locknut steel hex cond 50mm

Cable Management Machined Brass, Steel Couplings, 50Mm Steel Locknut

Catalogue Number: 1259S50
locknut steel hex cond 50mm
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range
Clipsal
Product or component type
lock nut
Accessory / separate part category
fixing accessory
Range compatibility
Material
steel
Diameter
  • thread: 50 mm
  • external: 75 mm
    • Height pitch dimension
      1.5 mm
      Threaded length
      65 mm
      Thickness
      5 mm
      REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)
      Circularity Profile
      N/A

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      • Technical Data Catalogues

      • Installation Instruction

      • Specifications

      • Certificates (MSDS)

      Frequently Asked Questions

      hide show

      What is part number for lid to suit 1239/20/4?

      Part number 1239L20 will suit any of 1239/20 series.

      Control power rating on the CM4000 series meter is different than what is stated in the specifications in CM4 manual

      Issue
      Control power rating is different than what is shown in the CM4000 series user manual 

      Product Line
      CM4000 Series

      Environment
      Wiring

      Resolution
      The control power for the CM4000 series Circuit Monitors is rated for a voltage range of 90-305V ac or 100-300V dc. It was our standard practice to publish these ratings. Recently a change was implemented to mark the circuit monitors with the nominal voltage ranges instead of the maximum range. As a result the meters now show a control power voltage range of 100-277 V ac or 125-250 V dc.
      If the customer needs a document with signature for their customer, you can send them the following document from John Straughn below.

      CM4 Power Supply Rating.pdf

       

      What is the part number for a 20mm steel conduit plug?

      The part number  for a 20mm brass plug for steel conduit is 1220S20.

      Please confirm that the Neutral can be connected to either the left hand or the right hand pole in a Masterpact 4-pole breaker.

      The 4 neutral pole is specific. So a circuit breaker either comes equipped with a neutral pole configured on the far right pole or the far left pole. The pole is marked and must be wired accordingly because the trip system for the neutral set up separate form the 3 phases.


      CTA-ID : 2059750

      What profile should be used in PSE to add a PM5560

      Issue:
      In Profile Editor, there are two PM5000 options, PM5000S and PM5000S1

      Product:
      StruxureWare Power SCADA Expert (PSE) 7.4, 8,0, 8.1
      PowerSCADA Operations (PSO) 8.2

      Environment:
      Profile Editor

      Resolution:
      Select the PM5000S profile to add a PM5560 device to a project.

      Can a three pole breaker be used on a single phase (two-wire) load in a three phase panel?

      Issue:
      Product design

      Product Line:
      Molded Case Circuit Breakers

      Environment:  
      Square D Circuit Breakers

      Cause:
      Application

      Resolution:
      Yes.  According the UL White Book (Product Category DIVQ), multipole common trip circuit breakers rated 125/250V are suitable for use for a single-phase multiwire circuit, with or without the neutral connected to the load.  Courtesy of Mike Holt Enterprises 2008