bend solid galv cond 40mm

Series 1247 Machine Cast Fittings, Solid BEnds, 40Mm Galvanised Cast Iron

Catalogue Number: 1247/40
bend solid galv cond 40mm
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Series 247
Material
cast iron
Surface treatment
galvanised
Diameter
40 mm
Connector type
thread connector
Operating angle
90 °
Length
182 mm
Inner radius
105 mm
Standards
  • AS 2052
  • AS 1721
    • REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)

      Frequently Asked Questions

      hide show

      Does the 1240/25 series come with gaskets?

      No, they are light duty. Buy the 1240HL25 to obtain a heavy duty lid and gasket , or if gasket is required for retro fit then buy 1240GT
      For more information on this product range please visit the Clipsal web site on the link provided
      https://www.clipsal.com/Trade/search-results?q=1240

      L1 VME What size Fixing Screws for the PDL 600 Series are available?

      16mm, 30mm and 50mm Long 

      Whati s pitch thread for part number 1245/25?

      Pitch thread is 1.5mm

      What is part number for lid to suit 1239/20/4?

      Part number 1239L20 will suit any of 1239/20 series.

      What is the replacement for RE11RMMW Timer?

       The replacement for RE11RMMW Timer is  RE17RMMW

      RE17RMMW 
      time delay relay 10 functions - 1 s..100 h - 12..240 V AC/DC - 1 OC 

      For more information see: https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=RE17RMMW

      What registers hold the TMC2 analog cartridges status information in a M221 controller?

      The status/diagnostic information for TMC2 analog cartridges is hold in one dedicated object per channel

      First cartridge:
      %IWS0.100: first cartridge, channel 1
      %IWS0.101: first cartridge, channel 2

      Second cartridge (for M221 with two cartridges)
      %IWS0.200: second cartridge, channel 1
      %IWS0.201: second cartridge, channel 2

      Conext SW - Installation/ Wiring issue.

      Issue:

      Customer is installing the Conext SW and wants to confirm the wiring of the AC and DC cabling. 

      Environment:

      Conext SW 2524 120/240 Split-phase (865-2524)
       
      Conext SW 4024 120/240 Split-phase (865-4024)


      Resolution:
       

      See the attached wiring diagrams for the Conext SW and Conext SW-NA.
      Do not mix AC and DC wiring in the same conduit or panel. Consult the applicable installation code for details.
      There are two dual 3/4" /1" trade-size knockouts on the side panel and another two on the bottom panel for AC wiring. Use the same trade size of strain relief as the trade size of the knockout(s) you are using.

       

      What's the difference between the SyMax Model 50 programmable controllers 8005CP50 and 8005CP51?

      The difference between the two SyMax Model 50 programmable controllers is the power voltage rating.
      8005CP50 is a 120/240 VAC Processor Unit.
      8005CP51 is a 24 VDC Processor Unit.


      Legacy KB System (APS) Data: RESL169642 V1.0, Originally authored by on , Last Edited by on
      Related ranges: Sy/Max

      How can I power up an iEM3000 series meter?

      Issue
      The iEM3000 series meter documentation does not explicitly specify where and how control power is brought to the meter.  

      Product Line
      iEM3000 Series Meters
       
      Cause
      To know the maximum voltage to supply, where, and how to wire the supply power.

      Resolution
      The iEM3000 series meters derive control power through the meter's phase voltage inputs V1, V2, V3, and Vn.  The installation guide for the iEM3000 contains wiring diagrams for different voltage systems.  The meters support the direct power Voltage (L-L) 3 x 100/173 V AC to 3 x 277/480 V AC (50/60 Hz) and the direct current measurement up to 63 A or 125 A.

      Refer to FA352325 for documentation for iEM3000 meters.  

      Energy Meter shows "Phase Loss" Alarm

      Issue
      Energy meter shows “Phase Loss” alarm on front display.

      Product Line
      Energy meter (EMB and EME series).

      Environment
      Installing/wiring energy meter

      Cause
      If the voltage of any phase is measured as less than 75% of the voltage on any other phase, the display will show PHASE LOSS and indicate the specific phase(s).

      Resolution
      If the energy meter is installed with the proper number of phases (see selection below to determine this) then the phase voltages should be verified. If the number of phases installed is not correct, then the phase loss alarm will be indicated in all operating conditions.

      It’s very important to know the model number of your Energy meter.  
      For example, users see “Phase Loss” error when they use EMB2043 (1 phase, 3 wire) with 1 phase, 2 wire application.

      As a result, it’s very important for users to know their application and use appropriate meter that meets their system type.  Please review the tables below for selecting correct meter.

      Basic 120/240 Volt 208 Wye

      EMB1010 Basic 100A 1 Phase, 2 wire installation 1 CT
      EMB1021 Basic 200A 1 Phase, 2 wire installation 1 CT
      EMB1032 Basic 300A 1 Phase, 2 wire installation 1 CT
      EMB2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
      EMB2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
      EMB2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
      EMB2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
      EMB2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
      EMB3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
      EMB3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
      EMB3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
      EMB3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
      EMB3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
      EMB3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
      EMB3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs


      Extended Range 120/480 Volt Wye

      EME1010 Basic 100A 1 Phase, 2 wire installation 1 CT
      EME1021 Basic 200A 1 Phase, 2 wire installation 1 CT
      EME1032 Basic 300A 1 Phase, 2 wire installation 1 CT
      EME2010 Basic 100A 1 Phase, 3 wire installation 2 CTs
      EME2021 Basic 200A 1 Phase, 3 wire installation 2 CTs
      EME2032 Basic 300A 1 Phase, 3 wire installation 2 CTs
      EME2043 Basic 400A 1 Phase, 3 wire installation 2 CTs
      EME2083 Basic 800A 1 Phase, 3 wire installation 2 CTs
      EME3010 Basic 100A 3 Phase, 4 wire installation 3 CTs
      EME3021 Basic 200A 3 Phase, 4 wire installation 3 CTs
      EME3032 Basic 300A 3 Phase, 4 wire installation 3 CTs
      EME3043 Basic 400A 3 Phase, 4 wire installation 3 CTs
      EME3083 Basic 800A 3 Phase, 4 wire installation 3 CTs
      EME3084 Basic 800A 3 Phase, 4 wire installation 3 CTs
      EME3164 Basic 1600A 3 Phase, 4 wire installation 3 CTs


      NOTE: the meter will operate, however the phase loss alarm will constantly be present if the improper meter is in use.

      XW Won't qualify generator.

      Issue:

      XW inverter charger will not qualify AC generator. AC IN light blinks
      AC input qualification, overloading the generator, unable to sustain battery charging and and running loads (multi-tasking)


      Environment:

      XW 4024/4548/6048 with AC generator


      Resolution:

      1) Ensure generator is split phase 120/240, not 120 monophase or 120/208V. Voltage from (L1 to N) and (N to L2) should add up exactly to (L1 to L2) voltage
      3) Recommended, size your generator 2 times the rating of the XW system.
      2) Ensure no neutral to ground bond in Generator
      3) Connect gen output to AC2, not AC1 and open up AC2 parameters in XW advanced settings - ac settings menu
      4) Reduce max charge rate in XW
      5) If Kohler RES series generator, see  Solution 1179

      Cause:

      1) XW can only connect to splt-ph 120/240 unless converted to monophase 
      2) Potential ground loop
      3) AC2 qualification parameter window much wider than AC1
      4) Gen being overloaded by combination of house loads and XW charger.

      Can a circuit breaker be operated at a voltage less than the voltage marked on the breaker?

      Inquiry:
      Is it OK to apply a circuit breaker on a voltage system rated lower than the rating of the breaker?

      Product Line:
      MCB and MCCB circuit breakers

      Cause:
      Circuit breakers are typically marked only with a few standard voltages, while other voltage systems exist.

      Resolution:
      Yes. According to 2011 NEC article  240.83(E), a circuit breaker may be used at voltages equal to or less than its voltage rating. 
      When applied on a system of lower voltage than marked, he interrupting rating is equal to the next highest marked interrupting rating. 
      The only exceptions to application at less than rated voltage are:
      1. QO and HOM -GFI, -EPD, -AFI, -CAFI, and DF circuit breakers must be applied on 120/240 Vac systems only (they need over 100 Vac to power the electronic modules)
      2. EHB-EPD and EDB-EPD type breakers which must be applied on 480Y/277 systems only

      NOTE:  Circuit breakers marked with DC ratings only are not suitable for application on AC systems, and circuit breakers marked with AC ratings only are not suitable for application on DC systems.
      Show More