FAQ000246870
23 January 2023
SUMMARY:This article explains how to set the polling rate less than 1 second for Modbus TCP in Aveva Edge
SITUATION: This example is tested in Aveva Edge 2020 R2.
ACTION:This can be achieved by setting up a Standard Driver Sheet and configure a tag to its Read Trigger & Write Trigger to control the polling rate.
And this tag can be associated to a scheduler function to determine the polling rate value.
Example is shown below.