nipple brass cond 20mm

Cable Management Machined Brass, Steel Couplings, 20Mm Brass Nipple

Catalogue Number: 1243/20
nipple brass cond 20mm
Retail
$15.76*
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal
Range of product
Series 1243
Material
brass
Connector type
thread connector
Product destination
diameter: 20-20 mm tube
Length
30-30 mm
Standards
  • CS 792/S
  • AS 2052
  • AS 1721
    • REACh Regulation
      Free of Substances of Very High Concern above the threshold
      REACh free of SVHC
      Yes
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      Toxic heavy metal free
      Yes
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
       Pro-active China RoHS declaration (out of China RoHS legal scope)

      Frequently Asked Questions

      hide show

      Whati s pitch thread for part number 1245/25?

      Pitch thread is 1.5mm

      What is part number for lid to suit 1239/20/4?

      Part number 1239L20 will suit any of 1239/20 series.

      Does the 1240/25 series come with gaskets?

      No, they are light duty. Buy the 1240HL25 to obtain a heavy duty lid and gasket , or if gasket is required for retro fit then buy 1240GT
      For more information on this product range please visit the Clipsal web site on the link provided
      https://www.clipsal.com/Trade/search-results?q=1240

      What would be a longer screw to suit Clipsals round j-boxes (Junction Boxes)?

      The part number would be 248/20 which is a combination screw head 20MM 3/16 BSW.

      What is the part code for the cord connector to suit the PDL56P320F?

      We do not do one this size and with flat pins in 56 series
      clipsal option (not IP rated)
      438/20-WE - extention socket 20A
      1439/20 - 20A plug
       

      Is there a 32A version of the 1439/20?

      No, 20A is the largest size in this model plug.

      What changes/updates are included in Nxt 2.2 SP8?

      Special 8 Features
      ----------------------------------------------
      - Fixed DDO364-00 User Defined/Last Value settings.
      - Fixed CPS 114-20, CPS 124-20 editing and power ratings.
      - Fixed NOE771-11 card causing an error "File not Found" in the TCOP editor
      - Fixed partial write of state ram clearing logic unintentionally.
      - Removed "Restore PLC Run State Before Power Down" option on the Transfer to Flash dialog for Momentum controllers.


      Legacy KB System (APS) Data: RESL174020 V1.0, Originally authored by on , Last Edited by on
      Related ranges: ProWORX

      How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

      Issue:
      Implementing a hardwire stepdown transformer in a 208v or 240v environment


      Product Line:

      Smart-UPS / Symmetra

      Environment:

      APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

      Cause:

      Unbalanced UPS outputs require a stepdown transformer to power 120v loads


      Resolution:

      This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

      The wiring block outputs are as follows:


      For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

      The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



       Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

      What is the warranty length for repaired C-Bus product outside of warranty

      3 months if the product is repaired outside of warranty.

      What is the part number for a 20mm steel conduit plug?

      The part number  for a 20mm brass plug for steel conduit is 1220S20.

      What is the thread type on a 1235/25?

      The thread type on a 1235/25 is BS - British Standard.

      For more information, please refer to the link:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=1235/25 

      Conext SW - Installation/ Wiring issue.

      Issue:

      Customer is installing the Conext SW and wants to confirm the wiring of the AC and DC cabling. 

      Environment:

      Conext SW 2524 120/240 Split-phase (865-2524)
       
      Conext SW 4024 120/240 Split-phase (865-4024)


      Resolution:
       

      See the attached wiring diagrams for the Conext SW and Conext SW-NA.
      Do not mix AC and DC wiring in the same conduit or panel. Consult the applicable installation code for details.
      There are two dual 3/4" /1" trade-size knockouts on the side panel and another two on the bottom panel for AC wiring. Use the same trade size of strain relief as the trade size of the knockout(s) you are using.

       
      Show More