launch the Advanced View on the Appliance.
      2. Double click the 'Serial Devices' Applet
      3. In the drop-down menu, select the Sea-Level Product >> SeaLevel SeaI/O 450.
      4. Then select 'OK'


      What is the maximum number of Momentum IO bases allowed on IObus?

      An IObus network may consist of as many as 256 nodes, however there are also limitations on the number of I/O words available. The limit is based on the processor type as shown in the following table:

      Processor Type
      Max. Input Words
      Max. Output Words
      171CCS76000
      128
      128
      171CCC76010
      256
      256
      171CCC96020
      256
      256
      171CCC96030
      256
      256

      Note: Processors that support IEC are limited to a maximum number of 1408 used I/O points, regardless of the number of modules.
       

      What is the standard key used in a 9001KX,9001KR, 9001KS and 9001SKS selector switch?

      Issue:
      Replacement standard key for the 9001 oeprators.

      Product Line:
      Harmony Pushbuttons

      Environment:
      All Products

      Resolution:
      The standard key is the E10 key which is catalog number 2941101100.
       

      What is the right way to connect and chain the MET 148, MSA 141, and DSM 303 accessories on the Sepam 20 or 40?

      Goals and Symptoms

      What is the right way to connect and chain the MET 148, MSA 141, and DSM 303 accessories on the Sepam 20 or 40?

      Causes and Fixes


      On the D Port you have to connect and chain in order:

      (1) MSA 141

      (2) MET 148 ( Attention: Option 2 MET 148 for Sepam 40 only )

      (3) DSM 303 (Always at the end of this chain and only if no more than 2 accessories already connected on Sepam)

      Note: you can't connect more 3 accessories on this chain so if you already have 1 MSA 141 and 2 MET 148 it is impossible to set also 1 DSM 303. In this case if you want to put this DSM 303, you have to remove the MSA 141 or 1 MET 148.

      Key words and phrases: MSA141, MET148, DSM303

      AEDL3


      Legacy KB System (APS) Data: RESL201098 V1.0, Originally authored by DaMi on 01/22/2010, Last Edited by DaMi on 01/22/2010
      Related ranges: Sepam accessories, Sepam series 20, Sepam series 40
      Show More