Cable Management Machined Brass, Steel Couplings, 50mm Steel Locknut

Cable Management Machined Brass, Steel Couplings, 50mm Steel Locknut

Cable Management Machined Brass, Steel Couplings, 50mm Steel Locknut

Item Number: 1259S50

Retail
$30.80
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Clipsal

Product or component type

lock nut

Physical

Range compatibility

REACh free of SVHC

Yes

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Material

Material

steel

Others

Accessory / separate part category

fixing accessory

Diameter

  • thread: 50 mm
  • external: 75 mm
    • Height pitch dimension

      1.5 mm

      Threaded length

      65 mm

      Thickness

      5 mm

      Unit Type of Package 1

      PCE

      Number of Units in Package 1

      1

      Package 1 Weight

      0.06 kg

      Package 1 Height

      65 mm

      Package 1 width

      4 mm

      Package 1 Length

      65 mm

      Unit Type of Package 2

      BB1

      Number of Units in Package 2

      20

      Package 2 Weight

      1.3 kg

      Package 2 Height

      76 mm

      Package 2 width

      120 mm

      Package 2 Length

      160 mm

      Unit Type of Package 3

      CAR

      Number of Units in Package 3

      100

      Package 3 Weight

      6.5 kg

      Package 3 Height

      117 mm

      Package 3 width

      250 mm

      Package 3 Length

      310 mm
      Show all specifications

      Frequently Asked Questions

      hide show

      What is part number for lid to suit 1239/20/4?

      Part number 1239L20 will suit any of 1239/20 series.

      Control power rating on the CM4000 series meter is different than what is stated in the specifications in CM4 manual

      Issue
      Control power rating is different than what is shown in the CM4000 series user manual 

      Product Line
      CM4000 Series

      Environment
      Wiring

      Resolution
      The control power for the CM4000 series Circuit Monitors is rated for a voltage range of 90-305V ac or 100-300V dc. It was our standard practice to publish these ratings. Recently a change was implemented to mark the circuit monitors with the nominal voltage ranges instead of the maximum range. As a result the meters now show a control power voltage range of 100-277 V ac or 125-250 V dc.
      If the customer needs a document with signature for their customer, you can send them the following document from John Straughn below.

      What is the part number for a 20mm steel conduit plug?

      The part number  for a 20mm brass plug for steel conduit is 1220S20.

      Please confirm that the Neutral can be connected to either the left hand or the right hand pole in a Masterpact 4-pole breaker.

      The 4 neutral pole is specific. So a circuit breaker either comes equipped with a neutral pole configured on the far right pole or the far left pole. The pole is marked and must be wired accordingly because the trip system for the neutral set up separate form the 3 phases.


      CTA-ID : 2059750

      What profile should be used in PSE to add a PM5560

      Issue
      In Profile Editor, there are two PM5000 options, PM5000S and PM5000S1

      Product
      StruxureWare Power SCADA Expert (PSE) 7.4, 8,0, 8.1
      PowerSCADA Operations (PSO) 8.2

      Environment
      Profile Editor

      Resolution
      Select the PM5000S profile to add a PM5560 device to a project.

      Can a three pole breaker be used on a single phase (two-wire) load in a three phase panel?

      Issue:
      Product design

      Product Line:
      Molded Case Circuit Breakers

      Environment:  
      Square D Circuit Breakers

      Cause:
      Application

      Resolution:
      Yes.  According the UL White Book (Product Category DIVQ), multipole common trip circuit breakers rated 125/250V are suitable for use for a single-phase multiwire circuit, with or without the neutral connected to the load.  Courtesy of Mike Holt Enterprises 2008
      Show More