Frequently Asked Questions

hide show

What is part number for lid to suit 1239/20/4?

Part number 1239L20 will suit any of 1239/20 series.

How to control an ATV61 / ATV71 with a M340 CPU built-in Ethernet port using the DATA_EXCH function

The attached document describes an application using a M340 CPU with a built-in Ethernet port connected to an ATV71 Ethernet card VW3A3310D and using the DATA_EXCH function. The M340 will be communicating with the IO Scanner service in the drive.
 

What would cause a Quantum 140CPS11100 power supply to not power up?

The Quantum 140CPS11100 power supply that has a PV 01 or higher now require a jumper on pins 3 and 4 on the terminal strip for 115 VAC operations. If this jumper is not installed, it will be set for 220 VAC operations. Any power supply with a PV less than 1 did not require the jumpers.

Note: The Quantum line is obsolete 12/1/2018 and the recommended replacement is the M580 with the x80 I/O, for further information on this contact your local distributor.


Can my XW+ inverter qualify an input of 120V/208V 60Hz?

XW+ inverters input parameters

The XW+ and XW inverters, either the XW6848, XW5548, XW6048, XW4548 or the XW4024, require an input of 120V/240V 60Hz. When the input is 120V/208V 60Hz, is going to be a three phase setup. The reason for this is because the XW+ and XW unit require a phase difference between line 1 (L1) and line 2 (L2) of 180 degrees, on a three phase setup, L1 and L2 are 120 degrees offset. This causes the inverter to not recognize the input at all. The inverter can only accept input from 120/208V wye source if you have 3 inverters (1 per phase), each "converted" to 120V, and then configured for 3-phase multi-unit operation.

Single Phase Diagram:



Three Phase Diagram:


 

What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

Issue:
What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

Product Line:
Altistart 48, ATS48

Environment:
All open style units.  All models, All Serial numbers.

Cause:
Selection of Fuses.

Resolution:

ATS48D17Y and ATS48D22Y we recommend Class CC 600V 0.5 A fuses.

ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y we recommend Class CC 600V 0.6 A fuses.

ATS48C21Y, ATS48C24Y, and ATS48C32Y we recommend Class CC 600V 1.0 A fuses.

ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y we recommend Class CC 600V, 1.5 A fuses.

Information provided in Table 31 page 83) of document S1A37491 Altistart 48 Y-range Soft Start Controllers Instruction Bulletin.

What is the minimum clearance for mounting Twido Controllers in a cabinet?

Minimum Clearances for a Compact Controller and Expansion I/O Modules. In order to maintain a natural circulation of air around the Compact controller and expansion I/O modules in a control panel, observe the minimum clearances shown in the figures below.

Minimum Clearances for a Modular Controller and Expansion I/O Modules. In order to maintain a natural circulation of air around the Modular controller and expansion I/O modules in a control panel, observe the minimum clearances shown in the figures below.

 


Note: Twido was made obsolete 12/1/2015 and has been replaced with the M221. The Twido program can be imported into the M221 SoMachine Basic software and the dimensions are the same for the M221 as the Twido. For further information on this contact your local distributor or Schneider sales office.