box junct galv h/d 20mm 3w

Cable Management Machine Cast Fittings, Junction Boxes and Lid Kits, 20mm, 3 Way

Catalogue Number: 1239H20/3
box junct galv h/d 20mm 3w
Retail
$110.34
RRP (Inc. GST)

Specifications

hide show
Product brand
Clipsal
Range of product
Saturn Series
Material
cast iron
Depth
33 mm
Shape
round
Surface treatment
galvanised
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Weight
438.5 g
Package 1 Height
3.8 cm
Package 1 width
7.7 cm
Package 1 Length
7.8 cm
Unit Type of Package 2
BB1
Number of Units in Package 2
10
Package 2 Weight
4.385 kg
Package 2 Height
9.6 cm
Package 2 width
16.8 cm
Package 2 Length
17.8 cm
Unit Type of Package 3
CAR
Number of Units in Package 3
20
Package 3 Weight
8.82 kg
Package 3 Height
20 cm
Package 3 width
18 cm
Package 3 Length
22 cm
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

What is part number for lid to suit 1239/20/4?

Part number 1239L20 will suit any of 1239/20 series.

What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

Issue:
What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

Product Line:
Altistart 48, ATS48

Environment:
All open style units.  All models, All Serial numbers.

Cause:
Selection of Fuses.

Resolution:

ATS48D17Y and ATS48D22Y we recommend Class CC 600V 0.5 A fuses.

ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y we recommend Class CC 600V 0.6 A fuses.

ATS48C21Y, ATS48C24Y, and ATS48C32Y we recommend Class CC 600V 1.0 A fuses.

ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y we recommend Class CC 600V, 1.5 A fuses.

Information provided in Table 31 page 83) of document S1A37491 Altistart 48 Y-range Soft Start Controllers Instruction Bulletin.

Is there an alternative for 1239/20/1, Round, 20mm, 1 Way Entry, Light Duty Junction Box?

 Yes, however the alternatives may vary in style, material or number of entries.

The closest alternative in galvanised cast iron is a Junction Box, Round- 20mm I.D, 1 Way Entry, Heavy Duty. The Part number is 1239H20/1.
The closest alternative in PVC is a Junction and Adaptable Boxes PVC- 20mm Entries, 1 Way. The partn number is 240/20/1.

For further information please visit https://www.clipsal.com/Trade/searchround/jbox20MMENTRY1



             1239/20/1                          1239H20/1                           240/20/1                           



 

Sur le document suivant, PublicDocument Author Bertrand Guarinos Created : 12/09/2003 Sur le document suivant sur le site STIE-GHD. Title ...

Goals and Symptoms

Sur le document suivant,

PublicDocument
Author Bertrand Guarinos Created : 12/09/2003
Sur le document suivant sur le site STIE-GHD.
Title ATV11 line fuses list
Category d - PRODUCTS\ATV11\Maintenance, d - PRODUCTS\ATV11\Technical information.
e - Maintenance-Repair\ATV11.
Public.

figure deux types de fusible possibles à placer en tête d'alimentation des ATV11.
Où puis-je trouver la définition des classes fusible CC et J?
D'autre par pour qu'elle raison la valeur du courant assigné des fusibles rapides ou retardé en classe J est le même?
Voir document en attachement.

Causes and Fixes

Il s'agit de deux standards américains, protection au toucher pour le J et l'encombrement réduit pour le CC.

plus d'infos sur : https://www.ferraz-shawmut.com/fr/PRODUCTS/gen_nord_americain.html

What is the difference between the SyMax 8030PS25/35 power supplies and the 8030PS25F/35F power supplies?

The PS25F and PS35F power supplies are identical in function to the PS25 and PS35 modules, except that they do not have an ON/OFF switch located on the front of the module. A separate main disconnect switch or circuit breaker must be installed to shut off power to the programmable controller system.


NOTE: The Sy/Max product line was obsoleted 12/31/2013 and the recommneded upgrade is the M580, contact your local distributor or SchneiderElectric for more information.

What is the replacement part number for the Sy/Max RIM121 and ROM121 terminal strips?

Issue:
Replacements for Symax terminal blocks.

Product Line:
Symax

Cause>
Terminal blocks were corroded and needed to be replaced.

Resolution:
The part number for both the RIM121 and ROM121 replacement terminal strips is 2541002521. This is a service item and you will need to contact service.sales@se.com for pricing and availability.

Note: The Symax product line was obsolete 12/31/2013 and is no longer available. There are options for upgrade the the M580 that you can contact your local distributor or Schneider sales.

StruxureWare Power Monitoring 7.0 - Why do I see 'an unexpected error has occurred' when I try to add a Report Subscription in Web Reporter?

Issue
If StruxureWare Power Monitoring 7.0 is installed as a distributed system, that is, there is both a database server and an application server and Reporting Services is installed on the database server, you will not be able to create a report subscription.. When an attempt is made to add a report subscription, in the Web Reporter UI, the user will see a screen that says ''unexpected error has occurred. Your request cannot be processed at this time. If the problem persists, contact the Webpage administrator'.

If you look in the EventException table, the following will be displayed:

System.ApplicationException: Could not authenticate. at PowerMeasurement.Security.UserImpersonator..ctor(String username, String password, String domain) at PowerMeasurement.Apps.Web.EEM.Modules.Reports.AddRSReportSubscription.InitPrinterControl() at PowerMeasurement.Apps.Web.EEM.Modules.Reports.AddRSReportSubscription.Page_Load(Object sender, EventArgs e) at System.Web.Util.CalliHelper.EventArgFunctionCaller(IntPtr fp, Object o, Object t, EventArgs e) at System.Web.Util.CalliEventHandlerDelegateProxy.Callback(Object sender, EventArgs e) at System.EventHandler.Invoke(Object sender, EventArgs e) at System.Web.UI.Control.OnLoad(EventArgs e) at System.Web.UI.Control.LoadRecursive() at System.Web.UI.Page.ProcessRequestMain(Boolean includeStagesBeforeAsyncPoint, Boolean includeStagesAfterAsyncPoint)

Product Line
StruxureWare Power Monitoring (SPM) 7.0 or 7.0 to 7.0.1 Upgrade

Cause
This problem results because the IONUser windows account is not created on the application server at install time.

Resolution
The workaround is to add the IONUser Windows account manually. The password should be set to 'IONisgreat!' without the single quotes.. Most of the time, It does not need to be a member of any group. However, if the same error message shows up again, adding the IONUser to the Administrators group can correct the error.

This problem has been addressed in Struxureware Power Monitoring 7.0.1, but only on new installations. SPM 7.0 systems that are upgraded to SPM 7.0.1 will need to have the IONUser added to the application server manually.

What is the minimum firmware requirements for Powerlogic meters in StruxureWare Power Monitoring Expert?

Issue
What is the minimum firmware requirements for Powerlogic meters in StruxureWare Power Monitoring Expert?

Product Line
Powerlogic meters
StruxureWare Power Monitoring Expert 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0
Power Monitoring Expert 8.1
Power Monitoring Expert 8.2

Environment 
Power Monitoring Expert Software Configuration

Resolution
It is strongly recommended to upgrade the firmware to the recommended levels to rule out any potential issues. Below are minimum firmware requirements that SPM/PME will support.

Device Type Firmware Version(s)
PM810/PM820/PM850 10.6
PM870 10.7
CM3xxx 14.35
CM4xxx 14.34
PM750 3.02
PM700/PM700P/PM720 3.01
MicroLogic H 8.261 (Logic2005AF)
MicroLogic P 8.261 (Logic2005AF)
MicroLogic A No change in the last five years
MicroLogic Communications Module Use in type A, P, and H = 2.001
CM2050/CM2150/CM2250/CM2452 17.xxx
CM2350/CM2450 16.xxx
PM600 12.004
PM620 12.002
PM650 22.7
Momentum PLC D16 (EPSS) 1.01
Momentum PLC A8 (WAGES) 3.03
Momentum PLC D10 (WAGES) 3.03


NOTE: SPM can still support older firmware versions. However, some registers might be supported on those versions; and thus they may cause “n/a” or nonexistent measurement displays.
CM2 OS firmware version 14 (and older) has a Y2K issue that affects correct operation in the software. You should upgrade to the latest version.