Issue:
ATV212 or ATV21 set up to start/stop on terminal and ramp to 60 Hz
Product Line:
ATV21, ATV212
Environment:
All models and serial numbers.
Cause:
None
Resolution:
Begin by wiring the remote start switch or relay for two wire control between terminals P24 and F.
Program the nameplate motor parameters into the following parameters:
CODE - DESCRIPTION |
thr - Motor thermal prot. |
uLu - Motor rated voltage |
F415 - Motor rated current |
F417 - Motor rated speed |
Make the following parameter settings:
CODE - DESCRIPTION |
SETTING |
LL - Low limit frequency |
as desired |
UL - Upper limit freq |
60 |
Dec - Deceleration ramp time |
as desired |
ACC - Acceleration ramp time |
as desired |
CMOD - Command mode selection |
0 |