twin switched socket

Automatic Twin Socket Outlet, 250VAC, 10A, 2 Pole, Skirt Mount

Catalogue Number: 11/2
twin switched socket
Retail
$138.37
RRP (Inc. GST)
Colour White Electric (WE)
  • White Electric 1 PCE

Specifications

hide show
Range of product
Standard Series
Product brand
Clipsal
Quantity per set
set of 2
Cover type
full cover plate
Marking
without marking
Local signalling
without light indicator
Mounting support
skirt
Fixing mode
by screws
[In] rated current
10 A
[Ue] rated operational voltage
250 V AC
Depth
17 mm
Length
125 mm
Width
50 mm
Fixing center
104 mm
Number of poles
1
Standards
  • AS/NZS 3100
  • AS/NZS 3112
  • AS/NZS 3133:approval number S/1
    • Unit Type of Package 1
      PCE
      Number of Units in Package 1
      1
      Package 1 Weight
      0.132 kg
      Package 1 Height
      17 mm
      Package 1 width
      50 mm
      Package 1 Length
      125 mm
      Unit Type of Package 2
      BB1
      Number of Units in Package 2
      5
      Package 2 Weight
      0.676 kg
      Package 2 Height
      108 mm
      Package 2 width
      110 mm
      Package 2 Length
      154 mm
      Unit Type of Package 3
      CAR
      Number of Units in Package 3
      50
      Package 3 Weight
      6.6 kg
      Package 3 Height
      250 mm
      Package 3 width
      214 mm
      Package 3 Length
      338 mm
      Sustainable offer status
      Green Premium product
      EU RoHS Directive
      Compliant
      Mercury free
      Yes
      RoHS exemption information
      Yes
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information
      Environmental Disclosure
      ENVPEP120506EN

      Documents & downloads

      hide show
      Filter items
      • All

      • Product Brochures

      Frequently Asked Questions

      hide show

      Is a blanking plate available for 16/2?

      No. Unfortunately,there is no blank plate available for 16/2.

      Is there a mounting block for 16/2, skirting mount, double power point?

      No, unfortunately the mounting block to suit 16/2 is not available for for the skirting mout double power point.

      For further inforation on our product range please visit https://www.clipsal.com/Trade
       

      What does "1/2 Class System VA" this represent in "Transformer / Line Loss Calculations" document for ION Meters

      Issue
      User wants to determine Percent-loss constant calculations for Transformer / Line Loss Calculations

      Product
      ION7550/ION7650, ION8600, ION8800, ION8650, PM8000, ION7400

      Cause
      The documentation does not describe what 1/2 Class System VA represents.

      Resolution
      1/2 class system VA refers to the VA's at half of the current class of the meter  (for class 20 it is @ 10 amps and for class 2 it is @ 1 amp)

      For more information on the line loss calculation in ION meters, please refer to document 70072-0153-08

       

      What is the double gpo that can be fed separately?

      The C2016/2 is independantly fed where for the outlets on the 16/2 are fed from the same supply. see attachments

      Do the 9001KYSS control stations have a conduit hub?

      Issue:
      9001KYSS cable entry

      Product Line:
      Harmony 9001 Type KYSS 30mm Enclosures

      Environment:
      n/a

      Resolution:
      9001KYSS1 through 9001KYSS6 have a 3/4 inch hub.
      9001KYSS9 has a 1 inch hub.
      9001KYSS12 through 20 have a 1-1/2inch hub.
      9001KYSS25 and 9001KYSS30 have (2x) 1-1/2 inch hubs.

      Descriptions and Pictures of NEMA Designations for Straight Blade Power Connectors












      Descriptions and Pictures of NEMA Designations for Straight Blade Power Connectors
















      What is part number for Brass Adaptor 1/2 NPT male -20mm female?

      The part number for Brass Adaptor 1/2 NPT male -20mm female is - 1235NPT1.
      For further information, please visit:
      https://www.clipsal.com/Trade/Products/ProductDetail?catno=1235NPT1





       

      What is the amount of SF6 gas in 24 kV SF Circuit Breaker range.

      In 24 KV SF Circuit Breaker range, the weight of the SF6 gas per pole for different Circuit Breakers is as follows:
       
      1. SF1 Type 1 – 49 grams 
         
      2. SF1 Type 2 – 112 grams
         
      3. SF2 – 240 grams

      ION 7650/7550: Response time from detecting a disturbance/transient to triggering a digital output

      Issue
      What is the response time from detecting a disturbance/transient to triggering a digital output?

      Product Line
      ION 7650
      ION 7550

      Environment
      Digital Outputs
      Power Quality Detection

      Cause
      To determine the response time of a digital output from a power quality event

      Resolution
      ION7550/7650 can do high-speed digital out triggering since the digital out module will update every half-cycle (i.e. 0.01s for 50Hz). Thus, when the transient module fires AnyTrig, the digital out module will respond within 0.01 seconds.

      However, the actual amount of time from a sag/swell/transient on the line, to the digital output triggering is not a half-cycle. The half-cycle time represents the transient/sag/swell ION modules update rate. The actual chain of events is as follows:
      1. Transient occurs during a sampling window (1/2 cycle) 
      2. DSP processes transient (1/2 cycle)
      3. DSP transfers data to main processor, and main processor fires ION modules (1/2 cycle)
      4. Digital out changes state (1ms for solid state digital outs, 8 to 15 ms for mechanical relays)

      At 50 Hz, the total time for the solid-state digital out to change state based on a transient at the start of the sampling window, is 1.5 cycles + 1ms = 31ms.
      At 60 Hz, the total time for the solid-state digital out to change state based on a transient at the start of the sampling window, is 1.5 cycles + 1ms = 26ms.

      The sag/swell and transient modules can both be used to trigger digital outputs in this case, as they are both high-speed modules.

      You can use a Pulse Merge Module to trigger the digital out from both at once. It is also likely you will need to use a One Shot Timer to turn the digital output off again.

      How to modify/identify a lost password for 1/2 rack CRAC and Full Rack CRAC units

      See attached file

      Utilizing the maximum output capacity of the Symmetra RM 6kVA



      Issue

      How can I use the maximum output capacity of the Symmetra RM 6kva UPS system if it comes with an input power cord with L6-30P?


      Product Line

      Symmetra RM


      Environment

      6kva system only


      Cause

      This document describes how a customer can utilize the full capacity of this UPS system while complying to national electric code (NEC) requirements.


      Resolution

      In order for the Symmetra RM to be utilized to a capacity greater than 5kVA, the input to the unit should be hardwired to 40 amp service in order to meet local wiring code requirements.   Please reference the user manual for details on how to do so.  Also, the UPS would have to be populated with a minimum of three power modules.

      If the load on the UPS is going to be below 5kva, the input power cord that comes with the UPS can be utilized safely.


      Show More