Quantcast

GV2G05 does not line up with GV2P08 terminals when using GV2G45. Is another part required?

FA370585

15 April 2021

Connector diagram in catalogue only shows GV2ME. As the GV2P (and GV2L) are deeper than the GV2ME the terminals will not line up with the terminals of the GV2G05

For GV2P height compensation bracket GV1F03 is required (not shown in diagram). This will raise GV1F03 so the terminals are in line with the terminals of the GV2P.

Datasheet of item below: