Quantcast

Is it possible to connect Easergy P5 VT input directly on lines 415V or 240V line?

FAQ000248611

30 January 2023

It is not possible to perform this application and connect secondary P5 VT directly on lines 415/240.

As per P5 documentation, even though the secondary setting VT range is 25/250 V, the voltage withstand is only 276 Vac.
VT P5

And P5 is not designed for a direct VT scheme, and they have to add an interposing VT.