FAQ000219778
15 September 2022
The output voltage type of the delay unit for MN Undervolatge for Compact NSX range is "DC"

Refer the below part numbers for the delay unit and associated MN Undervoltage release for Compact NSX range

You can see all the delay unit associated MN Undervoltage release coils are rated for DC voltage.
For Example - delay unit part number "33682" has input (control circuit voltage) of 200-250 V AC or DC but the output is 250V DC which will connect to 250V DC MN Coil part number "LV429414"