Acti9 iC60H3 Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 25A, 100mA, A type, 10000A

Home ProductsCircuit ProtectionActi 9Residual current breaker with overcurrent protection (RCBO)

Acti9 iC60H3 Residual current breaker with overcurrent protection (RCBO) 3P+Ns, C Curve, 25A, 100mA, A type, 10000A

Item Number: A9DC2925

Datasheet

Product Dimensions

Width icon

Width54 mm

Height icon

Height112 mm

Depth icon

Depth77.2 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

residual current breaker with overcurrent protection (RCBO)

Physical

[in] rated current

25 A at 30 °C

[ue] rated operational voltage

400/415 V

Control type

toggle

Local signalling

ON/OFF indication

Mounting mode

clip-on

Mounting support

  • DIN rail
  • chassis

Height

112 mm

Width

54 mm

Depth

77.2 mm

Net weight

462 g

Mechanical durability

20000 cycles

Electrical durability

5000 cycles

Connections - terminals

  • screw clamp terminal (top) 1-25 mm² rigid without cable end
  • screw clamp terminal (top) 1-16 mm² flexible

Wire stripping length

  • power circuit: 11 mm for bottom connection
  • power circuit: 14 mm for top connection

Standards

  • AS/NZS 61009.1
  • IEC 61009-1
  • IEC 61009-2-2

Ip degree of protection

IP20

Relative humidity

95 % at 55 °C

Ambient air temperature for operation

-5...60 °C

Ambient air temperature for storage

-25...70 °C

Reach regulation

Free of Substances of Very High Concern above the threshold

Reach free of svhc

Yes

Eu rohs directive

Compliant

Rohs exemption information

Yes

China rohs regulation

 Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental disclosure

ENVPEP2308033EN

Circularity profile

ENVEOLI2308033EN

Others

Commercial status history

  • SESA602958
  • Sun Oct 29 17:35:00 EDT 2023
  • From Unitary Local
  • From 06 to 08

Package 1 bare product quantity

1

Package 2 bare product quantity

16

Circuit breaker application

distribution

Product name

Acti9 iC60 RCBO

Device short name

iC60H3 RCBO

Poles description

3P + Ns

Earthing system

TN

Curve code

C

Earth-leakage sensitivity

100 mA

Breaking capacity

10000 A Icn at 400/415 V

Neutral position

left

Number of protected poles

3

Device location in system

outgoer

Network frequency

50/60 Hz

Network type

AC

Trip unit technology

thermal-magnetic

Residual current tripping technology

voltage dependent

Earth-leakage protection time delay

instantaneous

Earth-leakage protection class

type A

[icw] rated short-time withstand current

Icw: 250 A during 8/20 µs impulse withstand

[ics] rated service breaking capacity

7500 A

Limitation class

3

[ui] rated insulation voltage

500 V

[uimp] rated impulse withstand voltage

4 kV

Surge current

250 A

Suitability for isolation

yes conforming to IEC 61009-1

Comb busbar and distribution block compatibility

YES

9 mm pitches

6

Provision for padlocking

  • padlockable with padlock Ø 4 mm
  • lead seal

Locking options description

ON/OFF locking facilities

Tightening torque

  • power circuit: 2.5...2.5 N.m top
  • power circuit: 2.5...2.5 N.m bottom

Earth-leakage protection

integrated

Test button operating voltage

260...457 V

Operating voltage earthleakage protection

150...457 V

Grid distance

45 mm

Locking options description

handle sealable with cable diameter 1.4mm in OFF or ON position

Tropicalisation

2

Unit type of package 1

PCE

Number of units in package 1

1

Package 1 height

12.7 cm

Package 1 width

6.6 cm

Package 1 length

9 cm

Package 1 weight

539 g

Unit type of package 2

S02

Number of units in package 2

16

Package 2 height

15 cm

Package 2 width

30 cm

Package 2 length

40 cm

Package 2 weight

9.376 kg

Green premium status for reporting

Green Premium product

Packaging made with recycled cardboard

Yes

Packaging without single use plastic

Yes

Sustainable packaging

Yes

Take-back

No

Take-back

No

Product contributes to saved and avoided emissions

No

Recycled metal content at cr level

0

Removable battery

N/A

Carbon footprint (kg.eq.co2 per cr, total life cycle)

11.12920964

Global warming ; total life cycle​

11 kg CO2 eq.

Minimum percentage of recycled plastic content

0
Show all specifications