Quantcast

Mureva Box 192 x 164 x 87mm, IP55, Halogen Free

Mureva Box 192 x 164 x 87mm, IP55, Halogen Free

Mureva Box 192 x 164 x 87mm, IP55, Halogen Free

Item Number: 05050

Retail
$120.81
RRP (Inc. GST)

Product Dimensions

Width icon

Width164 mm

Height icon

Height193 mm

Depth icon

Depth87 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Warranty

18 months

Colour code

RAL 7035

Physical

Mercury free

Yes

REACh free of SVHC

Yes

REACh Regulation

Free of Substances of Very High Concern above the threshold

China RoHS Regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

RoHS exemption information

Yes

Toxic heavy metal free

Yes

Cable entry

smooth faces

Device mounting

surface

Height

193 mm

Width

164 mm

Depth

87 mm

IP degree of protection

IP55

IK degree of protection

IK07

Ambient air temperature for operation

-5-40 °C

Others

Package 1 Height

88 mm

Package 1 Length

140 mm

Package 1 Weight

0.38 kg

Package 1 width

162 mm

Box category

big size junction box

Cover fixing

quarter turn screw

Housing material

polypropylene

Internal height

175 mm

Internal width

150 mm

Internal depth

80 mm
Show all specifications

Frequently Asked Questions

hide show

I need to have the mH datas for the motor line chokes of ATV28 and 58 .BR Asli

Goals and Symptoms

I need to have the mH datas for the motor line chokes of ATV28 & 58 .BR Asli

Causes and Fixes

VW3A66501 = 10 mH 4 A
VW3A66502 = 4 mH 10 A
VW3A66503 = 2m H 16 A
VW3A66504 = 1m H 30 A
VW3A66505 = 0,5 mH 60 A
VW3A66506 = 0,3 mH 100 A
VW3A66507 = 0,15 mH 230 A
VW3A66508 = 0,075 mH 370 A
VW3A66509 = 0,050 mH 500 A

What is the meaning of the MBP_MSTR error codes 5050, 5055 and 5056?

Issue
Explanation of the MBP_MSTR error code Hex values of  5050, 5055 and 5056
 
Product Line
140NOE77101, 140NOE77111, 140CPU65xxx
 
Environment
Unity Pro, Concept, ProWORX 32
 
Resolution
 The error code Hex values of 5050, 5055 and 5056 are all similar Ethernet TCP errors. But they do identify where in the TCP connection process the error is occurring.

The error 5050 Is defined as No Network resource. This is pretty much correctly stated. It indicates that the TCP stack does not have any resources free to open the TCP connection. It has a secondary cause in that the module internally, doesn't have a buffer to use to bring the message across from the backplane to the stack. This is that pool of resources that we refer to when we say the module has a pool of 64 connections that are shared between the client and the server functions.

The error 5055 is defined as No Remote Resources- This indicates that the NOE tried to open a connection to the remote device (Target) and that device either did not respond or reset the connection. This also has the added issue that as the EF's keep executing for a device that is not present (not answering) The error will gradually propagate across all connections.

Lastly, The error 5056 defined as Non Operational TCP connection. This is also pretty accurate. The module cannot establish a connection to the device. Often this is seen when a device is not present on the wire when the block starts. It tries to ARP for the address but gets no response or, it simply cannot establish a connection (Port 502 closed). This also can be seen if the Master and Remote Ip addresses are not on the same Network/Subnet address range.

What is the extended rotary handle for a 31104

The part code is 31050

What is the new code for 31050 ?

now =  LV431050

What is the code extended front rotary handle / shaft for an INS250?

Code = 31050

What does WRITE_REG error 6007 indicate when used in a Quantum over Ethernet TCPIP.

This means that the NOE module slot mapping register is set incorrectly.
 
The ADDRFLD pin is an Array of 5 words. The high byte of the first word is the physical slot position in HEX of the Ethernet module. The low byte is the Modbus mapping index if going through a bridge. A setting or 0500 HEX would mean that the NOE that the message is going out on resides in slot 5 and no index is needed for the slave device.
The remaining 4 words are the IP address of the slave device.
Note: If using the embedded port of a Unity Quantum the high byte of the first word should be FE